11
01: Output voltage setting
Interface
Setting
Parameter 3: Output voltage
For 208/220/230/240 VAC models, you may choose the
following output voltage:
208:
presents output voltage is 208Vac
220:
presents output voltage is 220Vac
230:
presents output voltage is 230Vac
240:
presents output voltage is 240Vac
For 110/150/120/127 VAC models, you may choose the
following output voltage:
110:
presents output voltage is 110Vac
115:
presents output voltage is 115Vac
120:
presents output voltage is 120Vac
127:
presents output voltage is 127Vac
02: Frequency Converter enable/disable
Interface
Setting
Parameter 2 & 3:
Enable or disable converter mode. You
may choose the following two options:
CF ENA:
converter mode enable
CF DIS:
converter mode disable
03: Output frequency setting
Interface
Setting
Parameter 2 & 3: Output frequency setting.
You may set the initial frequency on battery mode:
BAT 50:
presents output frequency is 50Hz
BAT 60:
presents output frequency is 60Hz
If converter mode is enabled, you may choose the following
output frequency:
CF 50:
presents output frequency is 50Hz
CF 60:
presents output frequency is 60Hz
04: ECO enable/disable
Interface
Setting
Parameter 3:
Enable or disable ECO function. You may
choose the following two options:
ENA:
ECO mode enable
DIS:
ECO mode disable
05: ECO voltage range setting
Interface
Setting
Parameter 2 & 3:
Set the acceptable high voltage point
and low voltage point for ECO mode by pressing Down key
or Up key.
HLS:
High loss voltage in ECO mode
in parameter 2.
For 208/220/230/240 VAC models, the setting range in
parameter 3 is from +7V to +24V of the nominal voltage.
For 110/115/120/127 VAC models, the setting range in
parameter 3 is from +3V to +12V of the nominal voltage.