W415-1243 / A / 03.19.15
12
IOM
IOM
5.0 COMBUSTIBLE CLEARANCES
H9.0
Table B provides the certi
fi
ed clearances to combustibles information. Also see the appliance rating plate
af
fi
xed to the furnace for speci
fi
c model number, serial number and clearance to combustibles information.
IMPORTANT
:
THIS FURNACE REQUIRES A MINIMUM OF 24" (610mm) OF FRONT CLEARANCE FOR
SERVICE PURPOSES. FOR THIS PURPOSE, SERVICE CLEARANCE TAKES PRECE-
DENCE OVER CLEARANCE TO COMBUSTIBLES.
H3.7
THIS FURNACE IS CERTIFIED FOR INSTALLATION ON COMBUSTIBLE FLOORS. THIS
SHALL BE INTERPRETED AS A WOOD FLOOR ONLY.
THE FURNACE MUST NOT BE INSTALLED DIRECTLY ON CARPETING, OR OTHER
COMBUSTIBLE MATERIAL EXCEPT WOOD.
INSTALLATION ON COMBUSTIBLE MATERIAL CAN RESULT IN FIRE, CAUSING PROPERTY
DAMAGE, PERSONAL INJURY OR DEATH.
THE AREA AROUND THE FURNACE MUST BE KEPT CLEAR AND FREE OF ALL
COMBUSTIBLE MATERIALS INCLUDING GASOLINE AND OTHER FLAMMABLE VAPORS
AND LIQUIDS.
THE HOMEOWNER SHOULD BE CAUTIONED THAT THE FURNACE AREA MUST NOT BE
USED AS A CLOSET OR FOR ANY OTHER STORAGE PURPOSE.
WARNING
!
!