INSTALLER:  LEAVE THIS MANUAL WITH THE APPLIANCE.

CONSUMER:  RETAIN THIS MANUAL FOR FUTURE REFERENCE.

NEVER LEAVE CHILDREN OR OTHER AT RISK INDIVIDUALS ALONE WITH THE APPLIANCE.

INSTALLATION AND 

OPERATING INSTRUCTIONS

Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada / 

103 Miller Drive, Crittenden, Kentucky, USA, 41030

Phone 1 (866) 820-8686 • www.continentalfi replaces.com • ask@continentalfi re.on.ca

1.24F

$10.00

SAFETY INFORMATION

!

WARNING

- Do not store or use gasoline or other fl ammable 

vapors and liquids in the vicinity of this or any 

other appliance.

- WHAT TO DO IF YOU SMELL GAS:

•  Do not try to light any appliance.

•  Do not touch any electrical switch; do not use        

any phone in your building.

•  Immediately call your gas supplier from a        

neighbour’s phone.  Follow the gas supplier’s        

instructions.

•  If you cannot reach your gas supplier, call the        

fi re department.

- Installation and service must be performed by a 

qualifi ed installer, service agency or the supplier.

If the information in these instructions 

are not followed exactly, a fi re or 

explosion may result causing property 

damage, personal injury or loss of life.

LA VITRE CHAUDE 

CAUSERA 

DES BRÛLURES.

NE PAS TOUCHER 

LA VITRE  

AVANT QU’ELLE AIT REFROIDI.

 

NE 

JAMAIS LAISSER LES 

ENFANTS TOUCHER LA VITRE.

HOT GLASS WILL CAUSE 

BURNS.

DO NOT TOUCH GLASS UNTIL 

COOLED.

NEVER ALLOW CHILDREN TO 

TOUCH GLASS.

!

DANGER

!

AVERTISSEMENT

A barrier designed to reduce the risk of burns from 

the hot viewing glass is provided with this appliance 

and shall be installed for the protection of children 

and other at-risk individuals.

Une barriére conçu à réduire le risque de brûlures 

causées par le verre chaud est fourni avec l’appareil 

et sera installé pour la protection des enfants et 

d’autres personnes à risque.

This appliance may be installed in an aftermarket, 

permanently located, manufactured home (USA 

only) or mobile home, where not prohibited by 

local codes.

This appliance is only for use with the type of gas  

indicated on the rating plate. This appliance is 

not convertible for use with other gases, unless a 

certifi ed kit is used.

FOR INDOOR USE ONLY

SAFETY

 BARRIER

ÉCRAN DE PROTECTION

CB46NTR / CB46NTRE

NATURAL GAS MODEL

CB46PTR / CB46PTRE

 

PROPANE GAS MODEL

CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS: CSA 2.22 · ANSI Z21.50 FOR VENTED DECORATIVE GAS FIREPLACES.

Summary of Contents for CB46NTR

Page 1: ... supplier If the information in these instructions are not followed exactly a fire or explosion may result causing property damage personal injury or loss of life LA VITRE CHAUDE CAUSERA DES BRÛLURES NE PAS TOUCHER LA VITRE AVANT QU ELLE AIT REFROIDI NE JAMAIS LAISSER LES ENFANTS TOUCHER LA VITRE HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN TO TOUCH GLASS DANGER ...

Page 2: ...RIZONTAL AIR TERMINAL INSTALLATION 30 4 3 2 VERTICAL AIR TERMINAL INSTALLATION 31 4 3 3 RESTRICTING VERTICAL VENTS 32 4 4 VERTICAL THROUGH EXISTING CHIMNEY 33 4 5 MOBILE HOME INSTALLATION 34 4 6 GAS INSTALLATION 35 4 7 OPTIONAL WALL SWITCH 35 5 0 FRAMING 36 5 1 MINIMUM FRAMING DIMENSIONS 37 5 2 MINIMUM ENCLOSURE CLEARANCES 39 5 3 NON COMBUSTIBLE FACING MATERIAL 43 5 4 ALCOVE CLEARANCES 43 5 5 RECE...

Page 3: ... See the section MINIMUM FRAMING DIMENSIONS Side Wall See the section FRAMING See the section VENTING and INSTALLATION See the section RATING PLATE INFORMATION SAFETY BARRIER Batteries must be disposed of according to the local laws and regulations Some batteries may be recycled and may be accepted for disposal at your local recycling center Check with your municipality for recycling instructions ...

Page 4: ...this appliance be modified This appliance must not be connected to a chimney flue pipe serving a separate solid fuel burning appliance Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water Do not operate the appliance with the glass...

Page 5: ...5 W415 1616 C 09 20 17 EN 2 1 DIMENSIONS ...

Page 6: ... cutting a floor or roof joist If the appliance is installed directly on carpeting vinyl tile or other combustible material other than wood flooring the appliance shall be installed on a metal or wood panel extending the full width and depth Some appliances have optional fans or blowers If an optional fan or blower is installed the junction box must be electrically connected and grounded in accord...

Page 7: ...r Column 10 25mb Water Column This appliance is approved for bathroom bedroom and bed sitting room installations and is suitable for mobile home installation PRODUCT CODE CB46NTR AND CB46PTR ONLY No external electricity 110 volts or 24 volts is required for the gas system operation However it is required with the installation of an optional blower Expansion contraction noises during heating up and...

Page 8: ...E WITH GLASS DOORS CERTIFIED WITH THIS UNIT ONLY WARNING THIS FIREPLACE USES AND REQUIRES A FAST ACTING THERMOCOUPLE REPLACE ONLY WITH A FAST ACTING THERMOCOUPLE SUPPLIED BY WOLF STEEL LTD DO NOT ADD ANY MATERIAL TO THE APPLIANCE WHICH WILL COME IN CONTACT WITH THE FLAMES OTHER THAN THAT SUPPLIED BY THE MANUFACTURER WITH THE APPLIANCE MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS DEGAGEMENTS MINIMAUX...

Page 9: ... terminal may be painted with a high temperature paint to match exterior colours Use an outdoor paint suitable for 400 F 200 C Application and performance of paint is the consumer s responsibility Spot testing is recommended NOTE If for any reason the vent air intake system is disassembled reinstall per the instructions provided for the initial installation WARNING RISK OF FIRE MAINTAIN SPECIFIED ...

Page 10: ... Mill Pac High temperature sealant must be ordered separately When using Wolf Steel venting components use only approved Wolf Steel rigid flexible components with the following termination kits wall terminal kit GD 222 GD 222R or 1 12 to 7 12 pitch roof terminal kit GD 110 8 12 to 12 12 roof terminal kit GD 111 flat roof terminal kit GD 112 or periscope kit GD 201 for wall penetration below grade Wi...

Page 11: ...LLATION 16 406MM MINIMUM 40 FT 12M MAXIMUM 3 FT 1M MINIMUM 34 5 8 879MM TOP VENT 8 203MM MINIMUM 34 5 8 879MM 42 5 8 1083MM MINIMUM PLUS RISE 24 610MM MAXIMUM See VENTING section 24 61 0cm 8 20 3cm 34 5 8 87 9cm 42 5 8 108 3cm 16 40 6cm 34 5 8 87 9cm ...

Page 12: ...12 W415 1616 C 09 20 17 EN REAR VENT See VENTING section 40 FT 12M MAXIMUM 3 FT 1M MINIMUM 16 40 6cm MINIMUM 20 508MM MAXIMUM 24 1 8 61 3cm MINIMUM PLUS RISE 24 1 8 61 3cm 20 50 8cm ...

Page 13: ...MAXIMUM 10FT VENT LENGTH 20 50 8cm MAXIMUM 20 50 8cm MAXIMUM 12 MINIMUM T INSTALLATION REAR EXIT INSTALLATION 30 MINIMUM 12 MINIMUM MAXIMUM 10FT VENT LENGTH 6 152mm RISE MINIMUM 50 8cm XIMUM 0 8cm IMUM 3 3 2 CORNER TERMINATION 12 30 5cm MINIMUM TO GRADE 12 30 5cm MINIMUM TO GRADE 30 76 2cm MINIMUM 30 76 2cm MINIMUM 34 5 8 87 9cm The maximum vent length for a corner installation is 20 508mm of hori...

Page 14: ...ther appliance K 6 1 8m 3 0 9m Clearance to a mechanical air supply inlet L 7 2 1m 7 2 1m Clearance above a paved sidewalk or paved driveway located on public property M 12 305mm 12 Clearance under a veranda porch or deck N 16 406mm 16 406mm Clearance above the roof O 2 0 6m 2 0 6m Clearance from an adjacent wall including neighbouring buildings P 8 2 4m 8 2 4m Roof must be non combustible without...

Page 15: ...es the vertical rise equal to or greater than the horizontal run 3 times the vertical rise equal to or greater than the horizontal run 13 2A REAR EXIT Horizontal Termination Vertical Termination Vertical rise is equal to or greater than the horizontal run Vertical rise is less than horizontal run Vertical rise is equal to or greater than the horizontal run Vertical rise is less than horizontal run...

Page 16: ...h horizontal vent lengths Hr and offsets Ho in feet HR combined horizontal vent lengths in feet HO offset factor 03 total degrees of offset 90 in feet VT combined vertical vent lengths in feet 3 7 ELBOW VENT LENGTH VALUES 15 1A FEET INCHES MILLIMETERS 1 0 03 0 5 12 7 15 0 45 6 0 152 4 30 0 9 11 0 279 4 45 1 35 16 0 406 4 90 2 7 32 0 812 8 The first 90 offset has a zero value and is shown in the fo...

Page 17: ...5 4 FT 1 7m hT hR hO 4 5 FT 1 4m 5 4 FT 1 6m 9 9 FT 3m hT vT 9 9 FT 3m 11 FT 3 4m 20 9 FT 6 4m formula 1 hT vT 9 9 FT 3m 11 FT 3 4m formula 2 hT vT 40 fT 12 2m 20 9 FT 6 4m 40 FT 12 2m Since both formulas are met this vent configuration is acceptable See graph to determine the required vertical rise VT for the required horizontal run HT The shaded area within the lines represents acceptable values...

Page 18: ... Since both formulas are met this vent configuration is acceptable The shaded area within the lines represents acceptable values for HT and VT 90 V1 H1 H2 90 Example V1 4 FT 1 2m V2 1 5 FT 0 5m VT V1 V2 4 FT 1 2m 1 5 FT 0 5m 5 5 FT 1 7m H1 2 FT 0 6m H2 1 FT 0 3m H3 1 FT 0 3m H4 1 5 FT 0 5m HR H1 H2 H3 H4 2FT 0 6m 1FT 0 3m 1FT 0 3m 1 5FT 0 5m 5 5 FT 1 7m HO 03 four 90 elbows 90 03 360 90 8 1 FT 2 5...

Page 19: ...hin the lines represents acceptable values for HT and HT HT VT 16 3A For vent configurations requiring more than two 90 elbows the following formulas apply Formula 1 HT VT Formula 2 HT VT 40 feet 12 2m Example V1 9 FT 2 7m V2 6 FT 1 8m VT V1 V2 9FT 2 7m 6FT 1 8m 15FT 4 6m H1 3 FT 0 9m H2 2 FT 0 6m H3 1 5 FT 0 5m HR H1 H2 H3 3FT 0 9m 2FT 0 6m 1 5FT 0 5m 6 5FT 2m HO 03 four 90 elbows 90 03 360 90 8 ...

Page 20: ...90 elbows the following formulas apply Formula 1 HT 3 5VT Formula 2 HT VT 24 75 feet 7 5m Example V1 4 FT 1 2m V2 1 5 FT 0 5m VT V1 V2 4FT 1 2m 1 5FT 0 5m 5 5 FT 1 7m H1 2 FT 0 6m H2 1 FT 0 3m H3 1 FT 0 3m H4 1 5 FT 0 5m HR H1 H2 H3 H4 2FT 0 6m 1FT 0 3m 1FT 0 3m 1 5FT 0 5m 5 5 FT 1 7m HO 03 four 90 elbows one 45 elbow 90 03 90 90 90 90 45 90 9 45 FT 2 9m HT HR HO 5 5FT 1 7m 9 45FT 2 9m 14 95FT 4 6...

Page 21: ...or vent configurations requiring one or more 90 elbows top exit or one or more 90 elbows rear exit the following formulas apply Formula 1 HT VT Formula 2 HT VT 40 feet 12 2m Example V1 5 FT 1 5m V2 6 FT 1 8m V3 10 FT 3 1m VT V1 V2 V3 5FT 1 5m 6FT 1 8m 10FT 3 1m 21 FT 6 4m H1 8 FT 2 4m H2 2 5 FT 0 8m HR H1 H2 8FT 2 4m 2 5FT 0 8m 10 5FT 3 2m HO 03 four 90 elbows 90 03 360 90 8 1 FT 2 5m HT HR HO 10 ...

Page 22: ...ormulas apply Formula 1 HT 3 VT Formula 2 HT VT 40 feet 12 2m Example V1 2 FT 0 6m V2 1 FT 0 3m V3 1 5 FT 0 5m VT V1 V2 V3 2FT 0 6m 1FT 0 3m 1 5FT 0 5m 4 5 FT 1 4m H1 6 FT 1 8m H2 2 FT 0 6m HR H1 H2 6FT 1 8m 2FT 0 6m 8 FT 2 4m HO 03 four 90 elbows 90 03 360 90 8 1 FT 2 5m HT HR HO 8FT 2 4m 8 1FT 2 5m 16 1FT 4 9m HT VT 16 1FT 4 9m 4 5FT 1 4m 20 6FT 6 3m Formula 1 HT 3 5 VT 3 5 VT 3FT 0 9m x 4 5FT 1...

Page 23: ...eflector from inside the top front of the firebox refer to Figure 1 D Place the gasket provided over the 4 102mm flue collar assembly and bend along perforation E From inside the firebox insert the 4 102mm flue collar through the back of the firebox Install the rear exit shield onto the 4 102mm flue collar See REAR ExIT ShIELD section for installation instructions F Secure the flue collar assembly...

Page 24: ... slide the rear exit shield in place by sliding its slotted openings behind the screwheads tighten the two previously loosened screws Refer to the illustration below C Reinstall the door and safety barrier assembly on the appliance refer to the SAFETY SCREEN DOOR REMOVAL AND INSTALLATION section of the manual for detailed instructions 3 12 REAR EXIT SHIELD FOR REAR VENT ONLY NOTE THIS SHIELD IS US...

Page 25: ...W415 1616 B 06 13 16 EN 3 13 TOP ExiT A Remove the safety screen and glass front refer to SAFETy SCREEN DOOR REMOVAL AND INSTALLATION section B Remove the contents from the firebox and set aside you will need the flue collar from the top of the log carton C To ease assembly remove the four hex head screws securing the deflector from inside the top front of the firebox D Remove the single screw fro...

Page 26: ...THE GAS AND ELECTRICAL SUPPLY TO THE APPLIANCE FOR SAFE AND PROPER OPERATION OF THE APPLIANCE FOLLOW THE VENTING INSTRUCTIONS EXACTLY ALL EXHAUST AND INTAKE VENT PIPE JOINTS MUST BE SEALED USING RED RTV HIGH TEMP SILICONE SEALANT W573 0002 NOT SUPPLIED OR BLACK HIGH TEMP MILL PAC W573 0007 NOT SUPPLIED WITH THE EXCEPTION OF THE APPLIANCE EXHAUST FLUE COLLAR WHICH MUST BE SEALED USING MILL PAC IF U...

Page 27: ...ent any materials such as insulation from filling up the 1 25mm air space around the pipe Nail headers between the joist for extra support B Apply a bead of caulking not supplied to the framework or to the Wolf Steel vent pipe shield plate or equivalent in the case of a finished ceiling and secure over the opening in the ceiling A firestop must be placed on the bottom of each framed opening in a r...

Page 28: ...V silicone W573 0002 not supplied C Insert the vent pipes through the firestop maintaining the required clearance to combustibles holding the air terminal lettering in an upright readable position secure to the exterior wall and make weather tight by sealing with caulking not supplied D If more vent pipe needs to be used to reach the fireplace couple them together as illustrated The vent system mu...

Page 29: ...he flashing over the air terminal connector leaving a min 3 4 19mm of the air terminal connector showing above the top of the flashing Slide the flashing underneath the sides and upper edge of the shingles Ensure that the air terminal connector is properly centred within the flashing giving a 3 4 19mm margin all around Fasten to the roof Do not nail through the lower portion of the flashing Make w...

Page 30: ...ht by sealing with caulking not supplied The air terminal mounting plate may be recessed into the exterior wall or siding no greater than the depth of the return flange 26 1A SCREWS 10x2 OUTER RIGID PIPE CAULKING INNER RIGID PIPE SCREWS SELF DRILLING 8x1 2 1 25 4mm OVERLAP SEALANT HI TEMP WARNING RISK OF FIRE DO NOT ALLOW LOOSE MATERIALS OR INSULATION TO TOUCH THE VENT PIPE REMOVE INSULATION TO ALL...

Page 31: ...he flashing over the air terminal connector and slide it underneath the sides and upper edge of the shingles Ensure that the air terminal connector is properly centered within the flashing giving a 3 4 19mm margin all around Fasten to the roof Do NOT nail through the lower portion of the flashing Make weather tight by sealing with caulking Where possible cover the sides and top edges of the flashi...

Page 32: ... KNOT BEFORE THROWING AWAY Vertical installations may display a very active flame If this appearance is not desirable the exhaust outlet may be restricted with a Wolf Steel approved restrictor kit This kit is not recommended for short vertical vent runs Depending on the model and or year of your appliance mounting holes may not exist A If mounting holes exist remove the screws from the firebox top...

Page 33: ...irectly off the appliance Follow vent manufacturer s installation instructions Different manufacturer s venting components must not be combined Once the preferred manufacturer s appliance adaptor has been attached the remainder of the system must be that of the same manufacturer The only exception to this rule is to use Wolf Steel s approved 3 76 2mm flex liner and co linear termination WARNING RI...

Page 34: ...cts contact your local authorized dealer distributor for the appropriate securing kit For mobile home installations the appliance must be fastened in place It is recommended that the appliance be secured in all installations Always turn off the pilot and the fuel supply at the source prior to moving the mobile home After moving the mobile home and prior to lighting the appliance ensure that the lo...

Page 35: ... SUCH AS SPARKS OR OPEN FLAMES SUPPORT GAS CONTROL WHEN ATTACHING GAS SUPPLY PIPE TO PREVENT DAMAGING GAS LINE ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT WITH THE GLASS DOOR OPENED OR REMOVED PURGING OF THE GAS SUPPLY LINE SHOULD BE PERFORMED BY A QUALIFIED SERVICE TECHNICIAN ASSURE THAT A CONTINUOUS GAS FLOW IS AT THE BURNER BEFORE CLOSING THE DOOR ENSURE A...

Page 36: ... METHOD FOR BEHAVIOUR OF MATERIALS IN A VERTICAL TUBE FURNACE AT 1382 F 750 C AND UL763 SHALL BE CONSIDERED NON COMBUSTIBLE MATERIALS MINIMUM CLEARANCE TO COMBUSTIBLES MUST BE MAINTAINED OR A SERIOUS FIRE HAZARD COULD RESULT THE APPLIANCE REQUIRES A MINIMUM ENCLOSURE HEIGHT MEASURE FROM THE APPLIANCE BASE IF STEEL STUD FRAMING KITS WITH CEMENT BOARD ARE PROVIDED OR SPECIFIED IN THE INSTALLATION IN...

Page 37: ...37 W415 1616 C 09 20 17 EN 461 2 118 1cm 35 88 9cm 189 16 47 1cm GAS INLET LOCATION ELECTRICAL CONNECTION ENCLOSURE TOP FINISHING MATERIAL 501 2 128 3cm 5 1 MINIMUM FRAMING DIMENSIONS ...

Page 38: ...ARANCES section Use firestop spacer W500 0096 not supplied Minimum clearance to combustible construction from appliance and vent surfaces Combustible Framing 0 to stand offs 1 25mm to bottom and sides of the vent pipe 3 76mm to top of the vent pipe Combustible Finishing 0 to rear 0 to front face top and sides Top Exit 50 1 2 1283mm to combustible enclosure top from base of the appliance 54 1372mm ...

Page 39: ...28 3cm TOP EXIT ENCLOSURE The appliance requires a minimum enclosure height of 50 1 2 1283mm For temperature requirements the enclosure space around and above the appliance must be left unobstructed See MINIMUM FRAMING DIMENSION section for details on reducing vent pipe top clearances These perameters also apply to the illustrations found in the MINIMUM ENCLOSURE CLEARANCES section NOTE The vent s...

Page 40: ... PLUSRISE COMBUSTIBLE NON COMBUSTIBLE 1 25mm 3 76mm BRICK 0 0MM IF NON COMBUSTIBLE FINISHINGISUSED SUCHASBRICK ANDSTONE 7 178mm PLUSRISE 10 20 254mm 508mm VENTRUN 415 8 105 7cm MINIMUM 1 10 25mm 254mm VENTRUN 345 8 87 9cm For rear vent termination not exceeding 10 254mm of horizontal vent run 241 8 612mm MINIMUM PLUSRISE 24 1 8 61 3cm MINIMUM PLUS RISE NOTE The vent shield is telescopic and must b...

Page 41: ...LE NON COMBUSTIBLE 3 76mm BRICK 0 0MM IF NON COMBUSTIBLE FINISHINGISUSED SUCHASBRICK ANDSTONE 7 COMBUSTIBLE NON COMBUSTIBLE 1 25mm 3 76mm BRICK 0 0MM IF NON COMBUSTIBLE FINISHINGISUSED SUCHASBRICK ANDSTONE 7 178mm 415 8 105 7cm 10 20 254mm 508mm VENTRUN 111 2 292mm 241 8 61 3cm MINIMUM PLUSRISE 345 8 879mm 345 8 87 9cm 24 1 8 61 3cm MINIMUM PLUS RISE NOTE The vent shield is telescopic and must be ...

Page 42: ...cted MAXIMUM REAR VENT CLEARANCES EXAMPLE 2 241 8 61 3cm MINIMUM PLUSRISE COMBUSTIBLE NON COMBUSTIBLE 1 25mm 3 76mm BRICK 0 0MM IF NON COMBUSTIBLE FINISHINGISUSED SUCHASBRICK ANDSTONE 7 178mm 415 8 105 7cm 10 20 254mm 508mm VENTRUN 111 2 292mm 345 8 879mm 345 8 87 9cm 24 1 8 613MM MINIMUM PLUS RISE NOTE The vent shield is telescopic and must be adjusted to shield the full depth of the combustible ...

Page 43: ...r all three sides If greater projections are desired increase the clearance to the sides and top by 2 51mm for every additional 1 25mm of projection If using an optional surround the same rule applies starting from the top of the surround Ensure clearances are maintained for surround removal as it must lift off the appliance for maintenance NON COMBUSTIBLE FACING MATERIAL GLASS DOOR TOP OF APPLIAN...

Page 44: ...the electronics or other materials will be reduced Follow mantel height and depth instructions for proper clearances NOTE Increasing the horizontal length of the mantel will further reduce the intensity of heat on the electronics B Refer to MINIMUM MANTEL CLEARANCES section for more detailed mantel clearance information Before placing anything above a heat source it is advisable to follow proper c...

Page 45: ...RANCES I E BACK SIDE TOP VENT MANTEL FRONT ETC ARE CLEARLY MAINTAINED WHEN USING PAINT OR LACQUER TO FINISH THE MANTEL THE PAINT OR LACQUER MUST BE HEAT RESISTANT TO PREVENT DISCOLOURATION 73 1 5 6 MINIMUM MANTEL CLEARANCES M A N T E L H E I G H T 0 2 50 8mm 2 4 6 8 10 12 MANTEL DEPTH INCHES 4 101 6mm 6 152 4mm 10 254mm 12 30 5cm 8 203 2mm 5 7 NAILING TAB INSTALLATION 55 3 A To determine the final ...

Page 46: ...risk of burns from the hot viewing glass is provided for the appliance and shall be installed Before the glass door can be removed the safety screen must be removed Lift the safety screen off the 4 pins tilt the top forward and remove from the appliance SAFETY SCREEN SAFETY SCREEN 46 W415 1616 B 06 13 16 EN 6 0 fiNiShiNG WARNING RISK OF FIRE NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE IF FIN...

Page 47: ...fully grip the sides of the door lifting it off the appliance NOTE These spring latches make up the spring relief system for the appliance Ensure they open freely and close sealed Reverse these steps to reinstall the safety screen and door Ensure safety screen is installed correctly 6 2 FRONT HOOD INSTALLATION HOOD SIDE VIEW A Safety door and screen must be removed B Remove the securing screws fro...

Page 48: ...JURY LOGS MUST BE PLACED IN THEIR EXACT LOCATION IN THE APPLIANCE DO NOT MODIFY THE PROPER LOG POSITIONS SINCE APPLIANCE MAY NOT FUNCTION PROPERLY AND DELAYED IGNITION MAY OCCUR THE LOGS ARE FRAGILE AND SHOULD BE HANDLED WITH CARE 76 1A C Place the right log W135 0645 onto the two studs located on the right side of the log support D Place the left crossover log W135 0546 onto the pin located in th...

Page 49: ... cause an incorrect flame pattern carbon deposits and delayed ignition PHAZERTM logs glow when exposed to direct flame Use only certified glowing embers and PHAZERTM logs available from your authorized dealer distributor 6 4 GLOWING EMBERS 6 5 LOGO PLACEMENT 97 1A Remove the backing of the logo supplied and place on the glass viewing door as indicated 12 7mm LOGO 12 7mm E Place the right crossover...

Page 50: ...nt of the appliance to the battery housing F Place the battery housing into the control compartment ensure that the battery housing is placed in a clean and easily accessible location G Reinstall the safety screen The safety screen must be installed at all times during the appliance operation H Turn the gas and electrical power back on to begin operating the appliance WARNING ENSURE THE GAS AND EL...

Page 51: ...e from the wire harness to the thermodisc E Attach the two 1 4 connectors black and red from the wire harness to the blower F Install the clear bumpers supplied onto the bottom of the blower to avoid the blower rubbing against the floor of the appliance G Pivot the blower into the bottom of the appliance ensuring the gasket remains in place between the blower and outer shell while sliding the blow...

Page 52: ...S TO THE ON OFF SWITCH AND CONNECT TO AN OPTIONAL THERMOSTAT IPI BOARD DC SUPPLY TRANSFORMER VALVE ELECTRONIC OFF ON This appliance comes equipped with a battery back up If this back up is used install 4AA batteries not supplied into the holder and connect to the wire harness OPTIONAL NOTE The battery holder was supplied with your appliance but not connected In an event of a power failure install ...

Page 53: ... all gas to the fireplace Open windows Do not try to light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department LIGHTING INSTRUCTIONS A Stop Read the above safety information on this label B Remove batteries ...

Page 54: ... pilot burner to be lit until the thermo couple has cooled Allow approximately 60 seconds for the thermocouple to cool When lighting and re lighting the gas knob cannot be turned from pilot to off unless the knob is depressed slightly A Stop Read the above safety information on this label B Turn off all electric power to the appliance C Turn the gas knob clockwise to off D Wait five 5 minutes to c...

Page 55: ...e same as above using screw B Gauge should read as described on the chart below Check pressure with main burner operating on HI AFTER TAKING PRESSURE READINGS BE SURE TO TURN SCREWS CLOCKWISE FIRMLY TO RESEAL DO NOT OVERTORQUE Leak test with a soap and water solution Prior to pilot adjustment ensure that the pilot assembly has not been painted If overspray or painting of the pilot assembly has occ...

Page 56: ...tronic intermittent pilot ignition IPI to a standing pilot for cold climates The anti condensation control standing pilot is located in the center of the control panel Using your finger flip the switch up for standing pilot or down for intermittent pilot ignition Turning the ACS switch on will allow the pilot flame burning to burn continuously This mode will minimize the condensation which forms o...

Page 57: ...ot flame is large enough to engulf the flame sensor and or thermocouple thermopile as well as reaches the burner E Replace the cleaned logs rocks or glass Failure to properly position the media may cause carbon which can be distributed inside of firebox and on exterior surfaces surrounding vent termination F Check to see that the main burner ignites completely on all openings when turned on A 5 to...

Page 58: ...lso gently remove any build up on the pilot assembly including if equipped thermopile thermocouple flame sensor and igniter NOTE Clean flame sensor using a fine emery cloth or a synthetic scrub pad such as Scotch Brite to remove any oxides Clean the pilot assembly using a vacuum with a soft brush attachment It is important that the pilot assembly is not painted Inspect all accessible gaskets and re...

Page 59: ...E CAUSERA DES BRÛLURES NE PAS TOUCHER LA VITRE AVANT QU ELLE AIT REFROIDI NE JAMAIS LAISSER LES ENFANTS TOUCHER LA VITRE AVERTISSEMENT 5 5A This appliance is factory equipped with 4mm tempered glass Use only replacement parts available from your appliance manufacturer DO NOT SUBSTITUTE MATERIALS WARNING DO NOT USE SUBSTITUTE MATERIALS GLASS MAY BE HOT DO NOT TOUCH GLASS UNTIL COOLED CARE MUST BE T...

Page 60: ...Installation date of appliance Part number Description of part Finish PARTS PART NUMBERS AND AvAiLABiLiTy ARE SUBjECT TO ChANGE wiThOUT NOTiCE PARTS iDENTifiED AS STOCKED wiLL BE DELivERED wiThiN 2 TO 5 BUSiNESS DAyS fOR MOST DELivERy DESTiNATiONS PARTS NOT iDENTifiED AS STOCKED wiLL BE DELivERED wiThiN A 2 TO 4 wEEK PERiOD 41 2A FAILURE TO POSITION THE PARTS IN ACCORDANCE WITH THIS MANUAL OR FAIL...

Page 61: ...5 0620 W135 0645 W485 0042 W361 0016 W200 0541 W010 3489 W500 0837 W290 0054 W290 0282 W018 0181 SER W010 3554 RP4 ACS SIT SAFETY SCREEN SAFETY BARRIER ASSEMBLY COMPLETE DOOR ASSEMBLY FRONT BAFFLE HOOD TOP FINISHING TRIM LEFT CROSSOVER LOG GL 699 RIGHT CROSSOVER LOG GL 699 LEFT SIDE LOG REAR LOG GL 699 RIGHT SIDE LOG LOG LOCATING PIN GL 699 GLOWING EMBERS GL 699 AIR OPENING COVER AIR COLLAR AND PL...

Page 62: ...2 43 45 W750 0270 SWITCH WIRE YES 12 13 16 A B46NTR ELECTRONIC VALVE TRAIN ASSEMBLY 43 36 31 30 28 26 37 23 21 20 40 38 39 44 41 44 40 39 38 37 36 30 29 28 27 33 31 32 45 34 43 42 41 W335 0039 PILOT HOOD YES W455 0070 PILOT ORIFICE 62 NG YES W455 0068 PILOT ORIFICE 35 P YES W720 0062 PILOT TUBE w FITTINGS YES W240 0013 ELECTRODE w WIRE YES 35 W350 0799 PILOT SHIELD W245 0037 FLAME SENSOR w WIRE YE...

Page 63: ...21 20 22 25 33 35 42 39 38 37 36 35 34 31 30 28 27 29 32 40 43 W357 0001 PUSH BUTTON IGNITOR 12 13 16 A 41 W350 0799 PILOT SHIELD 35 33 41 W750 0112 SWITCH WIRE 43 W010 0799 PILOT ASSEMBLY P 42 W010 0798 PILOT ASSEMBLY NG 42 YES PILOT HOOD W335 0039 W455 0070 PILOT ORIFICE 62 NG YES W290 0029 PILOT GASKET W680 0005 THERMOCOUPLE YES W240 0006 SER ELECTRODE w WIRE YES W720 0062 PILOT TUBE w FITTINGS...

Page 64: ...D TRIM LS BT46K BEVELLED TRIM RS BT46K 10 9 8 BT46K 5 6 GD873KT 7 50 51 3 4 PRPB46 6 7 8 9 10 11 12 13 W715 1087 SER BEVELLED TRIM TOP BT46K W062 0059 SER BLOWER AUB YES KB 35 VARIABLE SPEED SWITCH YES W690 0002 THERMODISC YES W200 0622 W200 0586 UPPER COVER H Z46F LOWER COVER H Z46F W475 1132 BK2GL SIDE PORCELAIN PANEL W475 1249 BK2GL REAR PORCELAIN PANEL W475 1247 W475 1246 W475 1248 FIBRE BRICK...

Page 65: ... plugs into the module Remove and verify continuity of each wire in wiring harness Improper switch wiring Troubleshoot the system with the simplest ON OFF switch Module is not grounded Verify the valve and pilot assemblies are properly grounded to the metal chassis of the appliance or log set Pilot sparks but will not light Gas supply Verify that the incoming gas line ball valve is Open Verify tha...

Page 66: ...lit but burner will not turn on Wiring Connection Inspect all wires ensure good tight connections Verify that all wiring is installed exactly as specified Wiring harness Inspect the wiring harness and verify the harness is tightly connected to the module Verify that all wires are connected in the right order See WIRING DIAGRAM section Exhaust fumes smelled in room headaches Appliance is spilling C...

Page 67: ... wall switch terminals if main burner lights replace switch thermostat Wall switch wiring is defective Disconnect the switch wires connect a jumper wire across terminals 1 3 if the main burner lights check the wires for defects and or replace wires Main burner orifice is plugged Remove stoppage in orifice Faulty valve Replace Pilot goes out while standing Main burner is in OFF position Gas piping ...

Page 68: ...ked Ensure air shutter opening is free of lint or other obstructions Flame is impinging on the logs or combustion chamber Check that the logs are correctly positioned Open air shutter to increase the primary air Check the input rate check the manifold pressure and orifice size as specified by the rating plate values Check that the door gasketing is not broken or missing and that the seal is tight ...

Page 69: ...smelled in room headaches Appliance is spilling Ensure exhaust bracket gasket seal Check door seal and relief flap seal Check for chimney blockage Check that chimney is installed to building code Room is in negative pressure increase fresh air supply Check cap gasket on the flue pipe assembly Remote wall switch is in OFF position main burner comes on when gas knob is turned to ON position Wall switc...

Page 70: ...ings nearby trees hills mountains inadequate vents or ventilation excessive venting configurations insufficient makeup air or negative air pressures which may or may not be caused by mechanical systems such as exhaust fans furnaces clothes dryers etc Any damages to appliance combustion chamber heat exchanger brass trim or other components due to water weather damage long periods of dampness condensa...

Page 71: ...16 0 NOTES 44 1 ...

Page 72: ...adienne Montréal Québec H4T 1A3 24 Napoleon Road Barrie Ontario Canada L4M 0G8 214 Bayview Drive Barrie Ontario Canada L4N 4Y8 103 Miller Drive Crittenden Kentucky USA 41030 Phone 1 866 820 8686 continentalfireplaces com ...

Page 73: ...s causées par le verre chaud est fourni avec l appareil et sera installé pour la protection des enfants et d autres personnes à risque CONSIGNES DE SÉCURITÉ AVERTISSEMENT N entreposez pas et n utilisez pas d essence ou autres liquides et vapeurs inflammables à proximité de cet ap pareil ou tout autre appareil QUE FAIRE SI VOUS DÉTECTEZ UNE ODEUR DE GAZ N allumez aucun appareil Ne touchez à aucun i...

Page 74: ...VACUATION 102 4 3 1 INSTALLATION DE LA TERMINAISON HORIZONTALE 102 4 3 2 INSTALLATION DE LA TERMINAISON VERTICALE 103 4 3 3 RENSTREIGNANT DES ÉVENTS VERTICAUX 104 4 4 TERMINAISON VERTICALE À TRAVERS UNE CHEMINÉE EXISTANTE 105 4 5 INSTALLATION DANS UNE MAISON MOBILE 106 4 6 BRANCHEMENT DU GAZ 107 4 7 INTERRUPTEUR MURAL OPTIONNEL 107 5 0 OSSATURE 108 5 1 DIMENSIONS MINIMALES DE L OSSATURE 109 5 2 DÉ...

Page 75: ...tion DIMENSIONS MINIMALES DE L OSSATURE Mur latéral Voir la section OSSATURE Voir les sections ÉVACUATION et INSTALLATION Voir la section INSTALLATION DES PERSIENNES ÉCRAN DE PROTECTION Les piles doivent être mises au rebut conformément aux lois et à la réglementation locales Certaines piles peuvent être recyclées dans votre centre de recyclage local Renseignez vous auprès de votre municipalité au...

Page 76: ...rovenant des tapis literie etc L emplacement de l appareil doit être gardé libre de tous matériaux combustibles essence ou autres liquides et vapeurs inflammables Cet appareil ne devra être modifié en aucun cas Cet appareil ne doit pas être raccordé au conduit d une cheminée desservant un autre appareil de chauffage à combustible solide N utilisez pas cet appareil si une partie quelconque a été subm...

Page 77: ...77 W415 1616 C 09 20 17 FR 2 1 DIMENSIONS ENTRÉE DE GAZ ÉCRAN DE PROTECTION ...

Page 78: ...ur une surface de vinyle ou tout autre revêtement de plancher combustible autre que le bois l appareil devra être monté sur un panneau continu de métal ou de bois se prolongeant sur toute la largeur et la profondeur Certains appareils ont une soufflerie ou un ensemble de deux souffleries optionnel Si la soufflerie ou l ensemble de deux souffleries optionnel est installé la boîte de dérivation doit...

Page 79: ...areil est approuvé pour installation dans les salles de bain les chambres à coucher ou les chambres studio et convient pour installation dans les maisons mobiles CODES PRODUITS CB46NTR ET CB46PTR SEULEMENT Aucune alimentation électrique externe 110 volts ou 24 volts n est requise pour le fonctionnement du système Toutefois c est requis avec l installation d une soufflerie optionnelle Les bruits ca...

Page 80: ... 000 BTU h MANIFOLD PRESSURE 3 5 9MB WATER COLUMN MANIFOLD PRESSURE 10 25MB WATER COLUMN PRESSION AU COLLECTEUR 3 5 9 MB D UNE COLONNE D EAU PRESSION AU COLLECTEUR 10 25MB D UNE COLONNE D EAU MINIMUM SUPPLY PRESSURE 4 5 11MB WATER COLUMN MINIMUM SUPPLY PRESSURE 11 27MB WATER COLUMN PRESSION D ALIMENTATION MINIMALE 4 5 11MB D UNE COLONNE D EAU PRESSION D ALIMENTATION MINIMALE 11 27MB D UNE COLONNE ...

Page 81: ... couleurs extéri eures utilisez une peinture extérieure pour 400 f 200 c application et performance de la peinture est la responsabilité du consommateur Spot test est recommandé NOTE Si pour une raison quelconque le système d évents de prise d air est démonté réinstallez le selon les instructions fournies dans l installation initiale 7 1E AVERTISSEMENT RISQUE D INCENDIE CONSERVEZ LES DÉGAGEMENTS N...

Page 82: ...minaison murale GD222 GD222R ou l ensemble de terminaison pour toit de pente 1 12 à 7 12 GD110 l ensemble de terminaison pour toit de pente 8 12 à 12 12 GD111 l ensemble de terminaison pour toit plat GD112 ou l ensemble périscopique GD201 pour pénétration des murs sous le niveau du sol lorsque vous utilisez des conduits flexibles conjointement avec les différentes terminaisons utilisez l ensemble d...

Page 83: ...NSTALLATIONS TYPIQUES D ÉVENTS ÉVACUATION SUR LE DESSUS 16 40 6cm MINIMUM 40 FT 12M MAXIMUM 3 FT 1M MINIMUM 34 5 8 87 9cm Voir la section ÉVACUATION 8 20 3cm MINIMUM 42 5 8 108 3cm MINIMUM PLUS LA PENTE 24 61 0cm MAXIMUM 34 5 8 87 9cm ...

Page 84: ...40 FT 12M MAXIMUM 3 FT 1M MINIMUM 24 1 8 61 3cm 16 40 6cm MINIMUM 20 50 8cm MAX 24 1 8 61 3cm PLUS LA PENTE ÉVACUATION SUR L ARRIÈRE 84 W415 1616 C 09 20 17 FR Voir la section ÉVACUATION ...

Page 85: ...ion de 45 Dans ce cas une pente de zéro pouce est acceptable Cependant il est conseillé de conserver une pente ascendante de 6 152mm Voir les illustrations ci dessous 30 MINIMUM 12 MINIMUM TOP EXIT INSTALLATION REAR EXIT 30 MINIMUM MAXIMUM 10FT VENT LENGTH 20 50 8cm MAXIMUM 20 50 8cm MAXIMUM 50 8cm AXIMUM 12 MINIMUM ION D UNE ÉVACUA UR LE DESSUS INSTALLATION D UNE ÉVACUA TION À L ARRIÈRE 30 MINIMU...

Page 86: ... voir le tableau pour les dimensions d un mur plus large R 6 1 8m 6 1 8m voir le tableau pour les dimensions d un mur plus profond la terminaison ne doit pas être installée sur quelconque mur ayant une ouverture entre la terminaison et le côté ouvert de la structure S 12 304 8mm 12 304 8mm dégagement sous un balcon couvert Δ Pour les structures comportant trois murs et un toit la terminaison doit ...

Page 87: ... verticale plus grande ou égale à la course horizontale 3 5 CHARTE D APPLICATION DES ÉVACUATIONS 13 2A ÉVACUATION À L ARRIÈRE Terminaison horizontale Terminaison verticale La course verticale est plus grande ou égale à la course horizontale La course verticale est plus petite que la course horizontale La course verticale est plus grande ou égale à la course horizontale La course verticale est plus...

Page 88: ...horizontales combinées en pieds HO facteur de la valeur d une déviation 0 03 du total des degrés de déviation 90 en pieds VT longueur des courses verticales combinées en pieds 15 1A PIEDS POUCES MILLIMÈTRES 1 0 03 0 5 12 7 15 0 45 6 0 152 4 30 0 9 11 0 279 4 45 1 35 16 0 406 4 90 2 7 32 0 812 8 La première déviation de 90 a une valeur zéro et est illustrée dans la formule comme 90 88 W415 1616 C 0...

Page 89: ... plus d un coude de 90 les formules suivantes s appliquent Formule 1 HT VT Formule 2 HT VT 40 pieds 12 2m Exemple V1 3 PI 0 9m V2 8 PI 2 4m VT V1 V2 3PI 0 9m 8PI 2 4m 11PI 3 4m H1 2 5 PI 0 8m H2 2 PI 0 6m HR H1 H2 2 5PI 0 8m 2PI 0 6m 4 5 PI 1 4m HO 0 03 trois coudes 90 90 0 03 270 90 5 4 PI 1 6m HT HR HO 4 5PI 1 4m 5 4PI 1 6m 9 9 PI 3m HT VT 9 9PI 3m 11PI 3 4m 20 9 PI 6 4m Formule 1 HT VT 9 9PI 3m...

Page 90: ...eux formules sont respectées cette configuration d évacuation est acceptable La section ombragée à l intérieur des lignes représente des valeurs acceptables pour HT et VT 90 V1 H1 H2 90 Exemple V1 4 PI 1 2m V2 1 5 PI 0 5m VT V1 V2 4PI 1 2m 1 5PI 0 5m 5 5 PI 1 7m H1 2 PI 0 6m H2 1 PI 0 3m H3 1 PI 0 3m H4 1 5 PI 0 5m HR H1 H2 H3 H4 2 PI 0 6m 1 PI 0 3m 1 PI 0 3m 1 5 PI 0 5m 5 5 PI 1 7m HO 0 03 quatre...

Page 91: ...r des lignes représente des valeurs acceptables pour HT et VT HT VT 16 3A Lorsque la configuration de l évacuation exige plus qu un coude de 90 les formules suivantes s appliquent Formule 1 HT VT Formule 2 HT VT 40 pieds 12 2m Exemple V1 9 PI 2 7m V2 6 PI 1 8m VT V1 V2 9 PI 2 7m 6 PI 1 8m 15 PI 4 6m H1 3 PI 0 9m H2 2 PI 0 6m H3 1 5 PI 0 5m HR H1 H2 H3 3PI 0 9m 2PI 0 6m 1 5PI 0 5m 6 5PI 2m HO 0 03 ...

Page 92: ...ivantes s appliquent Formule 1 HT 3 5VT Formule 2 HT VT 24 75 pieds 7 5m Exemple V1 4 PI 1 2m V2 1 5 PI 0 5m VT V1 V2 4PI 1 2m 1 5PI 0 5m 5 5 PI 1 7m H1 2 PI 0 6m H2 1 PI 0 3m H3 1 PI 0 3m H4 1 5 PI 0 5m HR H1 H2 H3 H4 2PI 0 6m 1PI 0 3m 1PI 0 3m 1 5PI 0 5m 5 5PI 1 7m HO 0 03 quatre coudes 90 un coude 45 90 0 03 90 90 90 90 45 90 9 45 PI 2 9m HT HR HO 5 5PI 1 7m 9 45PI 2 9m 14 95PI 4 6m HT VT 14 95...

Page 93: ... formules suivantes s appliquent Formule 1 HT VT Formule 2 HT VT 40 pieds 12 2m Exemple V1 5 PI 1 5m V2 6 PI 1 8m V3 10 PI 3 1m VT V1 V2 V3 5PI 1 5m 6PI 1 8m 10PI 3 1m 21PI 6 4m H1 8 PI 2 4m H2 2 5 PI 0 8m HR H1 H2 8PI 2 4m 2 5PI 0 8m 10 5PI 3 2m HO 0 03 quatre coudes 90 90 0 03 360 90 8 1 PI 2 5m HT HR HO 10 5PI 3 2m 8 1PI 2 5m 18 6PI 5 7m HT VT 18 6PI 5 7m 21PI 6 4m 39 6PI 12 1m Formule 1 HT 3 5...

Page 94: ... s appliquent Formule 1 HT 3 VT Formule 2 HT VT 40 pieds 12 2m Exemple V1 2 PI 0 6m V2 1 PI 0 3m V3 1 5 PI 0 5m VT V1 V2 V3 2PI 0 6m 1PI 0 3m 1 5PI 0 5m 4 5PI 1 4m H1 6 PI 1 8m H2 2 PI 0 6m HR H1 H2 6PI 1 8m 2PI 0 6m 8 PI 2 4m HO 0 03 quatre coudes 90 90 0 03 360 90 8 1 PI 2 5m HT HR HO 8PI 2 4m 8 1PI 2 5m 16 1 PI 4 9m HT VT 16 1PI 4 9m 4 5PI 1 4m 20 6 PI 6 3m Formule 1 HT 3VT 3VT 3 PI 0 9m x 4 5 ...

Page 95: ...3 quatre coudes 90 un coude 45 90 0 03 360 45 90 6 75 PI 2 1m HT HR HO 12 75PI 3 9m 6 75PI 2 1m 19 5PI 5 9m HT VT 19 5 PI 5 9m 6 5 PI 2m 26 PI 7 9m Formule 1 HT 3 VT 3 VT 3PI 0 9m x 6 5PI 2m 19 5PI 5 9m 19 5 PI 5 9m 19 5 PI 5 9m Formule 2 HT VT 40 PI 12 2m 26 PI 7 9m 40 PI 12 2m Puisque les deux formules sont respectées cette configuration d évacuation est acceptable 3 11 ÉvACUATiON À L ARRièRE WA...

Page 96: ...sant sa ouvertures fendues derrière les têtes de vis serrez les deux vis précédemment desserrées Se référer au illustration ci dessous C Réinstaller la porte et la sécurité ensemble de barrière sur l appareil se référer à la ENLÈVEMENT ET INSTALLATION DE LA PORTE ET L ÉCRAN DE PROTECTION section du manuel pour les instructions détaillées 3 12 ARRIÈRE BOUCLIER DE SORTIE POUR L APPLICATION DE VENTIL...

Page 97: ...Réinstaller la plaque de couvercle d extérieur sans knockout sur la collet d évacuation 7 178mm et fixez K De l intérieur de la chambre de combustion installez le collet d évacuation de 4 102mm à travers la haut de la chambre de combustion et des quatre vis à tête 3 8 NOTE Ne serrez pas trop les vis Il suffit d appuyer le joint d étanchéité contre la chambre de combustion NOTE Cet appareil a été l...

Page 98: ... NE SERREZ PAS LA GAINE FLEXIBLE RISQUE D INCENDIE D EXPLOSION OU D ASPHYXIE SI L ENSEMBLE DU SYSTÈME DE CONDUIT D ÉVENT N EST PAS ADÉQUATEMENT SOUTENU IL RISQUE DE FLÉCHIR OU DE SE SÉPARER UTILISEZ DES SUPPORTS DE CONDUIT ET RACCORDEZ LES SECTIONS DE CONDUITS SELON LES INSTRUCTIONS D INSTALLATION RISQUE D INCENDIE ÉVITEZ QUE L ISOLANT TOUCHE AU CONDUIT D ÉVACUATION RETIREZ L ISOLANT POUR PERMETTR...

Page 99: ...écran protecteur doit être installer pour protéger toute la profondeur de la pénétration de la paroi combustible La longueur de l écran protecteur peut être taillé pour des murs combustibles qui ont moins de 6 152 mm d épaisseur NOTE Pliez les onglets pour les dégagements latéraux réduits ou déplacer le bouclier Meilleurs jeux réduits A Appliquez un joint de calfeutrage non fourni tout autour de l...

Page 100: ...iptions étant à l endroit et lisibles fixez la terminaison au mur extérieur et rendez la étanche en scellant à haute température rtv rouge W573 0002 non fourni D Si plus de sections de gaine doivent être utilisées pour atteindre l appareil raccordez les ensemble tel qu illustré le système d évacuation doit être soutenu à environ tous les 3 pieds 0 9m pour les courses verticales et horizontales util...

Page 101: ... 2 3 RACCORDEMENT DEs ÉvENTs À L APPAREiL A fixez le support de toit au toit à l aide des vis fournies le support de toit est optionnel dans ce cas l évent doit être supporté adéquatement soit en utilisant une méthode alternative se conformant aux normes des autorités compétentes soit en utilisant le support de toit optionnel B Étirez la gaine flexible intérieure à la longueur requise Glissez la ga...

Page 102: ...Installez le premier évent et fixez le en utilisant un minimum de 3 vis autoperceuses Procédez de la même façon avec l évent rigide extérieur C Insérez les deux évents dans l espaceur coupe feu en respectant les dégagements aux combustibles requis En soutenant la terminaison les inscriptions étant à l endroit et lisibles fixez la au mur extérieur et rendez la étanche en la scellant avec du calfeut...

Page 103: ...n centrée dans le solin en laissant une marge de 3 4 19mm tout autour Fixez le au toit NE clouez PAS à travers la partie inférieure du solin Imperméabilisez le en le scellant avec du calfeutrage Si possible recouvrez les côtés et le bord supérieur du solin avec des matériaux de couvertures G Appliquez un généreux joint de calfeutrage à l épreuve de l eau à 2 51mm au dessus du solin Installez le co...

Page 104: ...CE SAC N EST PAS UN JOUET NOEUD AVANT DE JETER Installations verticales peuvent afficher une flamme très active Si cet aspect n est pas souhaitable la sortie d échappement peut être restreinte avec un kit de bride de Wolf Steel approuvé Ce kit n est pas recommandé pour les longueurs de conduit d évacuation vertical court Selon le modèle et année de votre appareil les trous de fixation peut ne pas ...

Page 105: ...du fabricant du système d évacuation Des composants d évacuation de différents fabricants ne doivent pas être combinés Une fois que l adaptateur de votre choix est installé le reste du système d évacuation doit provenir du même fabricant La seule exception à cette règle est l usage du système de conduit flexible de 3 76 2mm et de terminaison colinéaire Wolf Steel RISQUE D INCENDIE LES CONFIGURATIO...

Page 106: ... la sécurisation kit lors d une installation dans une maison mobile l appareil doit être fixé au plancher Éteignez toujours la veilleuse et l alimentation en gaz à la source avant de déplacer la maison mobile après avoir déplacé la maison mobile et avant d allumer l appareil assurez vous que les bûches sont placées correctement cet appareil est certifié pour être installé dans une maison mobile inst...

Page 107: ...e gaz de 3 8 l appareil est muni d une soupape d arrêt manuelle pour fermer l alimentation en gaz C Branchez le gaz en conformité avec les codes locaux en l absence de codes locaux l installation doit être conforme au code d installation du gaz can cSa B149 1 dans sa version pour le canada ou le national fuel Gas code anSi Z223 1 nfPa 54 pour les États unis D lorsque vous manipulez des conduites d...

Page 108: ...LES AFIN D ÉVITER UN RISQUE D INCENDIE LES DÉGAGEMENTS MINIMAUX AUX MATÉRIAUX COMBUSTIBLES DOIVENT ÊTRE MAINTENUS L ENCEINTE DE L APPAREIL DOIT RESPECTER LA HAUTEUR MINIMALE REQUISE MESUREZ À PARTIR DE LA BASE DE L APPAREIL SI DES ENSEMBLES DE MONTANTS EN ACIER AVEC PANNEAU DE CIMENT SONT FOURNIS OU SPÉCIFIÉ DANS LES INSTRUCTIONS D INSTALLATION ILS DOIVENT ÊTRE INSTALLÉS SI SPÉCIFIÉ DANS LES INSTR...

Page 109: ...415 1616 C 09 20 17 FR 461 2 118 1cm 35 88 9cm 189 16 47 1cm RACCORDEMENT ÉLECTRIQUE DESSUS DEL ENCEINTE MATÉRIAU DEFINITION EMPLACEMENT DEL ENTRÉE DUGAZ 501 2 128 3cm 5 1 DIMENSIONS MINIMALES DE L OSSATURE ...

Page 110: ... minimal aux matériaux combustibles de 1 25mm est requis sur toutes les courses verticales à l exception des dégagements à l intérieur de l enceinte de l appareil Voir la section DÉGAGEMENTS MINIMAUX DE L ENCEINTE Utilisez l espaceur coupe feu W500 0096 non fourni Dégagements minimaux de l appareil aux matériaux combustibles Ossature combustible 0 aux espaceurs 1 25mm en dessous et sur les côtés d...

Page 111: ...UPE FEU ENCEINTE AVEC ÉVACUATION SUR LE DESSUS L enceinte de l appareil doit avoir une hauteur minimale de 50 1 2 1283 mm Afin de respecter les con straintes de température l espace à l intérieur de l enceinte autour de l appareil et au dessus doit demeurer sans obstruction Voir la section DIMENSIONS MINIMALE DE L OSSATURE pour plus d informations sur la réduction d évacuation tuyau supérieur déga...

Page 112: ...OMBUSTIBLE 1 25mm 3 76mm 7 178mm 10 20 254mm 508mm ÉVENTS 415 8 105 7cm MINIMUM 1 10 25mm 254mm ÉVENTS 345 8 87 9cm ENCEINTE AVEC ÉVACUATION À L ARRIÈRE L enceinte de l appareil doit avoir une hauteur minimale de 41 5 8 1057mm Afin de respecter les contraintes de température l espace à l intérieur de l enceinte autour de l appareil et au dessus doit demeurer sans obstruction FR NOTE Le bouclier d ...

Page 113: ... au dessus doit demeurer sans obstruction INCOMBUSTIBLE 0 0MM SILESMATÉRIAUX SONTINCOMBUSTIBLES COMMEDELABRIQUE 0 0MM SILESMATÉRIAUX SONTINCOMBUSTIBLES COMMEDELABRIQUE ETDELAPIERRE INCOMBUSTIBLE BRIQUE BRIQUE 241 8 61 3cm MINIMUM PLUSLAPENTE COMBUSTIBLE 3 76mm 10 COMBUSTIBLE 1 25mm 3 76mm 7 178mm 415 8 105 7cm 10 20 254mm 508mm ÉVENTS 111 2 292mm 345 8 87 9cm FR NOTE Le bouclier d évent est télesc...

Page 114: ...178mm 415 8 105 7cm 111 2 292mm 345 8 879mm 345 8 87 9cm ENCEINTE AVEC ÉVACUATION À L ARRIÈRE L enceinte de l appareil doit avoir une hauteur minimale de 41 5 8 1057mm Afin de respecter les contraint es de température l espace à l intérieur de l enceinte autour de l appareil et au dessus doit demeurer sans obstruction FR NOTE Le bouclier d évent est télescopique et doit être ajusté pour protéger l...

Page 115: ... des projections plus grandes sont requises augmentez les dégagements des côtés et du dessus de 2 50 8mm pour chaque pouce 24 5mm supplémentaire de projection Si vous utilisez un moulure optionelle les même règles s applique commençant du sommet du moulure Garantir que les dégagements sont maintenus pour l enlèvement du moulure vous devez l enlever de l appareil pour l entretien 71 7 4 102mm VITRE...

Page 116: ...sité de la chaleur sur l électronique B Se référer à la section DÉGAGEMENTS MINIMAUX DE LA TABLETTE pour plus d informations sur les dégagements de la cheminée WARNING L INSTALLATION D UNE TÉLÉVISION OU D AUTRES APPAREILS ÉLECTRONIQUES DESSUS DE L APPAREIL PEUT PROVOQUER LA DÉCOLORATION FUSION OU DOMMAGE L APPAREIL ÉLECTRONIQUE UTILISER LES DÉGAGEMENTS À TITRE INDICATIF ET SE RÉFÉRER AUX INSTRUCTI...

Page 117: ... 38mm 49 1244mm 34 864mm DEMATÉRIAU INCOM BUSTIBLE 61 2 165mm MIN 15 381mm UNLINTEAU ENACIEREST REQUISSILE CONTOUR PLEINEVISION OPTIONNEL SONT INSTALLÉS M A N T E L H E I G H T 0 2 50 8mm 2 4 6 8 10 12 MANTEL DEPTH INCHES 4 101 6mm 6 152 4mm 10 254mm 12 30 5cm 8 203 2mm 0 12 2 4 6 8 10 12 PROFONDEUR DE LA TABLETTE 14 16 18 20 22 H A U T E U R D E L A T A B L E T T E HAUT DE L OUVERTURE 4 2 18 16 1...

Page 118: ... avec l appareil et sera être installés Avant d enlever la porte vitrée l écran de protection doit être enlever Soulevez l écran de protection hors des 4 goupilles et enlever de l appareil puis inclinez la partie haut de la porte vitrée puis enlever de l appareil 118 FR AVERTISSEMENT RISQUE D INCENDIE N OBSTRUEZ JAMAIS L OUVERTURE SUR LE DEVANT DE L APPAREIL SI LA FINITION DE LA FAÇADE DE L APPARE...

Page 119: ...rs du dispositif de retenu inférieur NOTE Ces système de décharge constituent le système de secours de printemps de l appareil Vérifiez si le système de décharge effectue efficacement Inversez ces étapes pour réinstaller la porte et l écran de protection Assurez l écran de protection est correctement installé 6 2 L AVANT HOTTE D INSTALLATION HOOD SIDE VIEW A La porte et l écran de protection doive...

Page 120: ...t différent dans chaque installation Prenez le temps de bien installer les braises incandescentes pour obtenir le meilleur effet possible La couleur des bûches peut varier Lors de la première utilisation de l appareil les couleurs deviendront plus uniformes à mesure que leurs pigments seront absorbés pendant le procédé de cuisson ÉPINGLES C Placez la bûche droite W135 0645 sur les deux goujons aux...

Page 121: ...ocage des orifices du brûleur peuvent créer une flamme irrégulière des dépôts de carbone et un retard d allumage Les bûches PHAZERMD rougeoient lorsqu elles sont exposées à une flamme directe N utilisez que des braises incandescentes et des bûches certifiées PHAZERMD disponibles chez votre détaillant au torisé 6 4 BRAISES INCANDESCENTES 97 1A Retirez le papier dorsal du logo et placez le sur la po...

Page 122: ...s quatre vis d épaulement E Attacher les fils étiqueté PILE à partir de harnais de fils de l appareil aux boîtier de batterie F Placez le boîtier de batterie dans la compartiment du soupape au dessous du brûleur garantir que le boîtier de batterie est placer dans un endroit facile d accès G Garantir que l écran de protection soit réinstallez pendant l opération de l appareil H Ouvrir l alimentatio...

Page 123: ...frottement du soufflerie contre le plancher de l appareil G Faites pivoter la soufflerie dans le bas de l appareil assurez que le joint d étanchéité reste en place entre le soufflerie et le foyer pendant que vous glissez le soufflerie contre la côté gauche dans la patte du montage du soufflerie Fixer en place utilisant une vis voir Figure 4 5 K Branchez le connecteur de l IVV dans la prise correspondan...

Page 124: ... dans la boîtier de piles et connectez au harnais de fil AVERTISSEMENT NE RACCORDEZ PAS L INTERRUPTEUR MURAL OU LA SOUPAPE DE GAZ À L ALIMENTATION ÉLECTRIQUE 110 VOLTS BOÎTIER DE PILES FOURNI AUX SAC DU MANUEL TERRE DFC SOUPAPE ON OFF IPI CPI ALIMENTATION CC OFF ON ORANGE VERT CARTE DE CIRCUITS IMPRIMÉS IPI SOUPAPE ÉLECTRONIQUE ANNEAU DE MISE À LA TERRE INTERRUPTER ACS IPI Débranchez ces connecteu...

Page 125: ...vrez les fenêtres n allumez aucun appareil ne touchez à aucun interrupteur électrique n utilisez aucun téléphone dans votre immeuble de la maison d un voisin appelez im médiatement votre fournisseur de gaz et suivez ses instructions Si vous ne pouvez pas rejoindre votre fournisseur de gaz appelez le service des incendies INSTRUCTIONS D ALLUMAGE 1 arrêtez lisez les consignes de sécurité ci dessus 2...

Page 126: ...dir Durant l allumage et le réallumage le bouton de contrôle du gaz ne peut tourner de PILOT à OFF à moins de l enfoncer légèrement 1 Arrêtez Lisez les consignes de sécurité ci dessus 2 Coupez l alimentation électrique à l appareil 3 Tournez le bouton de contrôle du gaz vers la droite à OFF 4 Attendez 5 minutes pour que le gaz puisse s échapper Si vous détectez une odeur de gaz incluant au niveau ...

Page 127: ...a pression d arrivée tournez la vis A vers la gauche deux à trois tours puis emboîtez le tube du manomètre sur la pointe d essai Le manomètre doit indiquer la pression comme décrit sur le diagramme ci dessous Vérifier la pression avec brûleur principal sur HI La vérification de la pression de sortie s effectue comme ci dessus en utilisant la vis B Le manomètre doit indiquer la pression comme décri...

Page 128: ...tent à une veilleuse permanente pour les climats froids Le contrôle contre la condensation veilleuse permanente est situé dans le centre du panneau de contrôle Avec votre doigt appuyez sur l interrupteur vers le haut pour la veilleuse permanente ou vers le bas pour l allumage intermittent Tourner l interrupteur sur ACS permettra à la flamme de la veilleuse à bruler en continu Ce mode permet de min...

Page 129: ...elopper la sonde de flamme et ou le thermocouple thermopile et qu elle atteigne le brûleur E Remettez en place les bûches les roches ou la vitre nettoyées si équipé Omettre de positionner les composants décoratifs adéquatement peut causer des dépots de carbone qui peuvent se déposer à l intérieure de la chambre de combustion et sur les surfaces extérieures entourant d évent F Vérifiez si le brûleu...

Page 130: ...nlevez aussi tout dépôt se trouvant sur l assemblage de la veilleuse et aussi s il y a lieu sur la thermopile le thermocouple le capteur de flamme et l allumeur NOTE Vous devrez nettoyer le capteur de flamme à l aide d une morceau de de laine d acier ou un tampon récurage Scotch Brite afin de retirer toute trace d oxydation Nettoyez l assemblage du pilote à l aide d un aspirateur muni d une brosse...

Page 131: ...ER ALLOW CHILDREN TO TOUCH GLASS WARNING AVERTISSEMENT 10 3 SOINS DE LA VITRE 5 5A L appareil est muni d une 4mm vitre en verre trempé Remplacez uniquement avec une vitre certifiée pour le foyer disponible chez votre détaillant autorisé N UTILISEZ PAS DE MATÉRIAUX SUBSTITUTS AVERTISSEMENT N UTILISEZ PAS DE MATÉRIAUX DE SUBSTITUTION LA VITRE PEUT ÊTRE CHAUDE NE TOUCHEZ PAS LA VITRE JUSQU À CE QU ELL...

Page 132: ...RO DES PIÈCES ET SI IL SOIT DISPONIBILITÉ PEUT CHANGER SANS PRÉAVIS PARTIES IDENTIFIÉES COMME GARNIE SERONT LIVRÉS DANS 2 À 5 JOURS POUR LA PLUPART DES DESTINATIONS DE LIVRAISON PIÈCES NON IDENTIFIÉES QUE STOCKÉS SERONT LIVRÉS DANS UN DÉLAI DE 2 À 4 SEMAINES 41 2A OMETTRE DE POSITIONNER LES PIÈCES CONFORMÉMENT À CE MANUEL OU D UTILISER UNIQUEMENT DES PIÈCES SPÉCIFIQUEMENT APPROUVÉES POUR CET APPAR...

Page 133: ...ORTE DÉFLECTEUR AVANT HOTTE GARNITURE DE FINITION SUPÉRIEURE BÛCHE CROISÉ GAUCHE GL 699 BÛCHE CROISÉ DROITE GL 699 BÛCHE DU CÔTÉ GAUCHE BÛCHE DE L ARRIÈRE GL 699 BÛCHE DU CÔTÉ DROITE GL 699 GOUPILLES DES BÛCHES BRAISES LUISANTES GL 699 ENSEMBLE DE COLLET D AIR ET PLAQUE JOINT D ÉTANCHÉITÉ DE LA BRIDE ARRIÈRE BOUCLIER DE SORTIE ENSEMBLE DE LOQUET DE PORTE PLAQUE DE RESTRICTION 4 INTERRUPTEUR ACS av...

Page 134: ... DE CONTRÔLE OUI W350 0799 BOUCLIER DE VEILLEUSE W335 0039 OUI HOTTE DU VEILLEUSE W455 0068 OUI INJECTEUR DE VEILLEUSE 35 P W720 0062 OUI TUBE DE VEILLEUSE RACCORD W240 0013 OUI ALLUMEUR AVEC FILS W245 0037 CAPTEUR DE FLAMME AVEC FILS OUI OUI W290 0029 JOINT D ÉTANCHÉITÉ DU VEILLEUSE W750 0270 INTERRUPTEUR DU FILS OUI OUI W010 2763 W010 2808 ENSEMBLE DE VEILLEUSE GN ENSEMBLE DE VEILLEUSE P W725 00...

Page 135: ...OCOUPLE OUI TUBE DE VEILLEUSE RACCORD ALLUMEUR AVEC FILS JOINT D ÉTANCHÉITÉ DU VEILLEUSE W335 0039 W455 0070 HOTTE DU VEILLEUSE INJECTEUR DE VEILLEUSE 62 GN OUI OUI W350 0799 W750 0112 INTERRUPTEUR DU FILS BOUCLIER DE VEILLEUSE W010 0798 W010 0799 ENSEMBLE DE VEILLEUSE GN ENSEMBLE DE VEILLEUSE P W500 0276 SER COUVERCLE OUI OUI W455 0068 INJECTEUR DE VEILLEUSE 35 P 27 28 28 29 30 31 32 32 33 34 35 ...

Page 136: ...NTERRUPTEUR À VITESSE VARIABLE GARNITURE CAMBRÉE DE DROITE BT46K GARNITURE CAMBRÉE DE GAUCHE BT46K OUI W062 0059 SER W715 1070 SER W715 1087 SER W715 1069 SER SOUFFLERIE AUB GARNITURE CAMBRÉE SUPÉRIEURE INFÉRIEURE X2 BT46K W200 0622 W200 0586 W475 1132 BK2GL W475 1247 W475 1246 W475 1248 W475 1249 BK2GL COUVERCLE SUPÉRIEURE COUVERCLE INFÉRIEURE PANNEAU DE PORCELAINE DU CÔTÉ PANNEAU DE PORCELAINE D...

Page 137: ...rre Vérifiez si les assemblages de la veilleuse et de la soupape sont bien mis à la terre au niveau du châssis métallique de l appareil ou de l ensemble de bûches Étincelle à la veilleuse mais celle ci ne s allume pas Alimentation en gaz Vérifiez si la soupape à bille de la conduite d arrivée du gaz est Ouverte Vérifiez si la pression d arrivée est dans les limites acceptables La pression d arrivé...

Page 138: ...s assurez vous que les connexions sont bien serrées Vérifiez si tout le filage est installé exactement tel que spécifié Harnais de fils Inspectez le harnais de fils et vérifiez qu il soit solidement branché au module Vérifiez que tous les fils sont branchés dans le bon ordre Voir la section SCHÉMA DE CÂBLAGE On détecte l odeur des gaz de combustion dans la pièce maux de tête L appareil refoule les...

Page 139: ... principal le bouton du gaz est à HI l interrupteur mural thermostat est à ON Le thermostat ou l interrupteur sont défectueux Reliez un fil de dérivation entre les bornes de l interrupteur mural si le brûleur principal s allume remplacez l interrupteur thermostat Le raccordement de l interrupteur est défectueux Débranchez les fils de l interrupteur et reliez un fil de dérivation entre les bornes 1 et...

Page 140: ... prinicpal fonctionne à HI APRÉS AVOIR PRIS LA LECTURE DES PRESSIONS ASSUREZ VOUS DE TOURNER FERMEMENT LA VIS VERS LA DROITE POUR SCELLER NE SERREZ PAS TROP FORT Vérifiez pour des fuites en appliquant une solution d eau savonneuse Les flammes sont trés actives La porte est entrouverte Serrez les vis qui retiennent la porte en place Forte action de ventilation Assurez vous que l évacuation est adéqua...

Page 141: ... buse d évacuation amovible Vérifiez tous les joints scellés et la plaque d expansion Vérifiez si la cheminée ne serait pas bloquée Vérifiez si la cheminée est installée selon les codes du bâtiment La pièce est sous pression négative augmentez l apport d air frais Vérifiez le joint d étanchéité du couvercle d évacuation L interrupteur mural est à OFF le brûleur principal s allume lorsque le bouton du ...

Page 142: ... les fournaises les sécheuses de linge etc Tous dommages causés a l appareil à la chambre de combustion à l échangeur de chaleur aux garnitures de laiton ou autres composants par l eau les dommages causés par les intempéries de longues périodes d humidité la condensation des produits chimiques ou produits d entretien nuisibles ne seront pas la responsabilité de CONTINENTAL Toutes les pièces rempla...

Page 143: ...143 W415 1616 C 09 20 17 FR 16 0 NOTES 44 1 ...

Page 144: ...adienne Montréal Québec H4T 1A3 24 Napoleon Road Barrie Ontario Canada L4M 0G8 214 Bayview Drive Barrie Ontario Canada L4N 4Y8 103 Miller Drive Crittenden Kentucky USA 41030 Phone 1 866 820 8686 continentalfireplaces com ...

Reviews: