4. Specification
Power supply from 15 to 33V DC and from 12 to 24V AC (preferably DC to minimize ageing)
Consumption on KNX or LON bus: 9mA max (only for interface board)
Consumption on 24V AC or 31V DC: 45 mA (+10 mA during RS485 communication)
RS485 bus interface resident
KNX bus interface module: Optional board (TP1 / E mode)
LON bus interface module: Optional board
EnOcean: Optional radio module
Analog: 2 dry contacts, i
solation 3750 V rms / 1 min, 30VDC / 0.6A max
and 1-10V: Optional board
Ambient temperature range: 0 ° C to +45 ° C
Protection class: III
Protection grade: IP 30
Applicable Standard: EN 60730-1 (electrical controls for household machines and the like)
Case: 135 x 90 x 28 mm
The unit complies with European Directive 73/23/EEC (Low Voltage Directive) and 89/336/EEC (EMC
Directive).
KNX:
The ETS database and the LON Plug-In are available on line on