 SLE-LTE Commercial Series Alarm Communicators -- Installation Instructions 

signal strength detected, it will blink the Signal Strength 
LED from 1 to 8 times, providing a signal strength indica-
tor that is updated constantly and is always displayed.  
Refer to Coverage Table below.

 

 

 

Green LED Operation 

 

Signal strength (as received by the radio) is displayed by 
this LED blinking 1 to 8 times at a constant rate (with a 
short delay between blink cycles).  Acceptable power 
level is greater than or equal to -91dBm (minimum 4 
blinks at the mounting location).   

 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 

 

  YELLOW OPERATIONAL STATUS LED 

 Labeled 

"

D4

", this LED is located at the bottom right of 

the PC board.  Operation is as follows: 

 

  Normal Standby Condition: 



Blinks on momentarily every 10 seconds:  

Unit is in 

standby waiting for an alarm to report. 

  Processing Alarm Conditions: 



When processing an alarm, this LED will blink variably 
during each part of the process (dialing, handshaking, 
data transmission, etc.). 

 

  RED TROUBLE LED 

 Labeled 

"

D5

", this LED is located at the bottom right of 

the PC board.  Operation is as follows: 



1 Blink: 

 Low Aux Power input voltage 



2 Blinks: 

 Battery trouble 



3 Blinks:

  Alarm report Failed to Communicate  



4 Blinks:

  RF trouble (antenna connection or cellu-

lar registration)  



5 Blinks:

  Network trouble (signal unable to reach 

the SLE Control Center)  



6 Blinks: 

 Unit disabled (reporting or control panel 

downloading not allowed)  



7 Blinks:

  Unit was shutdown and has no function-

ality; requires a restart (full power down and full power 
up sequence) to restore operation 



8 Blinks:

  Telco Line Cut (this is not the DACT inter-

connect to the radio) 

 

  RED DIAGNOSTIC LED 

 Labeled 

"

D7

", this LED is located in the middle of the PC 

board.  One blink indicates a weak or non-existent signal 
from the network (green LED is off). If this red LED is 
blinking in any other manner, please contact technical 
support.   

 

SUPPLYING POWER 

  Control panels can provide power through their Auxiliary 

Power terminals if the available standby current is reduced by 
71mA.  When there is insufficient standby current due to the 
application (such as when 24-hour standby time is required 
for Fire or CO), the SLE-ULPS-R Charger Module accessory 
must be used to charge an additional battery and to supply 
the power for the StarLink radio.  See WI2131. 

 

JUMPER DESCRIPTIONS 

 

Jumper block labeled "

X5

"; from top to bottom, as detailed in 

the following table.  

Note:

 Contact ID is always available in 

response to a Contact ID handshake. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
  The StarLink SLE-LTE Series radios are compatible with 

any Listed alarm control unit DACT communicating contact 
ID or any 4+2 pulse format (4/2 Pulse Dialing formats such 
as Ademco Slow, Radionics Slow, Silent Knight Fast, Radi-
onics Fast and Universal High Speed, with 10pps, 20pps, 
and 40pps with and without checksum, either 1400Hz or 
2300Hz handshake / kissoff).   

 

 

The StarLink SLE-LTE Series radios and NOC are compati-
ble with the Listed Ademco model 685 with model 685-8 line 
card DACR or any Listed compatible DACR with any 4+2 
pulse or contact ID format which is specified in the Installa-
tion Instructions for the interconnected DACT / Alarm Con-
trol Unit. 

 

  Refer to WI2140 (available on the NOC) for selecting the 

required handshake / kissoff frequency in the NOC 
(

www.NapcoNOC.com

) setup screens (as required by the 

control panel).   

 

PRIMARY AND BACK-UP REPORTING 

 

The StarLink radio can function as a primary wireless com-
municator, in cases where there are no telephone lines pre-
sent, when connected directly to the control panel Telco 

Jumper Block "X5" Options 

Jumper block labeled "X5" contains 5 jumper terminals; from top  

(labeled "1") to bottom (labeled "5") as follows:

 

Jumper ON 

Jumper  

Number

 

Jumper OFF 

Tech on site must temporarily 

remove to download 

Not permitted by UL 864 and  

UL 1610 

4/2 with Checksum Pulse Format  

4/2 Pulse Format 

Backup Mode 

Primary Mode 

Supervised inputs.  EOLR(s) re-

quired, see page 3 

and 

Not permitted by UL 864 and  

UL 1610 (UL 864 permits use of 

conduit within 20 feet of FACP in 

lieu of Supervision) 

D4  D3  D5 

RED DIAGNOSTIC LED (Labeled "D7")

 

YELLOW OPERATIONAL STATUS LED (Labeled "D4") 

GREEN RF SIGNAL STRENGTH LED (Labeled "D3") 

RED TROUBLE LED (Labeled "D5")

 

LED LOCATIONS 

GREEN RF SIGNAL STRENGTH LED 

RADIO RECEIVER COVERAGE TABLE 

LED Blinks 

-55 

-65 

-75 

-85 

-91 

-95 

-99 

-105 

Power 

(dBm) 

Summary of Contents for StarLink SLE-LTE Commercial Series

Page 1: ...y com Note Technical Service is for security professionals only Publicly traded on NASDAQ Symbol NSSC NAPCO 2018 INTRODUCTION The StarLink Commercial Residential Fire and Burglary alarm capture radio communicators are fully supervised wireless digital two way subscriber units supported by an extensive nationwide wireless network All models are compatible with most 12VDC alarm control panels always...

Page 2: ...n structions Note Antennas are not Listed by UL For LTE radios where an External Antenna needs to be in stalled outside of the room in which the radio is installed maximum 30 meters 98 feet in Residential applica tions please use RF Transmitter Board 9SLELTEEXAPSLD available from our Customer Ser vice Department if not provided The 9SLELTEEXAPSLD is identified by two red dots locat ed on the lower...

Page 3: ...oc com Located at the bottom of the StarLink radio PC board the 17 terminals are described as follows TB1 PWR 12V Note Model SLE LTEV CFB is rat ed 12 24VDC input Refer to section STEP 4 APPLY POWER TB2 PWR GND Refer to section STEP 4 APPLY POWER TB3 PGM1 Open collector output PGM1 is nor mally on active low When it is triggered for ex ample a trouble is detected it becomes open col lector high To...

Page 4: ...rrent due to the application such as when 24 hour standby time is required for Fire or CO the SLE ULPS R Charger Module accessory must be used to charge an additional battery and to supply the power for the StarLink radio See WI2131 JUMPER DESCRIPTIONS Jumper block labeled X5 from top to bottom as detailed in the following table Note Contact ID is always available in response to a Contact ID hands...

Page 5: ... StarLink radio can also func tion as a backup to the existing telephone lines install jumper 3 in terminal block X5 When used as a backup communicator and when it senses telephone line trouble the StarLink radio automatically switches the communica tion channel from the telephone line to the network NETWORK COVERAGE The StarLink radio constantly supervises the network cov erage When the StarLink ...

Page 6: ...n receivers via TCP IP STARLINK RADIO RELATED EVENT REPORT CODES Contact ID by default EVENT AREA CONTACT ID CODE ZONE IN 1 Fire 0 E110 990 1A IN 2 Panic 0 E120 992 22 IN 3 Trouble 0 E300 993 F3 Low Battery Voltage 0 E302 994 F4 Tamper Trouble 0 E341 995 F5 Line Cut 0 E352 996 F6 Reboot 0 E625 997 F7 IN 1 CO Carbon Monoxide 0 E162 998 18 Panic Alarm E123 Holdup Alarm E122 Medical Alarm E100 24 hou...

Page 7: ...o PGM activates the control panel zone and the panel generates a trouble that is sent to the central station All installations also require wiring an output from the control panel as follows With Gemini C Series GEMC control panels we recommend using the Fire Aux Relay Program the Fire Aux Relay to activate as a trouble relay Wire this relay to the StarLink module IN2 terminal Note We recommend us...

Page 8: ...the transformer compartment knockouts Keep all non power limited wiring separate from all power limited wiring inside the housing by 1 4 In addition maintain a minimum 1 4 separation of all primary wiring in the transformer compartment from the yellow secondary wires of the transformer Remove shunt J2 to isolate relay common from ground i e jumper on wet circuit common off dry contact When wet con...

Page 9: ...ing inside the housing by 1 4 Remove shunt J2 to isolate relay common from ground i e jumper on wet circuit common off dry contact When wet configuration is used the power should be derived from the alarm control panel StarLink module must be configured to trigger PGM1 on any trouble PGM1 of the StarLink module must be wired to the trouble input terminal 5 of the power supply The Power Supply Trou...

Page 10: ...ither the TRF12 T123 16 5V 20VA transformer or the chas sis mounted 16 5VAC 20VA transformer Transformer optional Optional When Power Supply SLE ULPS R is not used connect Panel Aux Power to StarLink terminals 1 and 2 observing polarity Wire to dedicated zone on the control panel for Supervision when the Power Supply board SLE ULPS R is not used SLE LTEV CB TF PC Board All connections are power li...

Page 11: ...TIP STARLINK RADIO HOUSING Power Supply SLE ULPS R Either the TRF12 T123 16 5V 20VA transformer or the chassis mounted 16 5VAC 20VA transformer optional Transformer TELCO QUAD WIRE Optional When Power Supply SLE ULPS R is not used connect Panel Aux Power to StarLink terminals 1 and 2 observing polarity ZONE DEDICATED TO SUPERVISION 8 9 10 N C COM N O J2 EOLR Wire to dedicated zone on the control p...

Page 12: ...nstructions for the GEMC F8ZCPIM as a Monitor Zone Only When PGM1 is wired to a GEMC F8ZCPIM zone replace the 2 2k ohm EOL resistor with a 560ohm 1 2 watt min EOL resistor Connect PGM1 to the negative terminal of the zone When PGM2 and or PGM3 are wired to a GEMC F8ZCPIM zone replace the 2 2k ohm EOL resistor with two 1K ohm 1 4 watt min EOL resistors Connect the PGM wire to the common wire of the...

Page 13: ... Radio Terminals PANEL RING PANEL TIP STARLINK RADIO HOUSING Either the TRF12 T123 16 5V 20VA transformer or the chassis mounted 16 5VAC 20VA transformer StarLink BATTERY RED BLACK Power Supply SLE ULPS R optional 2 2K 8 9 10 N C COM N O J2 2 2K ZONE DEDICATED TO SUPER VISION CONTROL PANEL HOUSING SLE LTEV CB TF PC Board All con nections are power limited except AC Mains Telco and battery terminal...

Page 14: ...TTERY RED BLACK Refer to section SUPPLYING POWER 6 7 8 15 14 13 12 11 9 10 2 3 4 5 1 V PGM1 PGM2 PGM3 IN1 IN2 GND IN3 RING TIP 17 16 RTS R PANEL TX B PANEL RX G CTS Y StarLink Radio Terminals PANEL RING PANEL TIP STARLINK RADIO HOUSING Power Supply SLE ULPS R Either the TRF12 T123 16 5V 20VA transformer or the chassis mounted 16 5VAC 20VA transformer optional 8 9 10 N C COM N O J2 Optional When Po...

Page 15: ...iring Diagram for PRIMARY Reporting Configuration GEM X255 GEM P9600 GEM P3200 Control Panels Use when telephone line is NOT available AUX POWER CONTROL PANEL HOUSING 13 14 15 16 17 18 19 20 21 22 26 27 28 29 23 24 25 33 30 31 32 Control Panel PC Board un polarized Refer to section SUPPLYING POWER TIP RING TIP RING TEL LINE PHONE ZONE DEDICATED TO SUPERVISION 2 2K un polarized SLE LTEV CB TF PC Bo...

Page 16: ...N GRAY GRAY Optional When Power Supply SLE ULPS R is not used connect Panel Aux Power to StarLink terminals 1 and 2 observing polarity GRN RED YELLOW BLACK StarLink BATTERY RED BLACK Refer to section SUPPLYING POWER 6 7 8 15 14 13 12 11 9 10 2 3 4 5 1 V PGM1 PGM2 PGM3 IN1 IN2 GND IN3 RING TIP 17 16 RTS R PANEL TX B PANEL RX G CTS Y StarLink Radio Terminals PANEL RING PANEL TIP STARLINK RADIO HOUSI...

Page 17: ... report Open Close radio remembers last state of panel for Napco panels when used with local download cable 5 BURG without DACT Use IN2 or IN3 for both Alarm and Trouble Panel has alarm and Trouble Relay PGM outputs Two EOLRs are needed since for UL Burg it is required to detect both wire breaks and shorts ALARM TBL ALARM TBL TBL TBL No Supervised Burg Alarm Trouble Requires two 10K EOLRs Three of...

Page 18: ... wire to a zone on the control panel GEM Tamperkit consists of Description QTY SC206LF Slotted Pan Head 6 32 x 3 4 Machine Screw 6 SW105 Tamper Switch 2 Tamper Switch Mounting Instructions Back Tamper Door Tamper VIEW OF TAMPER SWITCHES 1 ENCLOSURE BASE 2 BACK TAMPER SWITCH TO PREVENT REMOVAL FROM WALL 3 DOOR TAMPER SWITCH TO PROTECT THE ENCLOSURE DOOR 1 3 2 NYCFD Conditions of Acceptability 1 Onl...

Page 19: ...23 TRANSFORMER FOR CONNECTION TO SLE CHARGER BOARD UL LISTED SURFACE OR FLUSH MOUNT OUTLET BOX AND NON SWITCHED RECEPTACLE WALL TRANSFORMER SECONDARY WIRING CONDUIT LIMITED TO 20 FEET MAXIMUM LENGTH Maintain a minimum of 1 4 inch separation of circuits transformer secondary wiring from 120V branch circuit EXAMPLE OF CONDUIT LOCATION Optional Alternate Methods for Commercial Fire Branch Circuit Pow...

Page 20: ...compromised or circumvented or that the product or system will prevent any personal injury or property loss by burglary robbery fire or otherwise nor that the product or system will in all cases provide adequate warning or protection A properly installed and maintained alarm may only reduce risk of burglary robbery fire or otherwise but it is not insurance or a guarantee that these events will not...

Reviews: