NAPCO Security Group
NAPCO Gemini C
-
Series Control Panel Programming Instructions
--
Volume 2
Page 88
Programming Instructions, Volume 2
ZONE OPTIONS / ZONES 73-80 (ADDRESS 2902-2988)
ZONE OPTIONS:
1.
Select the desired zone option by entering the option
number (1
-
8) for each selected zone.
2.
Enter corresponding option number in address location, in
Binary (Bit) Format.
3.
Press
U
to save.
NOTE:
Dark shaded data value box shows option not avail-
able.
ZONE OPTIONS
ADDR
ZONES 73
► 80
Z73
Z74
Z75
Z76
Z77
Z78
Z79
Z80
1
2
3
4
5
6
7
8
Zone Area 1 (Fire)
2944
Zone Area 2
2945
Zone Area 3
2946
Zone Area 4
2947
Zone Area 5
2948
Zone Area 6
2949
Zone Area 7
2950
Zone Area 8
2951
Reserved
2952
Reserved
2953
Zone Anding Group 1
2954
Zone Anding Group 2
2955
Zone Anding Group 3
2956
Zone Anding Group 4
2957
Zone Anding Group 5
2958
Zone Anding Group 6
2959
Zone Anding Group 7
2960
Zone Anding Group 8
2961
Interior 1 Bypass
2962
Interior 2 Bypass
2963
Keypad Sounder on Alarm 2964
Ext Fire Output 1
2965
Ext Fire Output 2
2966
Ext Fire Output 3
2967
Ext Fire Output 4
2968
Ext Fire Output 5
2969
Ext Fire Output 6
2970
Ext Fire Output 7
2971
Ext Fire Output 8
2972
Reserved
2973
Reserved
2974
Carbon Monoxide
2975
Verification (Fire)
2976
Waterflow (Fire)
2977
Supervisory
2978
Monitor Zone
2979
NAC A
2980
NAC B
2981
NAC C
2982
NAC D
2983
Reserved
2984
Reserved
2985
Chime 2
2986
Delayed Trip 1
2987
Delayed Trip 2
2988
ZONE OPTIONS
ADDR
ZONES 73
► 80
Z73
Z74
Z75
Z76
Z77
Z78
Z79
Z80
1
2
3
4
5
6
7
8
Priority Zone
2902
Priority / Bypass
2903
AutoBypass
2904
Selective Bypass
2905
Keyswitch Arming
2906
AutoBypass Re-entry
2907
Pre-Alarm Warning
2908
Never Arm
2909
24-Hour Protection
2910
Burg Bell
2911
Pulse Burg Bell
2912
Burg PGM2
2913
Burg Relay
2914
Burg PGM1
2915
Exit/Entry #1
2916
Exit/Entry #2
2917
Exit/Entry Follower
2918
Auto Reset
2919
Swinger Shutdown
2920
Chime Zone
2921
Abort Delay
2922
Power-Up Delay
2923
Day Zone/Trouble Open 2924
Day Zone/Trouble Short 2925
Alarm on Day Zone/Trouble
2926
Report Alarm Tel1
2927
Rpt Alm Restore Tel1
2928
Report Trouble Tel1
2929
Rpt Tbl Restore Tel1
2930
Reserved
2931
Reserved
2932
Reserved
2933
Reserved
2934
Report Alarm Tel3
2935
Rpt Alm Restore Tel3
2936
Report Trouble Tel3
2937
Rpt Tbl Restore Tel3
2938
No EOL Resistor
2939
Sensor Watch
2940
Trouble on Open
2941
Trouble on Short
2942
Trouble on Night Open 2943
FOOTNOTES AND SYMBOLS FOR TABLES
A
2
-
wire smoke detectors only available for zones 1
-
8 or utilizing
FWC
-
FSLC
-
CZM on SLC loop. See Installation Instructions
(WI1653) for more details.
B
If
Fire Alarm Verification
is selected, then
Fire
must also be
selected.
C
When the Easy Program Menu is used, these features are
enabled by default (for new panels or after a Cold Start
(address 8179)). Zone Area 1 is enabled for the first 8 zones
only, by default.
D
Disable
Auto
-
Reset
on non
-
Fire zones for SIA CP
-
01 installa-
tions.