Installation: Ducting
(Cont’d)
Ducting Can be installed as shown on the previous page. Extra outlets can be
installed to fit your own needs however you should ideally not fit more than
the maximum of 4 outlets, to ensure you are receiving sufficient hot air
output.
Exhaust System
Note:
Do not work on the exhaust system unless the heater has been
switched off for over an hour and wear safety gloves if necessary. All types of
combustion produce high temperatures and toxic fumes and must be
installed in accordance to these instructions.
The flexible exhaust pipe can be shortened to no less than 20cm and should
not exceed a length of 2m, depending on the installation parameters. Route
the exhaust pipe from the heater to a suitable outlet, ensuring that is securely
fitted to the heater using the clamp supplied in the kit.
As the exhaust gets very hot during operation, it should be installed in such a
way that will not cause damage to the vehicle. So ensure that it has sufficient
clearance of heat sensitive parts; paying close attention to fuel lines (plastic
and copper) and electrical components. Make sure that the outlet ends in
open air and does not point in the direction of travel. The whole system
should also point downwards and if necessary, a 5mm hole should be drilled
near the bottom to drain off any condensation. You should also route the
exhaust so that the fumes are not taken back in by the air intakes of the
heater and ensure that the outlet does not get blocked by anything like road
debris etc.