NAPCO Gemini C
-
Series Control Panel Installation Instructions
--
Volume 3
Installation Instructions, Volume 3
Page 9
DESCRIPTION
The GEMC
-
PS24V7A
-
R is both a charger and a super-
vised power supply rated at 24VDC/7A. Input rating is
120VAC, 60Hz, 3A. Fuse rated 5A, 250V. Replace on-
ly with UL Listed fuse rated 5A, 250V (see WI1653).
FEATURES
•
24VDC output.
•
Maximum charge current 1.96A.
•
7 ampere continuous supply current at 24VDC.
•
Built
-
in charger for sealed lead acid or gel type bat-
teries.
•
Automatic switch over to stand
-
by battery when AC
fails.
•
AC input, DC output.
•
Short circuit and thermal overload protection.
•
Board Dimensions: 9"(L) x 6"(W) x 1⅝"(H)
Specified at 25°C ambient.
INSTALLATION INSTRUCTIONS
H
Caution: Turn off branch circuit before servicing
power supply.
The GEMC
-
PS24V7A
-
R should be installed in accord-
ance with The National Electrical Code, ANSI / NFPA 70
and all applicable Local Regulations.
To install, see the Gemini C
-
Series control panel instal-
lation instructions (WI1653) detailing removal and re
-
installation instructions for all models of the Gemini C
-
Series control panels. Install jumpers on J3 as per the
chart below:
DESCRIPTION
The GEMC
-
PS24V4A
-
R is both a charger and a super-
vised power supply rated at 24VDC/4A. Input rating is
120VAC, 60Hz, 3A. Fuse rated 5A, 250V. Replace on-
ly with UL Listed fuse rated 5A, 250V (see WI1653).
FEATURES
•
24VDC output.
•
Maximum charge current 1.96A.
•
4 ampere continuous supply current at 24VDC.
•
Built
-
in charger for sealed lead acid or gel type bat-
teries.
•
Automatic switch over to stand
-
by battery when AC
fails.
•
AC input, DC output.
•
Short circuit and thermal overload protection.
•
Board Dimensions: 9"(L) x 6"(W) x 1⅝"(H)
Specified at 25° C ambient.
INSTALLATION INSTRUCTIONS
H
Caution: Turn off branch circuit before servicing
power supply.
The GEMC
-
PS24V4A
-
R should be installed in accord-
ance with The National Electrical Code, ANSI / NFPA 70
and all applicable Local Regulations.
To install, see the Gemini C
-
Series control panel instal-
lation instructions (WI1653) detailing removal and re
-
installation instructions for all models of the Gemini C
-
Series control panels. Install jumpers on J3 as per the
chart below:
GEMC
-
PS24V7A 7 AMP POWER SUPPLY
GEMC
-
PS24V4A 4 AMP POWER SUPPLY
BATTERY CHARGE CURRENT JUMPERS
No. of Jumpers
Trickle Charge Total Charge No. of Batteries
0
210 mA
1.50A
2 sets
1
440 mA
1.72A
3 sets
2
680 mA
1.96A
4 sets
BATTERY CHARGE CURRENT JUMPERS
No. of Jumpers
Trickle Charge Total Charge No. of Batteries
0
210 mA
1.50A
2 sets
1
440 mA
1.72A
3 sets
2
680 mA
1.96A
4 sets
Important:
To minimize the possibility of crosstalk, care should be taken when running digital com-
munication circuits (for example, 12V digital keypad bus wiring, Burg SLC and Fire SLC circuit wiring)
in close proximity to each other, such as within multi
-
conductor cables or the same conduit over long
distances. All wiring must comply with the NEC (National Electrical Code) and/or NFPA 70 codes.