EXCERPTS FROM ANSI/BHMA A156.19
– 1997
4.0
REQUIREMENTS FOR LOW ENERGY SWINGING POWER
OPERATED DOORS OR LOW ENERGY SWINGING POWER
OPEN DOORS
4.1
Opening Time
4.1.1
Doors shall be field adjusted so that opening time to back check or 80
degrees, which ever occurs first, shall be 3 seconds or longer as required
in Table 1. Back check shall not occur before 60 degrees opening.
4.1.2
Total opening time to fully open shall be 4 seconds or longer.
4.2
Closing Time
4.2.1
Doors shall be field adjusted to close from 90 degrees to 10 degrees in 3
seconds or longer as required in Table 1.
4.2.2
Doors shall be field adjusted to close from 10 degrees to fully closed in
not less than 1.5 seconds.
4.3
The door shall be field adjusted to remain fully open for not less than 5
seconds unless a sensing device is used to hold the door open.
4.4
The force required to prevent a stopped door from opening or closing shall
not exceed a 15 lbf (67 N) applied 1 in (25 mm) from the latch edge of the
door at any point in the opening or closing cycle.
4.5
The kinetic energy of a door in motion shall not exceed 1.25 lbf-ft (1.69
Nm). Table 1 provides speed settings for various widths and weights of
doors for obtaining results complying with this paragraph.
4.6
In the event of power failure to the operator, doors shall open with a
manual force not to exceed a 15 lbf (67 N) or torque of 40 lbf-in (4.5 Nm)
to release a latch, a 30 lbf (133 N) to set the door in motion, and a 15 lbf
(67 N) to fully open the door. The forces shall be applied at 1” (25 mm)
from the latch edge of the door.