NAPCO GEMINI C Series Installation Instructions Manual Download Page 5

NAPCO Gemini C

-

Series Control Panel Installation Instructions

--

Volume 3

 

Installation Instructions, Volume 3

 

Page 5

 

 

Output Power:

 

 

Burg Bell Power:  

12VDC Regulated, 2A maximum.

 

 

AUX Power:  

12VDC Regulated, 750mA maximum.

 

 

Burg  Bus  Power  ("Remote  Bus  Power"):   

12V Regulated, 750mA 

maximum.

 

 

PGM1:  

Active low, 10.6 

-

 12VDC @ 150mA.

 

 

PGM2:   

Active low, 10.6 

-

 12VDC @ 150mA (For UL Commercial in-

stallations)

 

 

Aux  Relay:

  Wet 12V Regulated @ 750mA maximum (subtract from 

AUX Power); may be set to a dry form "c" relay contact upon removing 
the jumper "R"; output rated 30VDC, 3A (Resistive Load)

 

 

Total Combined Standby Current 

(Auxiliary power + Burg Bus power 

+ Aux Relay power +25mA standby current):  750mA.

 

 

Total Combined Standby and Alarm Current 

(Auxiliary power + Burg 

Bus power + Aux Relay power + Bell power):  2.5A.

 

 

GEMC

-

F8ZCPIM Conventional 8 Fire Zone Expander Module 

 

 

ELECTRICAL RATINGS

 

 

Input  Power:

    12V  Regulated,  120mA  standby  +  total  combined 

standby and alarm current.

 

 

Output Power:

 

 

AUX PWR:

  12V Regulated, 700mA maximum.

 

 

RST PWR: 

 12V Regulated, 700mA maximum.

 

 

Maximum Total Combined Standby and  Alarm Current:

  120MA + 

total  combined  standby  current.    Must  reduce  GEMC

-

XXXMB  total 

combined  12V  standby  power  by  GEMC

-

F8ZCPIM  total  combined 

standby current.

 

 

Zone Ratings:

 

 

Voltage:

  13.8 

-

 8.5VDC.

 

 

Current:

  2mA standby loop current.

 

 

Alarm:

  42mA maximum alarm current per zone.

 

 

Maximum Loop Resistance

:  10 ohms.

 

 

Note:  

Zones not programmed into Area 1 and not wired with an EOLR 

will not pull any current in standby or in alarm.  All initiating circuits are 
Class B.

 

 

GEMC

-

FW

-

SLC Fire Signaling Line Circuit Module

 

 

Electrical Ratings

 

 

Input Power:

 

 

Power  Requirements:

    24VDC,  70mA  (standby  current)  +  device 

current.

 

 

Maximum Total Combined 24V Input Current:

  475mA.

 

 

Output  Power:

  36V, 150mA maximum.  The additional alarm current 

(5  LED's  @  8mA  for  40mA)  is  automatically  added  to  determine 
s alarm current. 

 

 

Note:

  Refer to PCD

-

Windows Quickloader download software's calcu-

lation  tools  for  24V  standby  current  calculation.    GEMC

-

XXXMB  total 

combined  24V  auxiliary  standby  current  must  be  reduced  by  GEMC

-

FW

-

SLC input current.

 

 

Operating Temperature:

  0°C to 49°C

 

 

Storage Temperature: 

 20°C to + 85°C

 

 

Dimensions W x D x H:

  4.5" x 4" x 1"

 

 

GEMC

-

BSLC Burglary Signaling Line Circuit Module

 

 

Electrical Ratings

 

 

Input Power:

 

 

Power  Requirements:

    24VDC,  55mA  (standby  current)  +  device 

current (provided by GEMC Series control panel).

 

 

Maximum Total Combined 24V Input Current:

  590mA.

 

 

Output Power:

  16.5V, 500mA maximum.

 

 

Note:

  Refer to PCD

-

Windows Quickloader download software's calcu-

lation  tools  for  24V  standby  current  calculation.    GEMC

-

XXXMB  total 

combined  24V  auxiliary  standby  current  must  be  reduced  by  GEMC

-

BSLC current.

 

 

Operating Temperature: 

 32° to 120°F (0° to 49°C) 

 

 

Dimensions W x D x H:  

4.5" x 4" x 1"

 

 
 
 
 
 
 
 
 

Modules Mounted Inside 

 

the C

-

Series Motherboard Enclosure:

 

 

GEMC

-

NL

-

MOD Network Communication Module 

 

 

Electrical Ratings

 

 

Input Power:

  Nominal 12VDC, 85mA.

 

 

Note:   

12V power must be supplied from GEMC

-

XXXMB 

AUX  PWR

 

terminals.  Available panel 12V combined auxiliary current is reduced 
by 85mA.

 

 

Output  Power:

    PGM

-

style  open  collector  (negative  trigger)  with  a 

maximum sink current of 50mA.  Wire only to power

-

limited circuits less 

than 14VDC.

 

 

Dimensions:  

1½" x 7" x 4¾" (H x W x D)

 

 

Note:

   The  GEMC

-

NL

-

MOD  Network  Communication  Module can  be 

used as the primary communicator; see WI1754 for details.

 

 

GEMC

-

RS232 Control Panel / Computer Converter

 

 

Electrical Ratings

 

 

Input Power

:  12.6 

-

 10.2, 60mA.

 

 

Note:   

12V power must be supplied from GEMC

-

XXXMB 

AUX  PWR

 

terminals.  Available GEMC

-

XXXMB total combined 12V auxiliary cur-

rent must be reduced by 60mA.  

 

 

Output:

  RS232 format, maximum 50 feet.

 

 

Note:  For supplementary use only.

 

 

Dimensions (HxWxD) :  

11/16" x 2 9/16" x 2 9/16" 

 

 

Range:  

50 feet using RS232 serial cable; 100 feet using Cat5 cable

 

 

Note:  For supplementary use only.

 

 

GEMC

-

24VR 24 Volt "Regulated" Output Module

 

 

Electrical Ratings

 

 

Input  Power:   

24V Unregulated, 2A maximum.  Supplied from NAC 

output  of  the  GEMC

-

XXXMB  or  GEMC

-

NACXX  programmed  for  re-

versed polarity.

 

 

Output Power:  

24V Regulated, 1.0A maximum (maximum is reduced 

by battery configuration and required standby time).

 

 

Dimensions:  

W = 3.5", L = 4.32", H = 1.15" 

 

 
 

Modules Wired to Fire Bus 

 

and/or Burglary Bus:

 

 

GEMC

-

FK1 FIRE KEYPAD

 

 

ELECTRICAL RATINGS

 

 

Input Power: 

12VDC nominal, 110mA maximum, 35mA if backlighting 

is disabled (cut jumpers W1, W2 & W3).

 

 

Maximum Number of Fire Keypads:

  7

 

 

Maximum Number of Fire K Burglary Keypads

:  15

 

 

POWER RATINGS

 

 

GEMC

-

FK1  is  powered  by  the  Fire  bus  of the  GEMC

-

Series mother-

board, GEMC

-

12V2APS or an appropriately rated UL Listed Security/

Signaling  power limited power supply.   Deduct these  values from the 
system  standby  current,  as  described  in  the  control  panel  wiring  dia-
gram.

 

 

GEMC

-

BK1 BURGLARY KEYPAD

 

 

ELECTRICAL RATINGS

 

 

Input  Power:

  12.5 

-

  7.5VDC,  110mA maximum (120mA  when using 

integral EZM).  35mA if backlighting is disabled (cut jumpers W1, W2 & 
W3).

 

 

Output Power:

 

 

PGM Output (active low):  

5mA, 12V.  Wiring to power limited circuits 

less than 14VDC.

 

 

Maximum Number of Burglary Keypads:  

15.

 

 

Maximum Number of Fire K Burglary Keypads:

  15.

 

 

Maximum Wiring Length for each run:  

(#22AWG):  1000' divided by 

total number of keypads on run.

 

 

POWER RATINGS

 

 

GEMC

-

FK1  and GEMC

-

BK1  are  both  powered by  the keypad bus  of 

the control panel, GEMC

-

12V2APS or an appropriately rated UL Listed 

Security/Signaling  power

-

limited  power  supply.    Deduct  these  values 

from  the  system  standby  current,  as  described  in  the  control  panel 
wiring diagram.

 

 

Summary of Contents for GEMINI C Series

Page 1: ...IAL GEMC 255 GEMC 128 GEMC 96 GEMC 32 CONTROL PANEL COMMUNICATOR Installing the GEMINI C Series Control Panels with the GEMC FK1 Keypad and the GEMC BK1 Keypad WIRELESS HARDWIRE GEMC FK1 Keypad GEMC B...

Page 2: ...ws are registered trademarks of the Microsoft Corporation All other trademarks cited in this manual are for reference only and are the property of their respective owners Copyright 2021 by NAPCO Secur...

Page 3: ...rammable Output Module 6 GEMC RECV Wireless RF Receiver 6 GEMC NACXX Supervised NAC Extender 6 GEMC FPRINT Parallel Printer Interface 6 GEMC 12V2APS CF Power Supply 6 GEMC 12V2APS R Power Supply 7 Fir...

Page 4: ...ent 25mA plus GEMC F8ZCPIM total standby and alarm current Maximum Total Combined 24V Standby Total combined 12V standby plus alarm current times 0 6 NAC A D 24V standby cur rent plus GEMC BM total co...

Page 5: ...ent must be reduced by GEMC BSLC current Operating Temperature 32 to 120 F 0 to 49 C Dimensions W x D x H 4 5 x 4 x 1 Modules Mounted Inside the C Series Motherboard Enclosure GEMC NL MOD Network Comm...

Page 6: ...outputs are 24V Regulated Supervision AC fail supervision approximate 1 minute delay to prevent nui sance swingers Battery presence low battery supervision and battery charger volt age supervision com...

Page 7: ...re Set Point 40 F 4 RATINGS Electrical Ratings Input Power 13 6 16 3VDC supplied by GEMC BSLC module 19mA Output Power not applicable Maximum Wiring Length 2000 feet 16 AWG Refer to GEMC BSLC document...

Page 8: ...Glass types minimum size 10 7 8 x 10 7 8 280 mm x 280 mm 3 32 3 8 plate 1 8 3 8 tempered 1 8 9 16 laminated 1 4 wired 5 8 overall sealed insulated Note Coated glass with security films including film...

Page 9: ...put Maximum charge current 1 96A 4 ampere continuous supply current at 24VDC Built in charger for sealed lead acid or gel type bat teries Automatic switch over to stand by battery when AC fails AC inp...

Page 10: ...t Entry Trouble 55 R370 Burg Exit Entry Trouble Restore 56 E137 Burg Zone Tamper Alarm 57 R137 Burg Zone Tamper Restore 58 E370 Burg Zone Tamper Trouble 59 R370 Burg Zone Tamper Trouble Restore 60 E40...

Page 11: ...Disable Restore 187 E342 Fire Monitor AC Fail 188 R342 Fire Monitor AC Fail Restore 189 E342 Fire Monitor AC Fail Trouble 190 R342 Fire Monitor AC Fail Trouble Restore 191 E338 Fire Monitor Bat Test...

Page 12: ...CPIM Conventional 8 Fire Zone Expander Plug in Module see WI1651 GEMC FK1 Fire keypad see WI1649 OI341 GEMC FPRINT Print module for Fire Bus see WI1708 GEMC FW SLC Fire SLC Module see WI1647 GEMC HSKI...

Page 13: ...ystem Kit As above but with 24V Panel 128 Points via commercial addressable wire less or conventional fire devices 4 on board NACs provid ing up to 6 5A notification power GEMC FW 32KT 32 Point GEM C...

Page 14: ...ogy Motion Detector PIR and Microwave Range 40 x40 Fire Peripherals GEMC FK1 LCD Fire Keypad for GEMC Combo System Red GEMC WL SMK Wireless Commercial Fire Device Photoelectric Smoke De tector GEMC WL...

Page 15: ...EMC NAC7S Remote NAC Extender Provides four 4 NAC Outputs for a combined output rating of 6 5A or a maximum of 2A on any one output Includes red enclosure 14 x16 must be connected to 120VAC source sup...

Page 16: ...e system design is possible These Worksheets have been placed into a single Microsoft Excel file available online at the NAPCO website http www napcosecurity com Once at the NAPCO website click the li...

Page 17: ...r lights indicating the Burglary Access Control portion of the sys tem is disabled 3 If the GEMC BM GEMC BM PS or GEMC BSLC module s are used The general idea is to unplug each of these Burglary modul...

Page 18: ...B 7 NAC C 9 NAC D 14V 8V pulsing when active 21 REMOTE BUS YEL 20 REMOTE BUS GRN 10V 2 NAC A 4 NAC B 6 NAC C 8 NAC D Zero 0 Volts 3 NAC A 5 NAC B 7 NAC C 9 NAC D 19 REM PWR 23 AUX PWR 2 or 4 GEMC FW...

Page 19: ...erences the Micro number either Micro 1 or Micro 2 for example ComboMicro1 hex Therefore for the Micro number referenced in the file name click the appro priate Browse button within either the Micro 1...

Page 20: ...ower supervise the power with an end of line relay as shown below Connect the EOL relay to a conventional or SLC zone programmed as a Fire Monitor Zone Zone Programmed as Fire Monitor Zone POWER IN PO...

Page 21: ...NAPCO Gemini C Series Control Panel Installation Instructions Volume 3 Installation Instructions Volume 3 Page 21 NOTES...

Page 22: ...NAPCO Gemini C Series Control Panel Installation Instructions Volume 3 Page 22 Installation Instructions Volume 3 NOTES...

Page 23: ...ons Commission helpful How to Identify and Resolve Radio TV Interference Problems This booklet is available from the U S Government Printing Office Washington DC 20402 Stock No 004 000 00345 4 CAUTION...

Page 24: ...paired by others improperly installed improperly used abused altered damaged subjected to accident nuisance flood fire or acts of God or on which any serial numbers have been altered defaced or remove...

Reviews: