Napoleon B36DFN Installation And Operation Instructions Manual Download Page 28

28

W415-0484 / A / 07.26.06

Pilot goes out
while standing;
Main burner is in
'OFF' position.

Gas piping is undersized.

-  turn on all gas appliances and see if pilot flame flutters, dimin-

ishes or extinguishes, especially when main burner ignites. Monitor
appliance supply working pressure.

-  check if supply piping size is to code. Correct all undersized piping.

Flames are con-
sistently too large
or too small.
Carboning occurs.

-  check pressure readings:
Inlet pressure can be checked by turning screw (A) counter-clock-
wise 2 or 3 turns and then placing pressure gauge tubing over the
test point. Gauge should read 7" (minimum 4.5") water column for
natural gas or 13" (11" minimum) water column for propane. Check
that main burner is operating on "HI".
Outlet pressure can be checked the same as above using screw (B).
Gauge should read 3.5" water column for natural gas or 10" water
column for propane. Check that main burner is operating on "HI".
AFTER TAKING PRESSURE READINGS, BE SURE TO TURN
SCREWS CLOCKWISE FIRMLY TO RESEAL. DO NOT OVERTORQUE.
Leak test with a soap and water solution.

Unit is over-fired or under-
fired.

White / grey film
forms.

Sulphur from fuel is being
deposited on glass, logs or
combustion chamber sur-
faces.

-  clean the glass with a recommended gas fireplace glass cleaner.
DO NOT CLEAN GLASS WHEN HOT.

If deposits are not cleaned off regularly, the glass may become
permanently marked.

Main burner flame
is a blue, lazy,
transparent flame.

Blockage in vent.

-  remove blockage. In extremely cold conditions, ice buildup may
occur on the terminal and should be removed as required.

-  ensure correct location of storm collars.

Incorrect installation.

-  check that the logs are correctly positioned.
-  open air shutter to increase the primary air.
-  check the input rate: check the manifold pressure and orifice size
as specified by the rating plate values.
- check that the door gasketing is not broken or missing and that the
seal is tight.
- check that both 5" and 8" vent liners are free of holes and well
sealed at all joints.
- check that minimum rise per foor has been adhered to for any
horizontal venting.

Carbon is being
deposited on
glass, logs or com-
bustion chamber
surfaces.

Flame is impinging on the
logs or combustion cham-
ber.

Air shutter has become
blocked

-  ensure air shutter opening is free of lint or other obstructions.

Remote wall
switch is in "OFF"
position; main
burner comes on
when gas knob is
turned to "ON" po-
sition.

Wall switch is mounted up-
side down

- reverse.

Faulty valve.

- replace.

- replace.

Remote wall switch is
grounding.

- check for ground (short); repair ground or replace wire.

Remote wall switch wire is
grounding.

Flames are very
aggressive.

- fit door assembly into the lower support brackets and secure the
two door latches.

Door is ajar

Venting action is too great.

-restrict vent exit with restrictor plate, 

W500-0205.

SYMPTOM

PROBLEM

TEST SOLUTION

Summary of Contents for B36DFN

Page 1: ...1 W415 0484 A 07 23 06 W415 0484 A 07 26 06...

Page 2: ...WHAT TO DO IF YOU SMELL GAS WARNINGS SAFETY PRECAUTIONS...

Page 3: ...rt of the control system and any gas control which has been under water Do not operate the fireplace with the glass door removed cracked or broken Replacement of the glass should be done by a licensed...

Page 4: ...are covered and eting and pilot assembly are covered and eting and pilot assembly are covered and eting and pilot assembly are covered and NAPOLEON NAPOLEON NAPOLEON NAPOLEON NAPOLEON will provide re...

Page 5: ...tates FOR YOUR SATISFACTION THIS FIREPLACE HAS BEEN TEST FIRED TO ASSURE ITS OPERATION AND QUALITY Maximum input is 23 000 BTU hr for natural gas and propane When the fireplace is installed at elevati...

Page 6: ...ce performance keep the vent length and number of elbows to a minimum The air terminal must remain unobstructed at all times Examine the air terminal at least once a year to verify that it is unobstru...

Page 7: ...tly closed windows Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet from the centerline of the terminal Clearance to unventilated soffit Cleara...

Page 8: ...m of 12 inches above grade The maximum allow able vent length depends on the fireplace as illustrated FIGURES3a c FIGURE4 TYPICAL VENT INSTALLATIONS SPECIAL VENT INSTALLATIONS NOTE When terminating ve...

Page 9: ...ntal run Horizontal run verti cal rise to maximum of 40 feet Vertical rise is less than horizontal run Horizontal run verti cal rise to m a x i m u m of 24 75 feet 4 2 times the vertical rise equal to...

Page 10: ...offset 135 in feet VT combined vertical vent lengths in feet feet inches 1 0 03 0 5 15 0 45 6 0 30 0 9 11 0 45 1 35 16 0 90 2 7 32 0 the first 45 and 90 offset has a zero value and is shown in the fo...

Page 11: ...ET HT when HT VT Simple venting configuration only one 45 and 90 elbow Example 2 V1 4ft V2 1 5ft VT V1 V2 4 ft 1 5 ft 5 5 ft H1 2ft H2 1ft H3 1ft H4 1 5ft HR H1 H2 H3 H4 2 1 1 1 5 5 5 ft HO 03 one 45...

Page 12: ...s are met this vent configuration is ac ceptable when HT VT Simple venting configurations FIGURE9 REQUIRED VERTICAL RISE IN FEET VT HORIZONTAL VENT RUN PLUS OFFSETS IN FEET HT FIGURE10 For vent config...

Page 13: ...eptable Formula 2 HT VT 40 feet 15 9 40 Since only formula 2 is met this vent configuration is unac ceptable and a new fireplace location or vent configuration will need to be established to satisfy b...

Page 14: ...nce the vent pipe liner is installed in its final position apply sealant between the pipe liner and the firestop spacer FIGURE16 This application occurs when vent ing through an exterior wall Having d...

Page 15: ...runs Use noncombustible strapping to maintain the minimum 1 clearance to combustibles FIGURE19 HORIZONTAL AIR TERMINAL INSTALLATION VERTICAL AIR TERMINAL INSTALLATION 4 Insert the liners through the...

Page 16: ...use open flame Do not connect either the wall switch thermostat or gas valve to electricity 110 volts Purge all gas lines with the glass door of the fireplace removed Assure that a continuous gas flow...

Page 17: ...for use with other gases unless a certified kit is used Conversion Kits The mobile home appliance is field convertible between Natural Gas NG and Propane LP To convert from Natural Gas to Propane ord...

Page 18: ...32b 2 To determine the final location of the nailing tab you must first determine the thickness of your finishing mate rial i e drywall This will determine the dimension from the front edge of the cor...

Page 19: ...g Secure using a screw through the centre slot LOWER LOUVRES Insert the hinge clips into the slots located at the bottom left and right corners of the unit To remove the louvres pull the back tabs of...

Page 20: ...ll of the burner area in front of the small logs 2 3 Care should be taken to shred the embers into thin small irregular pieces as only the exposed edges of the fibre hairs will glow The ember material...

Page 21: ...ireplace base or the firebox Attach the connectors from the black and white wires to the thermodisc and secure the thermodisc bracket to the unit at the bottom left of the unit using the ground screw...

Page 22: ...Steel Napoleon dealer With the thermostatic sensor option the fan when turned on becomes thermally activated and will automatically run approximately 15 30 minutes after the fireplace has been lit and...

Page 23: ...smell gas including near the floor Stop Follow B in the above safety information on this label If you don t smell gas go the next step 5 Turn gas knob counter clockwise to pilot 6 Depress slightly and...

Page 24: ...yellow flame but can lead to carboning Opening the air shutter will cause a more blue flame but can cause flame lifting from the burner ports The flame may not appear yellow immediately allow 15 to 30...

Page 25: ...KIT ARCHED BLACK 55 DK36 AG DOOR KIT ARCHED GOLD PLATED 56 DK36 W DOOR KIT WEBBED BLACK 56 DK36 WG DOOR KIT WEBBED GOLD PLATED 57 GA 566 HOT AIR KIT 58 GA 72 HOT AIR EXHAUST KIT 59 GA 70 EXTENSION KI...

Page 26: ...ouple It is an integral safety component Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd AT TE NT ION CH AU D CA UT ION HO T 5 4 6 3 22 46 49 50 53 52 51 38 21 54 57 55 28 23 5...

Page 27: ...an interlock device which will not allow the pilot burner to be lit until the ther mocouple has cooled Allow ap proximately 60 seconds for the thermocouple to cool System is not correctly purged purge...

Page 28: ...aned off regularly the glass may become permanently marked Main burner flame is a blue lazy transparent flame Blockage in vent remove blockage In extremely cold conditions ice buildup may occur on the...

Page 29: ...29 W415 0484 A 07 23 06 Wolf Steel Fireplace Service History This fireplace must be serviced annually depending on usage Date Service Technician Name Service Performed Special Concerns Dealer Name...

Page 30: ...30 W415 0484 A 07 26 06 NOTES...

Reviews: