12
LLS:
Low loss voltage in ECO mode in parameter 2.
For 208/220/230/240 VAC models, the setting range in
parameter 3 is from -7V to -24V of the nominal voltage.
For 110/115/120/127 VAC models, the setting voltage in
parameter 3 is from -3V to -12V of the nominal voltage.
06: Bypass enable/disable when UPS is off
Interface
Setting
Parameter 3:
Enable or disable Bypass function. You may
choose the following two options:
ENA:
Bypass enable
DIS:
Bypass disable
07: Bypass voltage range setting
Interface
Setting
Parameter 2 & 3:
Set the acceptable high voltage point
and acceptable low voltage point for Bypass mode by
pressing the Down key or Up key.
HLS:
Bypass high voltage point
For 208/220/230/240 VAC models:
230-264:
setting the high voltage point in parameter 3
from 230Vac to 264Vac.
For 110/115/120/127 VAC models:
120-132:
setting the high voltage point in parameter 3
from 120Vac to 132Vac
LLS:
Bypass low voltage point
For 208/220/230/240 VAC models:
170-220:
setting the low voltage point in parameter 3
from 170Vac to 220Vac
For 110/115/120/127 VAC models:
85-115:
setting the low voltage point in parameter 3 from
85Vac to 115Vac.
08: Programmable outlets enable/disable
Interface
Setting
Parameter 3:
Enable or disable programmable outlets.
ENA:
Programmable outlets enable
DIS:
Programmable outlets disable
09: Programmable outlets setting
Interface
Setting
Parameter 3:
Set up backup time limits for programmable
outlets.
0-999:
setting the backup time limits in minutes from
0-999 for programmable outlets which connect to
non-critical devices on battery mode.
00: Exit setting