![NAPCO GEMINI C Series Installation Instructions Manual Download Page 5](http://html2.mh-extra.com/html/napco/gemini-c-series/gemini-c-series_installation-instructions-manual_3288042005.webp)
NAPCO Gemini C
-
Series Control Panel Installation Instructions
--
Volume 3
Installation Instructions, Volume 3
Page 5
Output Power:
Burg Bell Power:
12VDC Regulated, 2A maximum.
AUX Power:
12VDC Regulated, 750mA maximum.
Burg Bus Power ("Remote Bus Power"):
12V Regulated, 750mA
maximum.
PGM1:
Active low, 10.6
-
12VDC @ 150mA.
PGM2:
Active low, 10.6
-
12VDC @ 150mA (For UL Commercial in-
stallations)
Aux Relay:
Wet 12V Regulated @ 750mA maximum (subtract from
AUX Power); may be set to a dry form "c" relay contact upon removing
the jumper "R"; output rated 30VDC, 3A (Resistive Load)
Total Combined Standby Current
(Auxiliary power + Burg Bus power
+ Aux Relay power +25mA standby current): 750mA.
Total Combined Standby and Alarm Current
(Auxiliary power + Burg
Bus power + Aux Relay power + Bell power): 2.5A.
GEMC
-
F8ZCPIM Conventional 8 Fire Zone Expander Module
ELECTRICAL RATINGS
Input Power:
12V Regulated, 120mA standby + total combined
standby and alarm current.
Output Power:
AUX PWR:
12V Regulated, 700mA maximum.
RST PWR:
12V Regulated, 700mA maximum.
Maximum Total Combined Standby and Alarm Current:
120MA +
total combined standby current. Must reduce GEMC
-
XXXMB total
combined 12V standby power by GEMC
-
F8ZCPIM total combined
standby current.
Zone Ratings:
Voltage:
13.8
-
8.5VDC.
Current:
2mA standby loop current.
Alarm:
42mA maximum alarm current per zone.
Maximum Loop Resistance
: 10 ohms.
Note:
Zones not programmed into Area 1 and not wired with an EOLR
will not pull any current in standby or in alarm. All initiating circuits are
Class B.
GEMC
-
FW
-
SLC Fire Signaling Line Circuit Module
Electrical Ratings
Input Power:
Power Requirements:
24VDC, 70mA (standby current) + device
current.
Maximum Total Combined 24V Input Current:
475mA.
Output Power:
36V, 150mA maximum. The additional alarm current
(5 LED's @ 8mA for 40mA) is automatically added to determine
s alarm current.
Note:
Refer to PCD
-
Windows Quickloader download software's calcu-
lation tools for 24V standby current calculation. GEMC
-
XXXMB total
combined 24V auxiliary standby current must be reduced by GEMC
-
FW
-
SLC input current.
Operating Temperature:
0°C to 49°C
Storage Temperature:
20°C to + 85°C
Dimensions W x D x H:
4.5" x 4" x 1"
GEMC
-
BSLC Burglary Signaling Line Circuit Module
Electrical Ratings
Input Power:
Power Requirements:
24VDC, 55mA (standby current) + device
current (provided by GEMC Series control panel).
Maximum Total Combined 24V Input Current:
590mA.
Output Power:
16.5V, 500mA maximum.
Note:
Refer to PCD
-
Windows Quickloader download software's calcu-
lation tools for 24V standby current calculation. GEMC
-
XXXMB total
combined 24V auxiliary standby current must be reduced by GEMC
-
BSLC current.
Operating Temperature:
32° to 120°F (0° to 49°C)
Dimensions W x D x H:
4.5" x 4" x 1"
Modules Mounted Inside
the C
-
Series Motherboard Enclosure:
GEMC
-
NL
-
MOD Network Communication Module
Electrical Ratings
Input Power:
Nominal 12VDC, 85mA.
Note:
12V power must be supplied from GEMC
-
XXXMB
AUX PWR
terminals. Available panel 12V combined auxiliary current is reduced
by 85mA.
Output Power:
PGM
-
style open collector (negative trigger) with a
maximum sink current of 50mA. Wire only to power
-
limited circuits less
than 14VDC.
Dimensions:
1½" x 7" x 4¾" (H x W x D)
Note:
The GEMC
-
NL
-
MOD Network Communication Module can be
used as the primary communicator; see WI1754 for details.
GEMC
-
RS232 Control Panel / Computer Converter
Electrical Ratings
Input Power
: 12.6
-
10.2, 60mA.
Note:
12V power must be supplied from GEMC
-
XXXMB
AUX PWR
terminals. Available GEMC
-
XXXMB total combined 12V auxiliary cur-
rent must be reduced by 60mA.
Output:
RS232 format, maximum 50 feet.
Note: For supplementary use only.
Dimensions (HxWxD) :
11/16" x 2 9/16" x 2 9/16"
Range:
50 feet using RS232 serial cable; 100 feet using Cat5 cable
Note: For supplementary use only.
GEMC
-
24VR 24 Volt "Regulated" Output Module
Electrical Ratings
Input Power:
24V Unregulated, 2A maximum. Supplied from NAC
output of the GEMC
-
XXXMB or GEMC
-
NACXX programmed for re-
versed polarity.
Output Power:
24V Regulated, 1.0A maximum (maximum is reduced
by battery configuration and required standby time).
Dimensions:
W = 3.5", L = 4.32", H = 1.15"
Modules Wired to Fire Bus
and/or Burglary Bus:
GEMC
-
FK1 FIRE KEYPAD
ELECTRICAL RATINGS
Input Power:
12VDC nominal, 110mA maximum, 35mA if backlighting
is disabled (cut jumpers W1, W2 & W3).
Maximum Number of Fire Keypads:
7
Maximum Number of Fire K Burglary Keypads
: 15
POWER RATINGS
GEMC
-
FK1 is powered by the Fire bus of the GEMC
-
Series mother-
board, GEMC
-
12V2APS or an appropriately rated UL Listed Security/
Signaling power limited power supply. Deduct these values from the
system standby current, as described in the control panel wiring dia-
gram.
GEMC
-
BK1 BURGLARY KEYPAD
ELECTRICAL RATINGS
Input Power:
12.5
-
7.5VDC, 110mA maximum (120mA when using
integral EZM). 35mA if backlighting is disabled (cut jumpers W1, W2 &
W3).
Output Power:
PGM Output (active low):
5mA, 12V. Wiring to power limited circuits
less than 14VDC.
Maximum Number of Burglary Keypads:
15.
Maximum Number of Fire K Burglary Keypads:
15.
Maximum Wiring Length for each run:
(#22AWG): 1000' divided by
total number of keypads on run.
POWER RATINGS
GEMC
-
FK1 and GEMC
-
BK1 are both powered by the keypad bus of
the control panel, GEMC
-
12V2APS or an appropriately rated UL Listed
Security/Signaling power
-
limited power supply. Deduct these values
from the system standby current, as described in the control panel
wiring diagram.