 SLE-LTE Commercial Series Alarm Communicators -- Installation Instructions 

NOTICE TO AUTHORITIES HAVING JURISDICTION, USERS, INSTALLERS,  

DEALERS, AND OTHER AFFECTED PARTIES 

Unattended Remote Downloading 

No 

Enable / Disable 

Disabled (Jumper 1 installed).  Also required for Commercial / Burgla-
ry installations. 

 Note:

  See page 7 "

Configuration Download / Firm-

ware Updates

" for jumper instructions.   

IN2 

and 

IN3 

Unsupervised 

Yes 

Supervised / Unsupervised 

Unsupervised using conduit within 20 feet of FACP (default).  If not 
using conduit, install Jumpers 4 and 5 and EOL Resistors (see pages 
3 and 4). 

7 Day Supervision, Radio to NOC 

No 

200 seconds, 5 minutes, 

60 minutes, 7 days 

200 seconds, 5 minutes, 60 minutes 

FIRE PROGRAMMING OPTION 

PERMITTED IN 

UL864? (Y/N) 

AVAILABLE SETTINGS 

REQUIRED UL 864  SETTINGS

 

ed inside its own housing compartment with a replaceable 
UL Listed .5A fast blow primary fuse.  120VAC connections 
are to be made by a licensed electrician using suitable con-
nectors, in accordance with N.E.C. and local code require-
ments. 

 

ADDITIONAL COMPONENTS 

  In addition to the models listed above, the following sub-

assemblies are available: 

SLE-ULPS-R 

- Power Supply.  Required for installations 

where the control panel cannot provide the 71mA of 
Auxiliary power required to operate the StarLink radio.  
Uses a standard 4AH / 12V minimum (7AH maximum) 
rechargeable battery to provide radio standby power.  
Requires connection to either the model NAPCO 
TRF12/T123 (16.5V / 20VA) external plug-in transformer 
or the chassis-mounted 16.5VAC / 20VA transformer 
affixed inside the housing (see wiring diagrams further in 
this manual).  

Note:  

For models without the SLE-ULPS-

R, connect the radio terminals 1 and 2 to the control 
panel Aux Power terminals (observing polarity). 

SLE-DLCBL

 -  Download Cable, 6 feet 

SLE-ANTEXT30

 - Extended antenna with 30 feet of cable 

SLE-ANTEXT50

 - Extended antenna with 50 feet of cable 

SLE-ANTEXT75

 - Extended antenna with 75 feet of cable 

  (Any suitable external cellular antenna is permitted by 

UL).  Always follow the manufacturer's installation in-
structions.  

Note:

  Antennas are not Listed by UL.  For 

LTE radios where an External Antenna needs to be in-
stalled outside of the room in which the radio is installed 
(maximum 30 meters (98 feet) in Residential applica-
tions), please use RF Transmitter Board 
9SLELTEEXAPSLD available from our Customer Ser-
vice Department, if not provided.  The 
9SLELTEEXAPSLD is identified by "two red dots" locat-
ed on the lower right corner of the board.  See WI2239 
included with the 9SLELTEEXAPSLD for the simple in-
stallation procedure.   

GEM-Tamperkit

 - Tamper switches and screws to protect 

metal housing (see page 18). 

 

SPECIFICATIONS

 

 

The following specifications apply to all StarLink radio mod-
els unless otherwise stated: 

 

  Electrical Ratings for 120VAC, 60Hz 
  For Models with Power Supply

 



Input Voltage:  120VAC nominal 



Input Current: 150mA maximum 



Maximum Charging Current:  200mA 

 

  Electrical Ratings for +12V  
  For Models without Power Supply* 



Input Voltage:  10-15VDC (power-limited output from 
Listed control panel).  

Note:

  Model 

SLE-LTEV-CFB

 is 

rated 10-25VDC input. 



Input Current for 

SLE-LTEV-CB

:  10V = 90mA, 12V = 

71mA, 15V = 63mA, with peak RF transmission current 
of 200mA.   



Input Current for 

SLE-LTEV-CFB

:  10V = 90mA, 12V = 

71mA, 25V = 68mA, with peak RF transmission current 
of 200mA. 

 

  Electrical Ratings for the IN 1 Burg/Fire Input: 



Input Voltage:  9-15VDC.  

Note:

  Model 

SLE-LTEV-CFB

 

is rated 9-25VDC input. 



Maximum Input Current:  Up to 2mA from FACP NAC 
circuit 

 

  Electrical Ratings for IN 2 and IN 3: 



Maximum Loop Voltage:  15VDC.  

Note:

  Model 

SLE-

LTEV-CFB

 is rated max 25VDC input. 



Maximum Loop Current:  1.2mA 



End of Line Resistor (EOLR) Value:  10K (2 req'd) 

 

  Electrical Ratings for 3 PGM Outputs: 



Open Collector Outputs:  Maximum Voltage 3V when 
active; 15V maximum when not active.  

Note:

  Model 

SLE-LTEV-CFB

 is rated max 25VDC output. 



Maximum PGM Sink Current:  50mA (up to 15VDC), 
25mA (15.1VDC - 25VDC) 

 

  Physical (W x H x D) 



Metal Housing:  11½ x 9½ x 3½" (29.2 x 24.1 x 8.9cm) 



Mounting:  Metal housing includes two keyhole slots for 
wall mounting (see measurements on page 7)   

 

 Environmental 



Operating Temperature:  0°C - 49°C (32°F - 120°F)  



Humidity:  Maximum 93% Non-Condensing 



Indoor / dry location use only 

 

*For Commercial Fire installations, a UL Listed Fire Alarm regulated power supply or FACP regulated auxiliary output is required.   

Summary of Contents for StarLink SLE-LTE Commercial Series

Page 1: ...y com Note Technical Service is for security professionals only Publicly traded on NASDAQ Symbol NSSC NAPCO 2018 INTRODUCTION The StarLink Commercial Residential Fire and Burglary alarm capture radio communicators are fully supervised wireless digital two way subscriber units supported by an extensive nationwide wireless network All models are compatible with most 12VDC alarm control panels always...

Page 2: ...n structions Note Antennas are not Listed by UL For LTE radios where an External Antenna needs to be in stalled outside of the room in which the radio is installed maximum 30 meters 98 feet in Residential applica tions please use RF Transmitter Board 9SLELTEEXAPSLD available from our Customer Ser vice Department if not provided The 9SLELTEEXAPSLD is identified by two red dots locat ed on the lower...

Page 3: ...oc com Located at the bottom of the StarLink radio PC board the 17 terminals are described as follows TB1 PWR 12V Note Model SLE LTEV CFB is rat ed 12 24VDC input Refer to section STEP 4 APPLY POWER TB2 PWR GND Refer to section STEP 4 APPLY POWER TB3 PGM1 Open collector output PGM1 is nor mally on active low When it is triggered for ex ample a trouble is detected it becomes open col lector high To...

Page 4: ...rrent due to the application such as when 24 hour standby time is required for Fire or CO the SLE ULPS R Charger Module accessory must be used to charge an additional battery and to supply the power for the StarLink radio See WI2131 JUMPER DESCRIPTIONS Jumper block labeled X5 from top to bottom as detailed in the following table Note Contact ID is always available in response to a Contact ID hands...

Page 5: ... StarLink radio can also func tion as a backup to the existing telephone lines install jumper 3 in terminal block X5 When used as a backup communicator and when it senses telephone line trouble the StarLink radio automatically switches the communica tion channel from the telephone line to the network NETWORK COVERAGE The StarLink radio constantly supervises the network cov erage When the StarLink ...

Page 6: ...n receivers via TCP IP STARLINK RADIO RELATED EVENT REPORT CODES Contact ID by default EVENT AREA CONTACT ID CODE ZONE IN 1 Fire 0 E110 990 1A IN 2 Panic 0 E120 992 22 IN 3 Trouble 0 E300 993 F3 Low Battery Voltage 0 E302 994 F4 Tamper Trouble 0 E341 995 F5 Line Cut 0 E352 996 F6 Reboot 0 E625 997 F7 IN 1 CO Carbon Monoxide 0 E162 998 18 Panic Alarm E123 Holdup Alarm E122 Medical Alarm E100 24 hou...

Page 7: ...o PGM activates the control panel zone and the panel generates a trouble that is sent to the central station All installations also require wiring an output from the control panel as follows With Gemini C Series GEMC control panels we recommend using the Fire Aux Relay Program the Fire Aux Relay to activate as a trouble relay Wire this relay to the StarLink module IN2 terminal Note We recommend us...

Page 8: ...the transformer compartment knockouts Keep all non power limited wiring separate from all power limited wiring inside the housing by 1 4 In addition maintain a minimum 1 4 separation of all primary wiring in the transformer compartment from the yellow secondary wires of the transformer Remove shunt J2 to isolate relay common from ground i e jumper on wet circuit common off dry contact When wet con...

Page 9: ...ing inside the housing by 1 4 Remove shunt J2 to isolate relay common from ground i e jumper on wet circuit common off dry contact When wet configuration is used the power should be derived from the alarm control panel StarLink module must be configured to trigger PGM1 on any trouble PGM1 of the StarLink module must be wired to the trouble input terminal 5 of the power supply The Power Supply Trou...

Page 10: ...ither the TRF12 T123 16 5V 20VA transformer or the chas sis mounted 16 5VAC 20VA transformer Transformer optional Optional When Power Supply SLE ULPS R is not used connect Panel Aux Power to StarLink terminals 1 and 2 observing polarity Wire to dedicated zone on the control panel for Supervision when the Power Supply board SLE ULPS R is not used SLE LTEV CB TF PC Board All connections are power li...

Page 11: ...TIP STARLINK RADIO HOUSING Power Supply SLE ULPS R Either the TRF12 T123 16 5V 20VA transformer or the chassis mounted 16 5VAC 20VA transformer optional Transformer TELCO QUAD WIRE Optional When Power Supply SLE ULPS R is not used connect Panel Aux Power to StarLink terminals 1 and 2 observing polarity ZONE DEDICATED TO SUPERVISION 8 9 10 N C COM N O J2 EOLR Wire to dedicated zone on the control p...

Page 12: ...nstructions for the GEMC F8ZCPIM as a Monitor Zone Only When PGM1 is wired to a GEMC F8ZCPIM zone replace the 2 2k ohm EOL resistor with a 560ohm 1 2 watt min EOL resistor Connect PGM1 to the negative terminal of the zone When PGM2 and or PGM3 are wired to a GEMC F8ZCPIM zone replace the 2 2k ohm EOL resistor with two 1K ohm 1 4 watt min EOL resistors Connect the PGM wire to the common wire of the...

Page 13: ... Radio Terminals PANEL RING PANEL TIP STARLINK RADIO HOUSING Either the TRF12 T123 16 5V 20VA transformer or the chassis mounted 16 5VAC 20VA transformer StarLink BATTERY RED BLACK Power Supply SLE ULPS R optional 2 2K 8 9 10 N C COM N O J2 2 2K ZONE DEDICATED TO SUPER VISION CONTROL PANEL HOUSING SLE LTEV CB TF PC Board All con nections are power limited except AC Mains Telco and battery terminal...

Page 14: ...TTERY RED BLACK Refer to section SUPPLYING POWER 6 7 8 15 14 13 12 11 9 10 2 3 4 5 1 V PGM1 PGM2 PGM3 IN1 IN2 GND IN3 RING TIP 17 16 RTS R PANEL TX B PANEL RX G CTS Y StarLink Radio Terminals PANEL RING PANEL TIP STARLINK RADIO HOUSING Power Supply SLE ULPS R Either the TRF12 T123 16 5V 20VA transformer or the chassis mounted 16 5VAC 20VA transformer optional 8 9 10 N C COM N O J2 Optional When Po...

Page 15: ...iring Diagram for PRIMARY Reporting Configuration GEM X255 GEM P9600 GEM P3200 Control Panels Use when telephone line is NOT available AUX POWER CONTROL PANEL HOUSING 13 14 15 16 17 18 19 20 21 22 26 27 28 29 23 24 25 33 30 31 32 Control Panel PC Board un polarized Refer to section SUPPLYING POWER TIP RING TIP RING TEL LINE PHONE ZONE DEDICATED TO SUPERVISION 2 2K un polarized SLE LTEV CB TF PC Bo...

Page 16: ...N GRAY GRAY Optional When Power Supply SLE ULPS R is not used connect Panel Aux Power to StarLink terminals 1 and 2 observing polarity GRN RED YELLOW BLACK StarLink BATTERY RED BLACK Refer to section SUPPLYING POWER 6 7 8 15 14 13 12 11 9 10 2 3 4 5 1 V PGM1 PGM2 PGM3 IN1 IN2 GND IN3 RING TIP 17 16 RTS R PANEL TX B PANEL RX G CTS Y StarLink Radio Terminals PANEL RING PANEL TIP STARLINK RADIO HOUSI...

Page 17: ... report Open Close radio remembers last state of panel for Napco panels when used with local download cable 5 BURG without DACT Use IN2 or IN3 for both Alarm and Trouble Panel has alarm and Trouble Relay PGM outputs Two EOLRs are needed since for UL Burg it is required to detect both wire breaks and shorts ALARM TBL ALARM TBL TBL TBL No Supervised Burg Alarm Trouble Requires two 10K EOLRs Three of...

Page 18: ... wire to a zone on the control panel GEM Tamperkit consists of Description QTY SC206LF Slotted Pan Head 6 32 x 3 4 Machine Screw 6 SW105 Tamper Switch 2 Tamper Switch Mounting Instructions Back Tamper Door Tamper VIEW OF TAMPER SWITCHES 1 ENCLOSURE BASE 2 BACK TAMPER SWITCH TO PREVENT REMOVAL FROM WALL 3 DOOR TAMPER SWITCH TO PROTECT THE ENCLOSURE DOOR 1 3 2 NYCFD Conditions of Acceptability 1 Onl...

Page 19: ...23 TRANSFORMER FOR CONNECTION TO SLE CHARGER BOARD UL LISTED SURFACE OR FLUSH MOUNT OUTLET BOX AND NON SWITCHED RECEPTACLE WALL TRANSFORMER SECONDARY WIRING CONDUIT LIMITED TO 20 FEET MAXIMUM LENGTH Maintain a minimum of 1 4 inch separation of circuits transformer secondary wiring from 120V branch circuit EXAMPLE OF CONDUIT LOCATION Optional Alternate Methods for Commercial Fire Branch Circuit Pow...

Page 20: ...compromised or circumvented or that the product or system will prevent any personal injury or property loss by burglary robbery fire or otherwise nor that the product or system will in all cases provide adequate warning or protection A properly installed and maintained alarm may only reduce risk of burglary robbery fire or otherwise but it is not insurance or a guarantee that these events will not...

Reviews: