Napoleon B36DFN Installation And Operation Instructions Manual Download Page 15

15

W415-0484 / A / 07.23.06

INNER FLEX

LINER

OUTER 

FLEX

LINER

INNER 

SLEEVE

HIGH

TEMPERATURE

SEALANT

AIR 

TERMINAL

CONNECTOR

FIGURE 18

A VENT SHIELD MUST BE USED IF THE WALL TERMINAL IS
INSTALLED ON COMBUSTIBLE, EXTERIOR SURFACES.

1. 

Cut or frame a hole in an exterior wall with a minimum

oval or rectangle opening of 10½"w x 11 ½"h. Secure the
firestop spacer over the opening to the interior wall, ensur-
ing 2" clearance above the vent pipe opening.

2.

 Stretch the 5" diameter aluminum flexible liner to the

required length taking into account the additional length
needed for the finished wall surface. Slip the liner a mini-
mum of 2" over the inner sleeve of the air terminal and
secure with 3 #8 screws. Apply a heavy bead of the high
temperature sealant.

3.

 Using the 8" diameter flexible aluminum liner, slide

over the outer combustion air sleeve of the air terminal and
secure with 3 #8 screws. Seal as before.

The air terminal mounting plate may be recessed into
the exterior wall or siding by 1½", the depth of the return
flange.

5. 

Apply a heavy bead of the high temperature sealant,

Mill Pac, to the inside of the 5" liner approximately 1" from
the end. Slip the liner a minimum of 2" over the fireplace
vent collar and secure with 3  #8 screws.

6. 

Using the 8" diameter flexible aluminium liner, apply

sealant, slide a minimum of 2" over the fireplace combus-
tion air collar and secure with 3 #8 screws.

7. 

If more liner needs to be used to reach the fireplace,

couple them together as illustrated. The vent system must
be supported approximately every 3 feet for both vertical
and horizontal runs. Use noncombustible strapping to
maintain the minimum 1" clearance to combustibles.

FIGURE 19

HORIZONTAL AIR TERMINAL INSTALLATION

VERTICAL AIR TERMINAL INSTALLATION

4.

 Insert the liners through the firestop maintaining the

required clearance to combustibles. Holding the air termi-
nal (lettering in an upright, readable position), secure to
the exterior wall and make weather tight by sealing with
caulking (not supplied).

Use only approved  aluminum flexible liner kits marked:

"Wolf Steel Approved Venting" as
identified by the stamp only on the 8”
outer liner.

USING FLEXIBLE VENT COMPONENTS

For safe and proper operation of the fireplace, follow the vent-
ing instructions exactly.

All inner exhaust and outer intake vent pipe joints may be
sealed using either Red RTV high temp silicone sealant or
Black high temp Mill Pac with the exception of the fireplace
exhaust flue collar which must be sealed using Mill Pac
(not supplied).

1. Fasten the roof
support to the roof
using the screws
provided. The roof
support is optional.
In this case the
venting is to be
a d e q u a t e l y
supported using
either an alternate
method suitable to

the authority having jurisdiction or the optional roof support.

2. Stretch the exhaust to
the required length. Slip
the liner a minimum of
2" over the inner sleeve
of the air terminal and
secure with 3 #8 screws.
Seal using a heavy bead
of the high temperature
sealant.

3. Repeat using air

intake vent pipe.

4. Thread the air

terminal pipe assembly
down through the roof.
The air terminal must be
located vertically and
plumb. Attach the air
terminal assembly to the
roof support, ensuring that a minimum 16" of air terminal
will penetrate the roof when fastened.

DO NOT CLAMP THE FLEXIBLE ALUMINIUM LINER.

ROOF SUPPORT

FIGURE 20

FIGURE 21

Summary of Contents for B36DFN

Page 1: ...1 W415 0484 A 07 23 06 W415 0484 A 07 26 06...

Page 2: ...WHAT TO DO IF YOU SMELL GAS WARNINGS SAFETY PRECAUTIONS...

Page 3: ...rt of the control system and any gas control which has been under water Do not operate the fireplace with the glass door removed cracked or broken Replacement of the glass should be done by a licensed...

Page 4: ...are covered and eting and pilot assembly are covered and eting and pilot assembly are covered and eting and pilot assembly are covered and NAPOLEON NAPOLEON NAPOLEON NAPOLEON NAPOLEON will provide re...

Page 5: ...tates FOR YOUR SATISFACTION THIS FIREPLACE HAS BEEN TEST FIRED TO ASSURE ITS OPERATION AND QUALITY Maximum input is 23 000 BTU hr for natural gas and propane When the fireplace is installed at elevati...

Page 6: ...ce performance keep the vent length and number of elbows to a minimum The air terminal must remain unobstructed at all times Examine the air terminal at least once a year to verify that it is unobstru...

Page 7: ...tly closed windows Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet from the centerline of the terminal Clearance to unventilated soffit Cleara...

Page 8: ...m of 12 inches above grade The maximum allow able vent length depends on the fireplace as illustrated FIGURES3a c FIGURE4 TYPICAL VENT INSTALLATIONS SPECIAL VENT INSTALLATIONS NOTE When terminating ve...

Page 9: ...ntal run Horizontal run verti cal rise to maximum of 40 feet Vertical rise is less than horizontal run Horizontal run verti cal rise to m a x i m u m of 24 75 feet 4 2 times the vertical rise equal to...

Page 10: ...offset 135 in feet VT combined vertical vent lengths in feet feet inches 1 0 03 0 5 15 0 45 6 0 30 0 9 11 0 45 1 35 16 0 90 2 7 32 0 the first 45 and 90 offset has a zero value and is shown in the fo...

Page 11: ...ET HT when HT VT Simple venting configuration only one 45 and 90 elbow Example 2 V1 4ft V2 1 5ft VT V1 V2 4 ft 1 5 ft 5 5 ft H1 2ft H2 1ft H3 1ft H4 1 5ft HR H1 H2 H3 H4 2 1 1 1 5 5 5 ft HO 03 one 45...

Page 12: ...s are met this vent configuration is ac ceptable when HT VT Simple venting configurations FIGURE9 REQUIRED VERTICAL RISE IN FEET VT HORIZONTAL VENT RUN PLUS OFFSETS IN FEET HT FIGURE10 For vent config...

Page 13: ...eptable Formula 2 HT VT 40 feet 15 9 40 Since only formula 2 is met this vent configuration is unac ceptable and a new fireplace location or vent configuration will need to be established to satisfy b...

Page 14: ...nce the vent pipe liner is installed in its final position apply sealant between the pipe liner and the firestop spacer FIGURE16 This application occurs when vent ing through an exterior wall Having d...

Page 15: ...runs Use noncombustible strapping to maintain the minimum 1 clearance to combustibles FIGURE19 HORIZONTAL AIR TERMINAL INSTALLATION VERTICAL AIR TERMINAL INSTALLATION 4 Insert the liners through the...

Page 16: ...use open flame Do not connect either the wall switch thermostat or gas valve to electricity 110 volts Purge all gas lines with the glass door of the fireplace removed Assure that a continuous gas flow...

Page 17: ...for use with other gases unless a certified kit is used Conversion Kits The mobile home appliance is field convertible between Natural Gas NG and Propane LP To convert from Natural Gas to Propane ord...

Page 18: ...32b 2 To determine the final location of the nailing tab you must first determine the thickness of your finishing mate rial i e drywall This will determine the dimension from the front edge of the cor...

Page 19: ...g Secure using a screw through the centre slot LOWER LOUVRES Insert the hinge clips into the slots located at the bottom left and right corners of the unit To remove the louvres pull the back tabs of...

Page 20: ...ll of the burner area in front of the small logs 2 3 Care should be taken to shred the embers into thin small irregular pieces as only the exposed edges of the fibre hairs will glow The ember material...

Page 21: ...ireplace base or the firebox Attach the connectors from the black and white wires to the thermodisc and secure the thermodisc bracket to the unit at the bottom left of the unit using the ground screw...

Page 22: ...Steel Napoleon dealer With the thermostatic sensor option the fan when turned on becomes thermally activated and will automatically run approximately 15 30 minutes after the fireplace has been lit and...

Page 23: ...smell gas including near the floor Stop Follow B in the above safety information on this label If you don t smell gas go the next step 5 Turn gas knob counter clockwise to pilot 6 Depress slightly and...

Page 24: ...yellow flame but can lead to carboning Opening the air shutter will cause a more blue flame but can cause flame lifting from the burner ports The flame may not appear yellow immediately allow 15 to 30...

Page 25: ...KIT ARCHED BLACK 55 DK36 AG DOOR KIT ARCHED GOLD PLATED 56 DK36 W DOOR KIT WEBBED BLACK 56 DK36 WG DOOR KIT WEBBED GOLD PLATED 57 GA 566 HOT AIR KIT 58 GA 72 HOT AIR EXHAUST KIT 59 GA 70 EXTENSION KI...

Page 26: ...ouple It is an integral safety component Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd AT TE NT ION CH AU D CA UT ION HO T 5 4 6 3 22 46 49 50 53 52 51 38 21 54 57 55 28 23 5...

Page 27: ...an interlock device which will not allow the pilot burner to be lit until the ther mocouple has cooled Allow ap proximately 60 seconds for the thermocouple to cool System is not correctly purged purge...

Page 28: ...aned off regularly the glass may become permanently marked Main burner flame is a blue lazy transparent flame Blockage in vent remove blockage In extremely cold conditions ice buildup may occur on the...

Page 29: ...29 W415 0484 A 07 23 06 Wolf Steel Fireplace Service History This fireplace must be serviced annually depending on usage Date Service Technician Name Service Performed Special Concerns Dealer Name...

Page 30: ...30 W415 0484 A 07 26 06 NOTES...