2
StarLink
™
SLE-LTE Commercial Series Alarm Communicators -- Installation Instructions
NOTICE TO AUTHORITIES HAVING JURISDICTION, USERS, INSTALLERS,
DEALERS, AND OTHER AFFECTED PARTIES
Unattended Remote Downloading
No
Enable / Disable
Disabled (Jumper 1 installed). Also required for Commercial / Burgla-
ry installations.
Note:
See page 7 "
Configuration Download / Firm-
ware Updates
" for jumper instructions.
IN2
and
IN3
Unsupervised
Yes
Supervised / Unsupervised
Unsupervised using conduit within 20 feet of FACP (default). If not
using conduit, install Jumpers 4 and 5 and EOL Resistors (see pages
3 and 4).
7 Day Supervision, Radio to NOC
No
200 seconds, 5 minutes,
60 minutes, 7 days
200 seconds, 5 minutes, 60 minutes
FIRE PROGRAMMING OPTION
PERMITTED IN
UL864? (Y/N)
AVAILABLE SETTINGS
REQUIRED UL 864 SETTINGS
ed inside its own housing compartment with a replaceable
UL Listed .5A fast blow primary fuse. 120VAC connections
are to be made by a licensed electrician using suitable con-
nectors, in accordance with N.E.C. and local code require-
ments.
ADDITIONAL COMPONENTS
In addition to the models listed above, the following sub-
assemblies are available:
SLE-ULPS-R
- Power Supply. Required for installations
where the control panel cannot provide the 71mA of
Auxiliary power required to operate the StarLink radio.
Uses a standard 4AH / 12V minimum (7AH maximum)
rechargeable battery to provide radio standby power.
Requires connection to either the model NAPCO
TRF12/T123 (16.5V / 20VA) external plug-in transformer
or the chassis-mounted 16.5VAC / 20VA transformer
affixed inside the housing (see wiring diagrams further in
this manual).
Note:
For models without the SLE-ULPS-
R, connect the radio terminals 1 and 2 to the control
panel Aux Power terminals (observing polarity).
SLE-DLCBL
- Download Cable, 6 feet
SLE-ANTEXT30
- Extended antenna with 30 feet of cable
SLE-ANTEXT50
- Extended antenna with 50 feet of cable
SLE-ANTEXT75
- Extended antenna with 75 feet of cable
(Any suitable external cellular antenna is permitted by
UL). Always follow the manufacturer's installation in-
structions.
Note:
Antennas are not Listed by UL. For
LTE radios where an External Antenna needs to be in-
stalled outside of the room in which the radio is installed
(maximum 30 meters (98 feet) in Residential applica-
tions), please use RF Transmitter Board
9SLELTEEXAPSLD available from our Customer Ser-
vice Department, if not provided. The
9SLELTEEXAPSLD is identified by "two red dots" locat-
ed on the lower right corner of the board. See WI2239
included with the 9SLELTEEXAPSLD for the simple in-
stallation procedure.
GEM-Tamperkit
- Tamper switches and screws to protect
metal housing (see page 18).
SPECIFICATIONS
The following specifications apply to all StarLink radio mod-
els unless otherwise stated:
Electrical Ratings for 120VAC, 60Hz
For Models with Power Supply
Input Voltage: 120VAC nominal
Input Current: 150mA maximum
Maximum Charging Current: 200mA
Electrical Ratings for +12V
For Models without Power Supply*
Input Voltage: 10-15VDC (power-limited output from
Listed control panel).
Note:
Model
SLE-LTEV-CFB
is
rated 10-25VDC input.
Input Current for
SLE-LTEV-CB
: 10V = 90mA, 12V =
71mA, 15V = 63mA, with peak RF transmission current
of 200mA.
Input Current for
SLE-LTEV-CFB
: 10V = 90mA, 12V =
71mA, 25V = 68mA, with peak RF transmission current
of 200mA.
Electrical Ratings for the IN 1 Burg/Fire Input:
Input Voltage: 9-15VDC.
Note:
Model
SLE-LTEV-CFB
is rated 9-25VDC input.
Maximum Input Current: Up to 2mA from FACP NAC
circuit
Electrical Ratings for IN 2 and IN 3:
Maximum Loop Voltage: 15VDC.
Note:
Model
SLE-
LTEV-CFB
is rated max 25VDC input.
Maximum Loop Current: 1.2mA
End of Line Resistor (EOLR) Value: 10K (2 req'd)
Electrical Ratings for 3 PGM Outputs:
Open Collector Outputs: Maximum Voltage 3V when
active; 15V maximum when not active.
Note:
Model
SLE-LTEV-CFB
is rated max 25VDC output.
Maximum PGM Sink Current: 50mA (up to 15VDC),
25mA (15.1VDC - 25VDC)
Physical (W x H x D)
Metal Housing: 11½ x 9½ x 3½" (29.2 x 24.1 x 8.9cm)
Mounting: Metal housing includes two keyhole slots for
wall mounting (see measurements on page 7)
Environmental
Operating Temperature: 0°C - 49°C (32°F - 120°F)
Humidity: Maximum 93% Non-Condensing
Indoor / dry location use only
*For Commercial Fire installations, a UL Listed Fire Alarm regulated power supply or FACP regulated auxiliary output is required.