7.2 ACCEPTABLE MATERIALS IN UNITED STATES
7.0 VENTING AND COMBUSTION PIPING
7.1 ACCEPTABLE MATERIALS IN CANADA
H3.10
READ, UNDERSTAND AND FOLLOW ALL INSTRUCTIONS IN THIS SECTION. FAILURE TO
PROPERLY VENT OR SUPPLY COMBUSTION AIR TO THIS FURNACE CAN CAUSE CAR-
BON MONOXIDE POISONING, OR AN EXPLOSION OR FIRE, RESULTING IN PROPERTY
DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
WARNING
!
!
H11.1A
Effective August 1, 2007, all vent piping materials and
fi
ttings for
fl
ue gas venting must be ULC S636 listed
and identi
fi
ed as such on the material. The
fi
rst 3ft. (900mm) of venting must be readily available for visual
inspection. Speci
fi
ed primers and glues of the certi
fi
ed vent system must be from a single system manufacture,
and not intermixed with other system manufacture’s vent system parts. The components of the certi
fi
ed vent
system must not be interchanged with other vent systems, or unlisted pipe, and or
fi
ttings. Follow the venting
manufacturers instructions on installation, cutting, de-burring, cementing, curing and supporting of the venting
system.
Furnace must be vented with ULC S636 certi
fi
ed PVC manufactured by IPEX, or ULC S636 certi
fi
ed PPE
manufactured by M&G Duravent.
PVC vent terminations may use concentric kits listed in section 10.3 - or terminate using 45 and 90 degree
elbows.
PPE venting must terminate using 45 and 90 degree elbows.
Minimum rating of 149 degrees F (65°C).
H11.2A
Furnace venting may be comprised of:
•
Schedule 40 PVC, ASTM D1785 or CSA B137.3
•
PVC-DWV, ASTM D2665 or CSA B181.2
•
Schedule 40 CPVC, ASTM F441 or CSA B137.6
•
PVC PRIMER AND SOLVENT CEMENT: ASTM D2564
•
PPE ULC S636 Manufactured by M&G Duravent - must terminate using 45 and 90 degree elbows.
Follow piping manufacturers instructions on proper installation of piping and
fi
ttings including cutting, deburring,
priming, cementing, curing and supporting.
Summary of Contents for 9700 SERIES
Page 1: ......
Page 28: ...W415 1243 A 03 19 15 27 IOM FIGURE 14A DIRECT VENT TERMINAL CLEARANCES...
Page 29: ...W415 1243 A 03 19 15 28 IOM IOM FIGURE 14B NON DIRECT VENT TERMINAL CLEARANCES...
Page 59: ...W415 1243 A 03 19 15 58 IOM IOM 23 0 SERVICE HISTORY 43 1...
Page 75: ...6 0 NOTES 44 1 W415 1243 A 03 19 15 UM 74...