Napoleon GDS25N Installation And Operation Instructions Manual Download Page 17

17

W415-0547 / B / 05.08.06

 1. Fasten the roof support 
to the roof using the screws 
provided. The roof support 
is optional. In this case the 
venting is to be adequately 
supported using either an 
alternate method suitable to 
the authority having jurisdiction 
or the optional roof support. 
 2. Stretch the inner aluminum fl ex 
liner to the required length. Slip the 
liner a minimum of 2” over the inner 
sleeve of the air terminal connector 
and secure with 3 #8 screws. Seal 
using a heavy bead of the high 
temperature sealant.  
 3.Repeat using the outer aluminum 
fl ex liner. 
 4. Thread the air terminal connector 
/ liner assembly down through 
the roof. The air terminal must be 
located vertically and plumb.  Attach 
the air terminal connector to the roof 
support, ensuring that the top of the 
air terminal is 16” above the highest 
point that it penetrates the roof.  
 5. Remove nails from the shingles, above and to the 
sides of the chimney. Place the 
fl ashing over the air terminal 
connector leaving a min. 3/4” 
of the air terminal connector 
showing above the top of the 
fl ashing.  Slide the fl ashing 
underneath the sides and upper 
edge of the shingles. Ensure 
that the air terminal connector 
is properly centred within the 
fl ashing, giving a 3/4” margin 
all around. Fasten to the roof. 
Do not nail through the lower 
portion of the fl ashing. Make 
weather-tight by sealing with 
caulking. Where possible, cover 
the sides and top edges of the 
fl ashing with roofi ng material.  
 6. Aligning the seams of 
the terminal and air terminal 
connector, place the terminal 
over the air terminal connector 
making sure the liner goes into the hole in the terminal.  
Secure with the three screws provided.  
 7. Apply a heavy bead of weatherproof caulking 2 
inches above the fl ashing.  Note:  Maintain a minimum 
2” space between the air inlet base and the storm collar.  
Install the storm collar around the air terminal and slide 
down to the caulking. Tighten to ensure that a weather-
tight seal between the air terminal and the collar is 
achieved. 

 

VERTICAL VENTING INSTALLATION

FOR SAFE AND PROPER OPERATION OF THE STOVE, 

FOLLOW THE VENTING INSTRUCTIONS EXACTLY.

ALL HORIZONTAL VENT RUNS MAY HAVE A 0" RISE 

PER FOOT.

FOR OPTIMUM PERFORMANCE IT IS RECOMMENDED 

THAT ALL HORIZONTAL RUNS HAVE A MINIMUM 

¼ INCH RISE PER FOOT.

ALL INNER EXHAUST AND OUTER INTAKE VENT 

PIPE JOINTS MAY BE SEALED USING EITHER RED 

RTV HIGH TEMP SILICONE SEALANT OR BLACK 

HIGH TEMP MILL PAC WITH THE EXCEPTION OF THE 

FIREPLACE EXHAUST FLUE COLLAR WHICH MUST BE 

SEALED USING MILL PAC (NOT SUPPLIED).

1. 

Stretch the 4" diameter aluminium fl exible liner to the re-

quired length taking into account the additional length needed 
for the fi nished wall surface. 

Spacers are attached to the 4" inner fl ex liner at predetermined 
intervals to maintain a 1-1/4" air gap to the 7" outer stove pipe. 
These spacers must not be removed.

 

Slip a 4" diameter length of aluminium fl exible liner a minimum 

of 2" over the inner sleeve of the air terminal. Secure to the 
sleeve using 3 screws. Seal the joint and screw heads using 
the high temperature sealant.

2.

 Slip the fi rst section of  7" diameter stove pipe a minimum 

of  2" over the outer sleeve of the air terminal. Secure to the 
sleeve using 3 screws. Seal the joint and screw heads using 
high temperature sealant. 

3. 

Insert the liners through the fi restop / vent pipe shield. 

Holding the air terminal (lettering in an upright, readable 
position), secure to the exterior wall. Make weather tight by 
sealing with caulking (not supplied). The air terminal mounting 
plate may be recessed (up to 1½" maximum) into the exterior 
wall or siding. 

4. 

If more than one length of liner needs to be used to reach 

the stove, couple them together as illustrated in 

FIGURE 21

Seal the joints using the same procedure as described 
above. 

The vent system must be supported approximately every 
10 feet along a horizontal run. Use supports or equivalent 
non-combustible strapping to maintain the 1" clearance from 
combustibles.

HORIZONTAL VENTING INSTALLATION

#10x2"

#

SEALANT

HI-TEMP

4"FLEX

CAULKING

  PIPE

7" RIGID

ATTENTION-CHAUD

CAUTION

 - 

HOT

FIGURE 20

SCREWS & 
WASHERS

4"COUPLER

SELF DRILLING

#8x1/2"

7" RIGID PIPE

SEALANT

HI-TEMP

4"FLEX

PIPE

7" RIGID PIPE

FIGURE 21

ROOF SUPPORT

DO NOT CLAMP 

THE FLEXIBLE 

ALUMINIUM 

LINER.

AIR

TERMINAL

CONNECTOR

INNER FLEX
LINER

OUTER FLEX
LINER

INNER
SLEEVE

HIGH
TEMPERATURE
SEALANT

Spacers are attached to

the inner fl ex liner at 

predetermined intervals to 

maintain a 1-1/4” air gap to 

the outer fl ex liner. These 

spacers must not be 

removed.

STORM COLLAR

FLASHING

CAULKING

WEATHER
    SEALANT

2”

AIR INLET
BASE

Summary of Contents for GDS25N

Page 1: ...1 W415 0547 B 05 08 06 W415 0547 B 05 08 06...

Page 2: ...l your gas supplier from a neighbor s phone Follow the gas supplier s instructions Installation and service must be performed by a qualified installer service agency or the gas supplier Follow the ins...

Page 3: ...f any part has been under water Immediately call a qualified service technician to inspect the stove and to replace any part of the control system and any gas control which has been under water Do not...

Page 4: ...AZER logs and embers nor any venting com ponents used in the installation of the fireplace NAPOLEON warrants its stainless steel burners against defects in workmanship and material for life subject to...

Page 5: ...to conform with local codes Installation practices vary from region to region and it is im portant to know the specifics that apply to your area for example in Massachusetts State The fireplace dampe...

Page 6: ...ove FIGURE 2 LOCATION CLEARANCES STOVE DIMENSIONS FIGURE 1 7 DIA 23 1 2 12 3 4 23 5 8 25 5 8 17 1 2 4 DIA AT A DISTANCE OF 2 FROM THE WALL INSTALLATION OR SERVICE TO THE BLOWER MAY NOT BE PRACTICAL A...

Page 7: ...the pal nut and the knob supplied 9 Connect the male connector on the switch to the female connector coming from the unit 10 Tuck all of the wires into the housing and close Secure using the screw re...

Page 8: ...anently closed windows Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet from the centerline of the terminal Clearance to unventilated soffit Cl...

Page 9: ...L KIT GD176 24 of venting included or 1 12 TO 7 12 PITCH ROOF TERMINAL KIT GD110 8 12 TO 12 12 ROOF TERMINAL KIT GD111 FLAT ROOF TERMINAL KIT GD112 or STOVE PERISCOPE KIT GD180 for wall penetration be...

Page 10: ...e installed so that when final grading is completed the bottom air slot is located a minimum of 12 inches above grade The maximum allowable vent length depends on the fireplace as illustrated FIGURES...

Page 11: ...ed vertical vent lengths in feet feet inches 1 0 03 0 5 15 0 45 6 0 30 0 9 11 0 45 1 35 16 0 90 2 7 32 0 the first 45 and 90 offset has a zero value and is shown in the formula as 45 and 90 respective...

Page 12: ...TAL VENT RUN PLUS OFFSETS IN FEET when HT VT Simple venting configuration only one 45 and 90 elbow Example 2 V1 4 ft V2 1 5 ft VT V1 V2 4 ft 1 5 ft 5 5 ft H1 2 ft H2 1 ft H3 1 ft H4 1 5 ft HR H1 H2 H3...

Page 13: ...n is acceptable when HT VT See graph to determine the required vertical rise VT for the FIGURE 9 REQUIRED VERTICAL RISE IN FEET VT HORIZONTAL VENT RUN PLUS OFFSETS IN FEET FIGURE10 90 elbow the follow...

Page 14: ...ration is unacceptable REQUIRED VERTICAL R I S E I N FEET VT HORIZONTAL VENT RUN PLUS OFFSET IN FEET FIGURE 11 The shaded area within the lines represents acceptable values for HT and VT 90 FIGURE 12...

Page 15: ...iner as straight as possible The inlet air collar of the termina tion cap must be connected to the air intake pipe Use Simpson Duravent Chimney Liner Termination Kit 923GK Baseplate and Co Linear to C...

Page 16: ...the stove pipe and any combustible material Try to center the exhaust pipe location midway between two joist to prevent having to cut them Use a plumb bob to line up the center of the openings DO NOT...

Page 17: ...RMANCE IT IS RECOMMENDED THAT ALL HORIZONTAL RUNS HAVE A MINIMUM INCH RISE PER FOOT ALL INNER EXHAUST AND OUTER INTAKE VENT PIPE JOINTS MAY BE SEALED USING EITHER RED RTV HIGH TEMP SILICONE SEALANT OR...

Page 18: ...or mobile home installations the fireplace must be fastened in place It is recommended that the fireplace be secured in all installations Use the levelling securing kit GDSLL KT for this purpose SEALA...

Page 19: ...he front fit behind the front legs Note It is not necessary to remove the cast front in order to remove the door DOOR RETAINER FRONT LEGS TAB FRONT FIGURE 31 LATCHES DOOR 3 2 FIGURE 30 FIGURE 32 SWITC...

Page 20: ...ar log as shown onto the rear log support brackets Ensure the cutout on the left underside of the log fits over the pilot assembly Bend the bracket on the right side to help retain the rear log 2 Plac...

Page 21: ...onnect the wires from the wall switch thermostat to the two brown wires extending from the fireplace mounted ignition control box Purge all gas lines with the glass door of the fireplace open Assure t...

Page 22: ...THIS FIREPLACE IF ANY PART HAS BEEN UNDER WATER IMMEDIATELY CALL A QUALIFIED SERVICE TECHNICIAN TO INSPECT THE FIREPLACE AND REPLACE ANY PART OF THE CONTROL SYSTEM AND ANY GAS CONTROL WHICH HAS BEEN U...

Page 23: ...place area must be kept clear and free of combustible materials gasoline or other flammable vapours and liquids The flow of combustion and ventilation air must not be obstructed 1 In order to properly...

Page 24: ...FIRESTOP WALL PLATE 32 W020 0032 HARDWARE 33 BRTC7 BRASS TRIM COLLAR 34 BM6724 24 STOVE PIPE 7 DIAMETER 35 W010 0300 10 ALUMINIUM FLEX LINER C W SPACERS 4 DIA 36 W025 0001 DECORATIVE BRASS BAND 37 GD1...

Page 25: ...25 W415 0547 B 05 08 06 WARNING This is a fast acting thermocouple It is an integral safety component Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd...

Page 26: ...ded wire about 3 16 away from the I terminal on the module If no spark the I terminal module must be replaced If there is a spark the I terminal is fine Inspect pilot assembly for a shorted wire or cr...

Page 27: ...res and they are connected in the right order Module or Valve Conduct the following test to verify if the problem is the module or valve To measure voltages turn multimeter to DC place the red lead fr...

Page 28: ...28 W415 0547 B 05 08 06 Fireplace Service History This fireplace must be serviced annually depending on usage DATE DEALER NAME SERVICE TECHNICIAN NAME SERVICE PERFORMANCE SPECIAL CONCERNS...

Reviews: