Napoleon GDS25N Installation And Operation Instructions Manual Download Page 18

18

W415-0547 / B / 05.08.06

 

1.

 Attach the adjustable pipe to the last section of rigid pip-

ing. Secure with screws and seal.

2. 

Install the 4" aluminium fl exible  liner 

to the stove. Secure with 3 screws 
and  fl at washers. Seal the joint 
and screw holes using high 
temperature sealant.

3.

 Run a bead of high tem-

perature sealant Mill Pac 
around the inside of the air 
intake collar. Pull the adjust-
able pipe a minimum 2" into 
the air intake collar. 

ENSURE THAT THE SEAL-
ANT IS NOT VISIBLE ON THE EXTERIOR PIPES ONCE 
INSTALLATION IS COMPLETED. AN OPTIONAL DECO-
RATIVE BRASS BAND IS AVAILABLE FOR THIS USE. 
(STANDARD WITH A GD175 KIT AND GD-176). IN THE 
EVENT THAT THE VENTING MUST BE DISASSEMBLED, 
CARE MUST BE TAKEN TO RESEAL THE VENTING.

In Canada, mobile home installation may be vented horizon-
tally or vertically. In the United States, it may only be installed 
vertically. See "Vertical Venting" or "Horizontal Air Terminal 
Installation" for installation. 

For mobile home installations, the fi replace must be fastened 
in place. It is recommended that the fi replace be secured in 
all installations. Use the levelling/securing kit, GDSLL-KT for 
this purpose.

SEALANT

2" OVERLAP

SELF DRILLING

#8x1/2"

SCREWS 

HI-TEMP

STOVE VENT CONNECTION

MOBILE HOME INSTALLATION 

1/2FPT

3/8NPT

CONNECTOR

FITTING

ADAPTER

FLEXIBLE

PIPE

BLACK

VALVE

SHUT OFF

1. 

Install rigid black pipe, or 1/2" type L copper tubing with a 

shut-off valve to the stove. 

2. 

Seal and tighten the gas line securely to a fl ex  connec-

tor. 

DO NOT KINK FLEXIBLE CONNECTOR.

3. 

Check for gas leaks by brushing on a soap and water solu-

tion. 

DO NOT USE OPEN FLAME.

FIGURE 28

GAS INSTALLATION

RESTRICTOR 

SHOWN IN A FULLY 

CLOSED POSITION

RESTRICTING VERTICAL VENTS

Vertical installations may display a very active fl ame. Loosen 
the two screws and slide the restrictor plate blocking the ex-
haust path. This reduces the velocity of the exhaust gases, 
slowing down the fl ame pattern and creating a more traditional 
fl ame appearance. For vertical vents greater than 15 feet, this 
restrictor must be fully closed.

FIGURE 27

RESTRICTOR 

SHOWN IN A FULLY 

OPEN POSITION

Summary of Contents for GDS25N

Page 1: ...1 W415 0547 B 05 08 06 W415 0547 B 05 08 06...

Page 2: ...l your gas supplier from a neighbor s phone Follow the gas supplier s instructions Installation and service must be performed by a qualified installer service agency or the gas supplier Follow the ins...

Page 3: ...f any part has been under water Immediately call a qualified service technician to inspect the stove and to replace any part of the control system and any gas control which has been under water Do not...

Page 4: ...AZER logs and embers nor any venting com ponents used in the installation of the fireplace NAPOLEON warrants its stainless steel burners against defects in workmanship and material for life subject to...

Page 5: ...to conform with local codes Installation practices vary from region to region and it is im portant to know the specifics that apply to your area for example in Massachusetts State The fireplace dampe...

Page 6: ...ove FIGURE 2 LOCATION CLEARANCES STOVE DIMENSIONS FIGURE 1 7 DIA 23 1 2 12 3 4 23 5 8 25 5 8 17 1 2 4 DIA AT A DISTANCE OF 2 FROM THE WALL INSTALLATION OR SERVICE TO THE BLOWER MAY NOT BE PRACTICAL A...

Page 7: ...the pal nut and the knob supplied 9 Connect the male connector on the switch to the female connector coming from the unit 10 Tuck all of the wires into the housing and close Secure using the screw re...

Page 8: ...anently closed windows Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet from the centerline of the terminal Clearance to unventilated soffit Cl...

Page 9: ...L KIT GD176 24 of venting included or 1 12 TO 7 12 PITCH ROOF TERMINAL KIT GD110 8 12 TO 12 12 ROOF TERMINAL KIT GD111 FLAT ROOF TERMINAL KIT GD112 or STOVE PERISCOPE KIT GD180 for wall penetration be...

Page 10: ...e installed so that when final grading is completed the bottom air slot is located a minimum of 12 inches above grade The maximum allowable vent length depends on the fireplace as illustrated FIGURES...

Page 11: ...ed vertical vent lengths in feet feet inches 1 0 03 0 5 15 0 45 6 0 30 0 9 11 0 45 1 35 16 0 90 2 7 32 0 the first 45 and 90 offset has a zero value and is shown in the formula as 45 and 90 respective...

Page 12: ...TAL VENT RUN PLUS OFFSETS IN FEET when HT VT Simple venting configuration only one 45 and 90 elbow Example 2 V1 4 ft V2 1 5 ft VT V1 V2 4 ft 1 5 ft 5 5 ft H1 2 ft H2 1 ft H3 1 ft H4 1 5 ft HR H1 H2 H3...

Page 13: ...n is acceptable when HT VT See graph to determine the required vertical rise VT for the FIGURE 9 REQUIRED VERTICAL RISE IN FEET VT HORIZONTAL VENT RUN PLUS OFFSETS IN FEET FIGURE10 90 elbow the follow...

Page 14: ...ration is unacceptable REQUIRED VERTICAL R I S E I N FEET VT HORIZONTAL VENT RUN PLUS OFFSET IN FEET FIGURE 11 The shaded area within the lines represents acceptable values for HT and VT 90 FIGURE 12...

Page 15: ...iner as straight as possible The inlet air collar of the termina tion cap must be connected to the air intake pipe Use Simpson Duravent Chimney Liner Termination Kit 923GK Baseplate and Co Linear to C...

Page 16: ...the stove pipe and any combustible material Try to center the exhaust pipe location midway between two joist to prevent having to cut them Use a plumb bob to line up the center of the openings DO NOT...

Page 17: ...RMANCE IT IS RECOMMENDED THAT ALL HORIZONTAL RUNS HAVE A MINIMUM INCH RISE PER FOOT ALL INNER EXHAUST AND OUTER INTAKE VENT PIPE JOINTS MAY BE SEALED USING EITHER RED RTV HIGH TEMP SILICONE SEALANT OR...

Page 18: ...or mobile home installations the fireplace must be fastened in place It is recommended that the fireplace be secured in all installations Use the levelling securing kit GDSLL KT for this purpose SEALA...

Page 19: ...he front fit behind the front legs Note It is not necessary to remove the cast front in order to remove the door DOOR RETAINER FRONT LEGS TAB FRONT FIGURE 31 LATCHES DOOR 3 2 FIGURE 30 FIGURE 32 SWITC...

Page 20: ...ar log as shown onto the rear log support brackets Ensure the cutout on the left underside of the log fits over the pilot assembly Bend the bracket on the right side to help retain the rear log 2 Plac...

Page 21: ...onnect the wires from the wall switch thermostat to the two brown wires extending from the fireplace mounted ignition control box Purge all gas lines with the glass door of the fireplace open Assure t...

Page 22: ...THIS FIREPLACE IF ANY PART HAS BEEN UNDER WATER IMMEDIATELY CALL A QUALIFIED SERVICE TECHNICIAN TO INSPECT THE FIREPLACE AND REPLACE ANY PART OF THE CONTROL SYSTEM AND ANY GAS CONTROL WHICH HAS BEEN U...

Page 23: ...place area must be kept clear and free of combustible materials gasoline or other flammable vapours and liquids The flow of combustion and ventilation air must not be obstructed 1 In order to properly...

Page 24: ...FIRESTOP WALL PLATE 32 W020 0032 HARDWARE 33 BRTC7 BRASS TRIM COLLAR 34 BM6724 24 STOVE PIPE 7 DIAMETER 35 W010 0300 10 ALUMINIUM FLEX LINER C W SPACERS 4 DIA 36 W025 0001 DECORATIVE BRASS BAND 37 GD1...

Page 25: ...25 W415 0547 B 05 08 06 WARNING This is a fast acting thermocouple It is an integral safety component Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd...

Page 26: ...ded wire about 3 16 away from the I terminal on the module If no spark the I terminal module must be replaced If there is a spark the I terminal is fine Inspect pilot assembly for a shorted wire or cr...

Page 27: ...res and they are connected in the right order Module or Valve Conduct the following test to verify if the problem is the module or valve To measure voltages turn multimeter to DC place the red lead fr...

Page 28: ...28 W415 0547 B 05 08 06 Fireplace Service History This fireplace must be serviced annually depending on usage DATE DEALER NAME SERVICE TECHNICIAN NAME SERVICE PERFORMANCE SPECIAL CONCERNS...

Reviews: