608MFX Network Segment Redundancy

Figure 2

608M FX

608M FX

Standby

M as te r

FIBER OPTIC PAIR

FIBER OPTIC PAIR

FIBER OPTIC PAIR

#7

#8

#7

#8

#7

#8

#7

#8

608M FX

Standby

Slave

608M FX

608M FX

FIBER OPTIC PAIR

FIBER OPTIC PAIR

#7

#8

#7

#8

608M FX

608MFX

RING

MANAGER

FIBER OPTIC PAIR

#7

#8

#7

ITP Cable

#1

#1

#1

#1

Cat5E

Cat5E

 

 

Replacing the Standby Master during operation 
 
When  replacing  a  standby  master  during  operation,  the  following 
procedure is necessary to prevent an interruption on the network. 
 
1.

 

Remove the terminal block for power supply to the standby master.  

2.

 

Remove the signal lines and the standby connecting cable from the 
standby master.                                                                                                                

3.

 

Connect the signal lines to the replacement device. 

4.

 

Plug the power terminal block into the replacement device. 

 
When replacing the standby slave, no special steps are necessary.   
 

Summary of Contents for 600 Series

Page 1: ...12 15 05 1 600 Series Industrial Ethernet Switches Hardware Installation Guide...

Page 2: ...12 15 05 2 Industrial Ethernet Switch Installation Guide 604MFX ST 604MFXE ST 15 604MFXE ST 40 604MFXE ST 80 608MFX ST 608MFXE ST 15 608MFXE ST 40 608MFXE ST 80...

Page 3: ...ted to the implied warranties of merchantability or fitness for a particular purpose In no event shall N TRON Corp be liable for any incidental special indirect or consequential damages whatsoever inc...

Page 4: ...ring periods of lightning activity WARNING Do not perform any services on the unit unless qualified to do so WARNING Do not block the air vents WARNING Observe proper DC Voltage polarity when installi...

Page 5: ...ports The 604 608MFX are managed switches that supports SNMP management software as well as configuration by a CLI Command Line Interface Serial Port Telnet and or Web based browsers The 600 Series Sw...

Page 6: ...its contain a class 1 laser Do not stare into the laser beam fiber optic connector when installing or operating the product Never install or work on electrical equipment or cabling during periods of l...

Page 7: ...product and who possess the relevant qualifications for their work e g Training in or authorization for connecting up grounding or labeling circuits and devices or systems in accordance with current...

Page 8: ...a fault detection Voltage Current for F1 F2 is limited to 24V 100mA 3 Plug the Voltage Input Plug back into the side header All LED s will flash ON Momentarily 4 The unit will complete the power up cy...

Page 9: ...wise the TX out port 8 should be connected to the RX in port 7 of the far end station completing the ring The RX in port 8 should be connected to the TX out port 7 on the far end station 608MFX RING M...

Page 10: ...of 40m and inform each other of their operating states One of the 608MFX units is assigned the redundant function using the DIP switch setting Stby on Standby Slave The other 608MFX unit takes over th...

Page 11: ...1 Cat5E Cat5E Replacing the Standby Master during operation When replacing a standby master during operation the following procedure is necessary to prevent an interruption on the network 1 Remove the...

Page 12: ...the 608MFX is in the active mode In other words the Ring master has failed and the standby takes over the data traffic RM Redundancy Manager green LED Status Meaning ON The 604 608MFX is operating in...

Page 13: ...ort Status OFF No Valid Connection to the port Green Valid Connection to the port good link Flashes green once per cycle port switched to standby Flashes green three time per cycle port is disabled by...

Page 14: ...to their defaults as set in the factory This allows you to cancel settings made from the Web based management tools Telnet or the command line configurator serial port or the fault mask If the Displa...

Page 15: ...2 1Q Users must configure their networks so that no VLAN packets are sent IEEE 802 1P QOS The 600 Series does support QOS Users should configure their networks such that no packets with a priority tag...

Page 16: ...work Management Users guide The pin outs are shown below DSR Pin 6 RTS Pin 7 CTS Pin 8 Pin 9 Pin 1 RXD Pin 2 TXD Pin 3 DTR Pin 4 GND Pin 5 Standby Sync Port 608MFX Only A 9 pin female connector is use...

Page 17: ...ollowing table shows the pin out and the connections for both types of cable PC Port 25 Pin 9 Pin 604 608MFX Female Female 9 Pin Female Signal Name Pin Pin Pin Signal Name TXD 2 3 2 RXD RXD 3 2 3 TXD...

Page 18: ...7 Verify that cabling is Category 5 or higher for 100Mbit TX Operation 62 5 125 m 1300nm for 100 Mbit FX Operation 8 Verify TX port 7 is connected to RX port 8 and vice versa 9 Verify that only one 60...

Page 19: ...Humidity 10 to 95 Non Condensing Operating Altitude 0 to 6 500 ft Shock and Vibration Shock 200g 10ms Vibration 1g 10 500Hz Seismic 20g 5 200Hz 15s 3 axis Reliability MTBF 1M Hours measured Network M...

Page 20: ...thernet Switch ST Fiber Connectors 608MFX ST MM 2km 604MFXE ST YY Industrial Ethernet Switch ST Fiber Connectors 608MFXE ST YY Singlemode Where YY 15 40 or 80km 900 RM 19 Rack Mount Kit SDP1 Din Rail...

Page 21: ...appropriately for safe shipment Responsibility for loss or damage does not transfer to N TRON until the returned item is received by N TRON The repaired or replaced item will be shipped to the custome...

Page 22: ...BUSINESS LOSS OF INFORMATION OR DATA OR OTHER FINANCIAL LOSS ARISING OUT OF OR IN CONNECTION WITH THE SALE INSTALLATION MAINTENANCE USE PERFORMANCE FAILURE OR INTERRUPTION OF ITS PRODUCTS EVEN IF N T...

Reviews: