* HORIZONTAL VENT SECTIONS:
A minimum of 1" (25mm) at the bottom and sides and 3" (76mm) at the top
of the vent pipe on all horizontal runs to combustibles is required. Use
fi
restop spacer W010-1774 (supplied).
* VERTICAL VENT SECTIONS:
A minimum of 1" (25mm) all around the vent pipe on all vertical runs to
combustibles is required except for clearances in appliance enclosures. See "MINIMUM ENCLOSURE
CLEARANCES" section. Use
fi
restop spacer W500-0096 (not supplied).
Minimum clearance to combustible construction from appliance and vent surfaces:
Combustible
Framing:
-
0" to stand-offs
-
1" (25mm) to bottom and sides of the vent pipe*
-
3" (76mm) to top of the vent pipe*
Combustible Finishing:
-
0" to rear
-
0" to front face top and sides
Top Exit
-
50 1/2" (1283mm) to combustible enclosure top from base of the appliance
-
54" (1372mm) to ceiling from base of the appliance
Rear Exit
-
36" (914mm) to combustible enclosure top from base of the appliance
-
54" (1372mm) to ceiling from base of the appliance
18 9/16"
471mm
2" 51mm
INSIDE
CHASE
OUTSIDE
CHASE
PROTRUSION
18 9/16"
471mm
42 1/2" 1080mm
SIDE
WALL
42 1/2" 1080mm
34 3/4"
883mm
42 1/2"
1080mm
56"
1422mm