background image

StarLink

 SLE-LTE Commercial Series Alarm Communicators -- Installation Instructions 

(Commercial Fire and Commercial Burglary) 

SLELTEV-CFB-PS  

Wiring Diagram 

SLELTEV-CFB-PS  

PC Board 

All connections are power limited except AC 

Mains, Telco and battery terminals 

Power Supply 
(SLE-ULPS-R)  

15 

14 

13 

12 

11 

9  10 

2*  3 

1* 

+V 

(

)  PGM1 PGM2 PGM3 

IN3 

RING 

TIP 

17 

16 

RTS 

(R) 

PANEL  

TX (B) 

PANEL  

RX (G) 

CTS 

Yellow 

Trouble 

LED 

Green AC 

ON LED 

+ BAT – 

RED   BLK 

4  5 

10 

N/C 

COM

 N/O 

Bl

ack (

Re

d (+)

 

Battery 

.5A 

Fuse 

PANEL  

RING 

PANEL  

TIP 

GND 

(To  

control 
panel*) 

16.5VAC 

Class 2 

*Notes: 



Connect the StarLink radio to the control panel output for Telco Trouble (this is the DACT interconnect wiring to the 
radio).  Remember to program the StarLink communicator module to report this 

IN2 

Telco Trouble and for line cut 

(EOLR) to the central station (options 1 or 4 on page 17).  In addition, always add an EOLR at the control panel Telco 
Trouble Output (Fire Aux Relay for the GEMC control panels). 



Use EOLR value as specified by the control panel installation instructions. 



IN1 

not supervised.  

IN2 

and 

IN3 

are supervised.   



Licensed electrician required to wire the 120VAC connections to the transformer in accordance with N.E.C. and local 
code requirements. 



Route 120VAC only through the transformer compartment knockouts. 



Keep all non-power limited wiring separate from all power-limited wiring inside the housing by 1/4".  In addition, maintain 
a minimum 1/4" separation of all primary wiring in the transformer compartment from the yellow secondary wires of the 
transformer. 



Remove shunt J2 to isolate relay common from ground (i.e. jumper on = wet (circuit common); off = dry contact).  When 
wet, configuration is used; the power should be derived from the alarm control panel.   



StarLink module must be configured to trigger PGM1 on any trouble. 



PGM1 of the StarLink module must be wired to the trouble input (terminal 5) of the power supply. 



The Power Supply Trouble Output must be wired to a control panel zone dedicated to a LTE trouble; see control panel 
programming instructions and program to Report Alarm / Alarm Restore / Trouble / Trouble Restore. 

IN1 

+ 12V 

 

AC IN 

Note:  Maintain 
minimum 1/4" 
separation of 
battery leads from 
all other wiring. 

EOLR

IN1 

J2 

Remo

ve

 shunt J2 to is

olate relay

 

common from ground (i.e. j

u

mp-

er on =

 w

e

t; off =

 dry

 c

ontact) 

 

Chassis Mounted 16.5VAC / 20VA Transformer 

BLK 

Note:  Maintain minimum 1/4" separation 
of all wiring in this compartment from the 
yellow wires of the transformer. 

Terminals 14-17:  No connections permitted . 

Relay con-

tacts rated 

max 30VDC, 

0.5A 

12VDC 

output is 

power limited 

(Earth Ground) 

IN2* 

Note:

  Connect IN2 to a 

panel output used for 
identifying Telco line cut (this 
is the DACT interconnect 
wiring to the radio). 

Summary of Contents for StarLink SLE-LTE Commercial Series

Page 1: ...y com Note Technical Service is for security professionals only Publicly traded on NASDAQ Symbol NSSC NAPCO 2018 INTRODUCTION The StarLink Commercial Residential Fire and Burglary alarm capture radio communicators are fully supervised wireless digital two way subscriber units supported by an extensive nationwide wireless network All models are compatible with most 12VDC alarm control panels always...

Page 2: ...n structions Note Antennas are not Listed by UL For LTE radios where an External Antenna needs to be in stalled outside of the room in which the radio is installed maximum 30 meters 98 feet in Residential applica tions please use RF Transmitter Board 9SLELTEEXAPSLD available from our Customer Ser vice Department if not provided The 9SLELTEEXAPSLD is identified by two red dots locat ed on the lower...

Page 3: ...oc com Located at the bottom of the StarLink radio PC board the 17 terminals are described as follows TB1 PWR 12V Note Model SLE LTEV CFB is rat ed 12 24VDC input Refer to section STEP 4 APPLY POWER TB2 PWR GND Refer to section STEP 4 APPLY POWER TB3 PGM1 Open collector output PGM1 is nor mally on active low When it is triggered for ex ample a trouble is detected it becomes open col lector high To...

Page 4: ...rrent due to the application such as when 24 hour standby time is required for Fire or CO the SLE ULPS R Charger Module accessory must be used to charge an additional battery and to supply the power for the StarLink radio See WI2131 JUMPER DESCRIPTIONS Jumper block labeled X5 from top to bottom as detailed in the following table Note Contact ID is always available in response to a Contact ID hands...

Page 5: ... StarLink radio can also func tion as a backup to the existing telephone lines install jumper 3 in terminal block X5 When used as a backup communicator and when it senses telephone line trouble the StarLink radio automatically switches the communica tion channel from the telephone line to the network NETWORK COVERAGE The StarLink radio constantly supervises the network cov erage When the StarLink ...

Page 6: ...n receivers via TCP IP STARLINK RADIO RELATED EVENT REPORT CODES Contact ID by default EVENT AREA CONTACT ID CODE ZONE IN 1 Fire 0 E110 990 1A IN 2 Panic 0 E120 992 22 IN 3 Trouble 0 E300 993 F3 Low Battery Voltage 0 E302 994 F4 Tamper Trouble 0 E341 995 F5 Line Cut 0 E352 996 F6 Reboot 0 E625 997 F7 IN 1 CO Carbon Monoxide 0 E162 998 18 Panic Alarm E123 Holdup Alarm E122 Medical Alarm E100 24 hou...

Page 7: ...o PGM activates the control panel zone and the panel generates a trouble that is sent to the central station All installations also require wiring an output from the control panel as follows With Gemini C Series GEMC control panels we recommend using the Fire Aux Relay Program the Fire Aux Relay to activate as a trouble relay Wire this relay to the StarLink module IN2 terminal Note We recommend us...

Page 8: ...the transformer compartment knockouts Keep all non power limited wiring separate from all power limited wiring inside the housing by 1 4 In addition maintain a minimum 1 4 separation of all primary wiring in the transformer compartment from the yellow secondary wires of the transformer Remove shunt J2 to isolate relay common from ground i e jumper on wet circuit common off dry contact When wet con...

Page 9: ...ing inside the housing by 1 4 Remove shunt J2 to isolate relay common from ground i e jumper on wet circuit common off dry contact When wet configuration is used the power should be derived from the alarm control panel StarLink module must be configured to trigger PGM1 on any trouble PGM1 of the StarLink module must be wired to the trouble input terminal 5 of the power supply The Power Supply Trou...

Page 10: ...ither the TRF12 T123 16 5V 20VA transformer or the chas sis mounted 16 5VAC 20VA transformer Transformer optional Optional When Power Supply SLE ULPS R is not used connect Panel Aux Power to StarLink terminals 1 and 2 observing polarity Wire to dedicated zone on the control panel for Supervision when the Power Supply board SLE ULPS R is not used SLE LTEV CB TF PC Board All connections are power li...

Page 11: ...TIP STARLINK RADIO HOUSING Power Supply SLE ULPS R Either the TRF12 T123 16 5V 20VA transformer or the chassis mounted 16 5VAC 20VA transformer optional Transformer TELCO QUAD WIRE Optional When Power Supply SLE ULPS R is not used connect Panel Aux Power to StarLink terminals 1 and 2 observing polarity ZONE DEDICATED TO SUPERVISION 8 9 10 N C COM N O J2 EOLR Wire to dedicated zone on the control p...

Page 12: ...nstructions for the GEMC F8ZCPIM as a Monitor Zone Only When PGM1 is wired to a GEMC F8ZCPIM zone replace the 2 2k ohm EOL resistor with a 560ohm 1 2 watt min EOL resistor Connect PGM1 to the negative terminal of the zone When PGM2 and or PGM3 are wired to a GEMC F8ZCPIM zone replace the 2 2k ohm EOL resistor with two 1K ohm 1 4 watt min EOL resistors Connect the PGM wire to the common wire of the...

Page 13: ... Radio Terminals PANEL RING PANEL TIP STARLINK RADIO HOUSING Either the TRF12 T123 16 5V 20VA transformer or the chassis mounted 16 5VAC 20VA transformer StarLink BATTERY RED BLACK Power Supply SLE ULPS R optional 2 2K 8 9 10 N C COM N O J2 2 2K ZONE DEDICATED TO SUPER VISION CONTROL PANEL HOUSING SLE LTEV CB TF PC Board All con nections are power limited except AC Mains Telco and battery terminal...

Page 14: ...TTERY RED BLACK Refer to section SUPPLYING POWER 6 7 8 15 14 13 12 11 9 10 2 3 4 5 1 V PGM1 PGM2 PGM3 IN1 IN2 GND IN3 RING TIP 17 16 RTS R PANEL TX B PANEL RX G CTS Y StarLink Radio Terminals PANEL RING PANEL TIP STARLINK RADIO HOUSING Power Supply SLE ULPS R Either the TRF12 T123 16 5V 20VA transformer or the chassis mounted 16 5VAC 20VA transformer optional 8 9 10 N C COM N O J2 Optional When Po...

Page 15: ...iring Diagram for PRIMARY Reporting Configuration GEM X255 GEM P9600 GEM P3200 Control Panels Use when telephone line is NOT available AUX POWER CONTROL PANEL HOUSING 13 14 15 16 17 18 19 20 21 22 26 27 28 29 23 24 25 33 30 31 32 Control Panel PC Board un polarized Refer to section SUPPLYING POWER TIP RING TIP RING TEL LINE PHONE ZONE DEDICATED TO SUPERVISION 2 2K un polarized SLE LTEV CB TF PC Bo...

Page 16: ...N GRAY GRAY Optional When Power Supply SLE ULPS R is not used connect Panel Aux Power to StarLink terminals 1 and 2 observing polarity GRN RED YELLOW BLACK StarLink BATTERY RED BLACK Refer to section SUPPLYING POWER 6 7 8 15 14 13 12 11 9 10 2 3 4 5 1 V PGM1 PGM2 PGM3 IN1 IN2 GND IN3 RING TIP 17 16 RTS R PANEL TX B PANEL RX G CTS Y StarLink Radio Terminals PANEL RING PANEL TIP STARLINK RADIO HOUSI...

Page 17: ... report Open Close radio remembers last state of panel for Napco panels when used with local download cable 5 BURG without DACT Use IN2 or IN3 for both Alarm and Trouble Panel has alarm and Trouble Relay PGM outputs Two EOLRs are needed since for UL Burg it is required to detect both wire breaks and shorts ALARM TBL ALARM TBL TBL TBL No Supervised Burg Alarm Trouble Requires two 10K EOLRs Three of...

Page 18: ... wire to a zone on the control panel GEM Tamperkit consists of Description QTY SC206LF Slotted Pan Head 6 32 x 3 4 Machine Screw 6 SW105 Tamper Switch 2 Tamper Switch Mounting Instructions Back Tamper Door Tamper VIEW OF TAMPER SWITCHES 1 ENCLOSURE BASE 2 BACK TAMPER SWITCH TO PREVENT REMOVAL FROM WALL 3 DOOR TAMPER SWITCH TO PROTECT THE ENCLOSURE DOOR 1 3 2 NYCFD Conditions of Acceptability 1 Onl...

Page 19: ...23 TRANSFORMER FOR CONNECTION TO SLE CHARGER BOARD UL LISTED SURFACE OR FLUSH MOUNT OUTLET BOX AND NON SWITCHED RECEPTACLE WALL TRANSFORMER SECONDARY WIRING CONDUIT LIMITED TO 20 FEET MAXIMUM LENGTH Maintain a minimum of 1 4 inch separation of circuits transformer secondary wiring from 120V branch circuit EXAMPLE OF CONDUIT LOCATION Optional Alternate Methods for Commercial Fire Branch Circuit Pow...

Page 20: ...compromised or circumvented or that the product or system will prevent any personal injury or property loss by burglary robbery fire or otherwise nor that the product or system will in all cases provide adequate warning or protection A properly installed and maintained alarm may only reduce risk of burglary robbery fire or otherwise but it is not insurance or a guarantee that these events will not...

Reviews: