Napoleon BGD90NT Installation And Operation Instructions Manual Download Page 11

11

W415-0580 / B / 03.12.08

INSTALLATION / FRAMING

WALL AND CEILING PROTECTION

HORIZONTAL VENT SECTIONS: 

A minimum clearance of 2” all around the vent pipe on all horizontal runs to combustibles is required 

except for clearances in fi replace enclosures**. Use fi restop spacer assembly W010-1797 (supplied).

VERTICAL VENT SECTIONS: 

A minimum of 1” all around the vent pipe on all vertical runs to combustibles is required except for clearances 

in fi replace enclosures**. Use fi restop spacer

 

W615-0075

 

(not supplied). 

** Horizontal and vertical sections require 5” and 9” clearance from combustibles, respectively. See minimum enclosure clearances sec-
tion. 

HORIZONTAL INSTALLATION

This application occurs when venting through an exterior wall. Having 
determined the correct height for the air terminal location, cut and frame a 
hole in the exterior wall 14 1/2” wide by 14 1/2” high to accommodate the 
firestop assembly. Dry fit the firestop assembly before proceeding to ensure 
the brackets on the rear surface fit to the inside surface of the horizontal 
framing.

NOTE:

 The firestop assembly must be installed with the vent shield to the 

top.

The length of the vent shield may be cut shorter for combustible walls that 
are less than 8 1/2" thick but the vent shield must extend the full depth of the 
combustible wall.

1. Apply a bead of caulking (not supplied) around the corner edge of the inside surface of 
the firestop assembly, fit the firestop assembly to the hole and secure using the 4 screws 
W415-0026 (supplied in your manual baggy).
2. Once the vent pipe is installed in its final position, apply high temperature sealant 
W573-0007 (not supplied) between the pipe and the firestop. 

NOTE:

 Do not fill the cavity between the pipe and the framing with any type of material.

14

1

/

2

DETERMINE
THE
CORRECT
HEIGHT

CAULKING

FIRESTOP

ASSEMBLY

VENT

SHIELD

FINISHING

MATERIAL

14

1

/

2

FIGURE 13

VERTICAL INSTALLATION

This application occurs when venting through a roof. Installation kits for various roof pitches are 
available from your NAPOLEON® dealer. See Accessories to order the specific kit required.

1.

 Determine the air terminal location, cut and frame 

141/2” x 141/2” openings in the ceiling and the roof to provide the minimum 2“ clearance between the 
fireplace pipe / liner and any combustible material. Try to centre the exhaust pipe location midway 
between two joist to prevent having to cut them. Use a plumb bob to line up the centre of the 
openings.  Do not fill this space with any type of material. 

A vent pipe shield will prevent any materials such as insulation, from filling up the 1” air space 
around the pipe. Nail headers between the joist for extra support. 

2.

Apply a bead of caulking (not supplied) to the framework or to the Wolf Steel vent pipe shield 

plate or equivalent (in the case of a finished ceiling), and secure over the opening in the ceiling.
A  firestop must be placed on the bottom of each framed opening in a roof or ceiling that the 
venting system passes through.  Apply a bead of caulking all around and place a firestop spacer 
over the vent shield to restrict cold air from being drawn into the room or around the fireplace. 
Ensure that both spacer and shield maintain the required clearance to combustibles. Once the vent 
pipe is installed in its final position, apply sealant W573-0002 (not supplied) between the pipe and the 
firestop spacer.    

3.

In the attic, after the pipe has been installed, slide the vent pipe collar down to cover up the 

open end of the shield and tighten. This will prevent any materials, such as insulation, from 
filling up the 1” air space around the pipe.

FIRESTOP

UNDERSIDE OF JOIST

14

1

/

2

14

1

/

2

CAULKING

VENT PIPE 

SHIELD

HI-TEMP 
SEALANT

2” OVERLAP

  #8X1/2”

SELF DRILLING 

     SCREWS

FIGURE 14

FIGURE 15

FIGURE 16

Summary of Contents for BGD90NT

Page 1: ...e or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch...

Page 2: ...e fireplace should be located out of traffic and away from furniture and draperies Ensure you have incorporated adequate safety measure to protect infants toddlers from touching hot surfaces Even afte...

Page 3: ...his limited warranty further does not cover any scratches dents corrosion or discolouring caused by excessive heat abrasive and chemical cleaners nor chip ping on porcelain enamel parts mechanical bre...

Page 4: ...EARANCES See the section FRAMING See the section VENTING and IN STALLATION Side Wall See the section FRAMING See the section FRAMING and MINIMUM MANTEL AND ENCLOSURE CLEARANCES for Drywall or other co...

Page 5: ...ity clearance for servicing and operating the fireplace Never obstruct the front opening of the fireplace Objects placed in front of the fireplace must be kept a minimum of 48 from the front face of t...

Page 6: ...nimum rise per foot Provide a means for visually checking the vent connection to the fireplace after the fireplace is installed Do not allow the inside liner to bunch up on horizontal or vertical runs...

Page 7: ...ceptable FIGURE 5 90 H1 V2 H2 V1 HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT The shaded area within the lines represents acceptable values for HT and VT for the following symbols used in the venting ca...

Page 8: ...1 HT 4 2 VT Formula 2 HT VT 24 75 feet Example 2 Example 3 V1 4 ft V2 1 5 ft VT V1 V2 4 1 5 5 5 ft H1 2 ft H2 1 ft H3 1 ft H4 1 5 ft HR H1 H2 H3 H4 2 1 1 1 5 5 5 ft HO 03 four 90 elbows 90 03 360 90...

Page 9: ...uration is unacceptable Formula 2 HT VT 40 feet 20 6 40 Since only formula 2 is met this vent con guration is unacceptable and a new replace location or vent con guration will need to be established t...

Page 10: ...10 W415 0580 B 03 12 08 MINIMUM AIR TERMINAL LOCATION CLEARANCES FIGURE 12...

Page 11: ...E THE CORRECT HEIGHT CAULKING FIRESTOP ASSEMBLY VENT SHIELD FINISHING MATERIAL 14 1 2 FIGURE 13 VERTICAL INSTALLATION This application occurs when venting through a roof Installation kits for various...

Page 12: ...TICAL AIR TERMINAL INSTALLATION 1 Move the fireplace into position 2 Fasten the roof support to the roof using the screws provided The roof support is optional In this case the venting is to be adequa...

Page 13: ...the mobile home appliance MOBILE HOME This Mobile Manufactured Home Listed appliance comes factory equipped with a means to secure the unit The fireplace is equipped with two 1 4 diameter holes locat...

Page 14: ...14 W415 0580 B 03 12 08 59 1 4 1 MIN 1 MIN 116 82 FIGURE 25 FIGURE 28 59 1 4 29 1 2 29 1 2 10 MIN 59 1 4 FIGURE 26 FIGURE 27...

Page 15: ...e nishing Front 5 1 2 to sides of replace opening Front 5 1 2 to sides of replace opening 23 3 4 to top of replace opening 23 3 4 to top of replace opening See Venting Section See Venting Section It i...

Page 16: ...losure requires the replace junction box to be hard wired This replace must be electrically connected and grounded in ac cordance with local codes In the absence of local codes use the current CSA C22...

Page 17: ...the thick side of the gasket facing up 3 Bend the glass retainers located along the edge of the door frame over the gasket holding the glass in place Careful not to break the glass GLASS DOOR REPLACE...

Page 18: ...al use the panels will darken temporarily The appearance of the panels will permanently lighten in colour with use INSTALL PANELS IN THE FOLLOWING ORDER RETAINER Secure the Left Panel and Right Panel...

Page 19: ...ff of log 7 2 Place log 2 and log 3 onto the locating pins The logs should sit at on the burner 3 Place the locating hole on the underside of log 4 onto the locating pin on top of log 3 The notch at t...

Page 20: ...event the lamps or lens need replacing follow these instructions Shut off breaker at main power supply Remove the four screws that secure the lens frame to the Firebox top This frame retains the glass...

Page 21: ...and thermocouple 6 Remove screws securing gas valve to the mounting bracket VALVE REMOVAL 1 Open the right control door by pulling bottom portion away from magnet catch 2 Remove the hearth strip by li...

Page 22: ...itialized TEMPERATURE DISPLAY 1 Press the ON OFF key on the transmitter The transmitter display will show all active icons on the screen At the same time the receiver connects the thermopile to the ga...

Page 23: ...levels With the system on and the ame level at the maximum press the Down Arrow Key once and it will reduce the ame height by one step until the ame is turned off The Up Arrow Key will increase the am...

Page 24: ...rmostat function to control the replace during a power failure The blower and night light features will not operate during a power failure The receiver will emit a beep sound to con rm programming has...

Page 25: ...t follow these instruc tions exactly a re or explosion may result causing property damage personal injury or loss of life Initial lighting of the pilot and main burners must be done with the glass doo...

Page 26: ...ches toward the burner with the third jet 5 Replace the cleaned logs 6 Check to see that the main burner ignites completely on all openings when the gas knob for the burner is turned on A 5 to 10 seco...

Page 27: ...peci cally approved with this appliance may result in property damage or personal injury WARNING WARNING PART NO DESCRIPTION 1 W390 0002 DOOR LATCH EA 2 W725 0047 NATURAL GAS VALVE MODULATING 2 W725 0...

Page 28: ...28 W415 0580 B 03 12 08 6 4 8 7 5 41 23 28 29 30 31 35 27 26 34 64 33 66 32 11 65 21 2 15 16 12 3 14 19 17 71 55 58 22 79 63 69 70 13...

Page 29: ...pattern around the thermocouple Pilot ame is not engul ng the thermocouple Thermocouple shorting faulty loosen and tighten thermocouple clean thermocouple and valve connection replace thermocouple re...

Page 30: ...t will not light check if pilot can be lit by a match check that the wire is connected to the spark module check batteries replace the wire if the wire insulation is broken or frayed replace the elect...

Page 31: ...31 W415 0580 B 03 12 08 Fireplace Service History This fireplace must be serviced annually depending on usage DATE DEALER NAME SERVICE TECHNICIAN NAME SERVICE PERFORMANCE SPECIAL CONCERNS...

Page 32: ...32 W415 0580 B 03 12 08 NOTES...

Reviews: