Napoleon BGD90NT Installation And Operation Instructions Manual Download Page 29

29

W415-0580 / B / 03.12.08

White / grey film 
forms.

Sulphur from fuel is being 
deposited on glass, logs or 
combustion chamber sur-
faces.

-  clean the glass with a gas fi replace glass cleaner. DO NOT CLEAN 
GLASS WHEN HOT. 
If deposits are not cleaned off regularly, the glass may become per-
manently marked.

Carbon is being de-
posited on glass, 
logs or combustion 
chamber surfaces.

Flame is impinging on the 
logs or combustion cham-
ber.

-  check that the logs are correctly positioned.
-  open air shutter to increase the primary air.
-  check the input rate: check the manifold pressure and orifi ce size as 
specifi ed by the rating plate values.
- check that the door gasket is not broken or missing and that the seal 
is tight.
- check that both 8” and 10” vent liners are free of holes and well 
sealed at all joints.
- check that minimum rise per foot has been adhered to for any hori-
zontal venting.

A i r   s h u t t e r   h a s   b e c o m e 
blocked

-  ensure air shutter opening is free of lint or other obstructions.

Pilot goes out when 
the gas knob is re-
leased.

The gas valve has 
an interlock device 
which will not al-
low the pilot burn-
er to be lit until 
the thermocouple 
has cooled. Allow 
approximately 60 
seconds for the 
thermocouple to 
cool.

S y s t e m   i s   n o t   c o r r e c t l y 
purged.

-  purge the gas line with the glass door open.

Out of propane gas.

-  fi ll the tank.

P i l o t   f l a m e   i s   n o t   l a r g e 
enough

-  turn up the pilot fl ame.

-  gently twist the pilot head to improve the fl ame pattern around the 
thermocouple.

Pilot fl ame is not engulfi ng the 
thermocouple.

Thermocouple shorting / 
faulty.

-  loosen and tighten thermocouple.
-  clean thermocouple and valve connection.
-  replace thermocouple.
-  replace valve.

Faulty valve.

-  replace.

Main burner fl ame 
i s   a   b l u e ,   l a z y, 
transparent fl ame.

Blockage in vent.

-  remove blockage. In really cold conditions, ice buildup may occur on 
the terminal and should be removed as required.

Incorrect installation.

-  refer to Figure 13 to ensure correct location of storm collars.

Flames are consis-
tently too large or 
too small. Carbon-
ing occurs.

-  check pressure readings:
Inlet pressure can be checked by turning screw (A) counter-clockwise 
2 or 3 turns and then placing pressure gauge tubing over the test point. 
Gauge should read 7” (minimum 4.5”) water column for natural gas or 
13” (11” minimum) water column for propane. Check that main burner 
is operating on “HI”.
Outlet pressure can be checked the same as above using screw (B). 
Gauge should read 3.5” water column for natural gas or 10” water col-
umn for propane. Check that main burner is operating on “HI”.
AFTER TAKING PRESSURE READINGS, BE SURE TO TURN 
SCREWS CLOCKWISE FIRMLY TO RESEAL. DO NOT OVER-
TORQUE.
Leak test with a soap and water solution.

Unit is over-fi red or under-
fi red.

A

B

E x h a u s t   f u m e s 
smelled in room, 
headaches.

Fireplace is spilling.

- check door seal and relief fl ap seal.
- check for chimney blockage
- check that the paint curing process is complete

TROUBLE SHOOTING GUIDE

SYMPTOM

PROBLEM

TEST SOLUTION

B

EFORE

 

ATTEMPTING

 

TO

 

TROUBLESHOOT

PURGE

 

YOUR

 

UNIT

 

AND

 

INITIALLY

 

LIGHT

 

THE

 

PILOT

 

AND

 

THE

 

MAIN

 

BURNER

 

WITH

 

THE

 

GLASS

 

DOOR

 

OPEN

.

Summary of Contents for BGD90NT

Page 1: ...e or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch...

Page 2: ...e fireplace should be located out of traffic and away from furniture and draperies Ensure you have incorporated adequate safety measure to protect infants toddlers from touching hot surfaces Even afte...

Page 3: ...his limited warranty further does not cover any scratches dents corrosion or discolouring caused by excessive heat abrasive and chemical cleaners nor chip ping on porcelain enamel parts mechanical bre...

Page 4: ...EARANCES See the section FRAMING See the section VENTING and IN STALLATION Side Wall See the section FRAMING See the section FRAMING and MINIMUM MANTEL AND ENCLOSURE CLEARANCES for Drywall or other co...

Page 5: ...ity clearance for servicing and operating the fireplace Never obstruct the front opening of the fireplace Objects placed in front of the fireplace must be kept a minimum of 48 from the front face of t...

Page 6: ...nimum rise per foot Provide a means for visually checking the vent connection to the fireplace after the fireplace is installed Do not allow the inside liner to bunch up on horizontal or vertical runs...

Page 7: ...ceptable FIGURE 5 90 H1 V2 H2 V1 HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT The shaded area within the lines represents acceptable values for HT and VT for the following symbols used in the venting ca...

Page 8: ...1 HT 4 2 VT Formula 2 HT VT 24 75 feet Example 2 Example 3 V1 4 ft V2 1 5 ft VT V1 V2 4 1 5 5 5 ft H1 2 ft H2 1 ft H3 1 ft H4 1 5 ft HR H1 H2 H3 H4 2 1 1 1 5 5 5 ft HO 03 four 90 elbows 90 03 360 90...

Page 9: ...uration is unacceptable Formula 2 HT VT 40 feet 20 6 40 Since only formula 2 is met this vent con guration is unacceptable and a new replace location or vent con guration will need to be established t...

Page 10: ...10 W415 0580 B 03 12 08 MINIMUM AIR TERMINAL LOCATION CLEARANCES FIGURE 12...

Page 11: ...E THE CORRECT HEIGHT CAULKING FIRESTOP ASSEMBLY VENT SHIELD FINISHING MATERIAL 14 1 2 FIGURE 13 VERTICAL INSTALLATION This application occurs when venting through a roof Installation kits for various...

Page 12: ...TICAL AIR TERMINAL INSTALLATION 1 Move the fireplace into position 2 Fasten the roof support to the roof using the screws provided The roof support is optional In this case the venting is to be adequa...

Page 13: ...the mobile home appliance MOBILE HOME This Mobile Manufactured Home Listed appliance comes factory equipped with a means to secure the unit The fireplace is equipped with two 1 4 diameter holes locat...

Page 14: ...14 W415 0580 B 03 12 08 59 1 4 1 MIN 1 MIN 116 82 FIGURE 25 FIGURE 28 59 1 4 29 1 2 29 1 2 10 MIN 59 1 4 FIGURE 26 FIGURE 27...

Page 15: ...e nishing Front 5 1 2 to sides of replace opening Front 5 1 2 to sides of replace opening 23 3 4 to top of replace opening 23 3 4 to top of replace opening See Venting Section See Venting Section It i...

Page 16: ...losure requires the replace junction box to be hard wired This replace must be electrically connected and grounded in ac cordance with local codes In the absence of local codes use the current CSA C22...

Page 17: ...the thick side of the gasket facing up 3 Bend the glass retainers located along the edge of the door frame over the gasket holding the glass in place Careful not to break the glass GLASS DOOR REPLACE...

Page 18: ...al use the panels will darken temporarily The appearance of the panels will permanently lighten in colour with use INSTALL PANELS IN THE FOLLOWING ORDER RETAINER Secure the Left Panel and Right Panel...

Page 19: ...ff of log 7 2 Place log 2 and log 3 onto the locating pins The logs should sit at on the burner 3 Place the locating hole on the underside of log 4 onto the locating pin on top of log 3 The notch at t...

Page 20: ...event the lamps or lens need replacing follow these instructions Shut off breaker at main power supply Remove the four screws that secure the lens frame to the Firebox top This frame retains the glass...

Page 21: ...and thermocouple 6 Remove screws securing gas valve to the mounting bracket VALVE REMOVAL 1 Open the right control door by pulling bottom portion away from magnet catch 2 Remove the hearth strip by li...

Page 22: ...itialized TEMPERATURE DISPLAY 1 Press the ON OFF key on the transmitter The transmitter display will show all active icons on the screen At the same time the receiver connects the thermopile to the ga...

Page 23: ...levels With the system on and the ame level at the maximum press the Down Arrow Key once and it will reduce the ame height by one step until the ame is turned off The Up Arrow Key will increase the am...

Page 24: ...rmostat function to control the replace during a power failure The blower and night light features will not operate during a power failure The receiver will emit a beep sound to con rm programming has...

Page 25: ...t follow these instruc tions exactly a re or explosion may result causing property damage personal injury or loss of life Initial lighting of the pilot and main burners must be done with the glass doo...

Page 26: ...ches toward the burner with the third jet 5 Replace the cleaned logs 6 Check to see that the main burner ignites completely on all openings when the gas knob for the burner is turned on A 5 to 10 seco...

Page 27: ...peci cally approved with this appliance may result in property damage or personal injury WARNING WARNING PART NO DESCRIPTION 1 W390 0002 DOOR LATCH EA 2 W725 0047 NATURAL GAS VALVE MODULATING 2 W725 0...

Page 28: ...28 W415 0580 B 03 12 08 6 4 8 7 5 41 23 28 29 30 31 35 27 26 34 64 33 66 32 11 65 21 2 15 16 12 3 14 19 17 71 55 58 22 79 63 69 70 13...

Page 29: ...pattern around the thermocouple Pilot ame is not engul ng the thermocouple Thermocouple shorting faulty loosen and tighten thermocouple clean thermocouple and valve connection replace thermocouple re...

Page 30: ...t will not light check if pilot can be lit by a match check that the wire is connected to the spark module check batteries replace the wire if the wire insulation is broken or frayed replace the elect...

Page 31: ...31 W415 0580 B 03 12 08 Fireplace Service History This fireplace must be serviced annually depending on usage DATE DEALER NAME SERVICE TECHNICIAN NAME SERVICE PERFORMANCE SPECIAL CONCERNS...

Page 32: ...32 W415 0580 B 03 12 08 NOTES...

Reviews: