Model
Typical Amperage
Battery Capacity Wire Size
Ring Terminal
2
Cable mm
Torque Value
Dimensions
D(mm)
L(mm)
66A
87A
200AH
200AH
1*4AWG
2*8AWG
1*4AWG
2*8AWG
2~ 3 Nm
2~ 3 Nm
22
6.4
33.2
14
6.4
29.2
22
6.4
33.2
14
6.4
29.2
5
3KW
50A
200AH
1*4AWG
2*8AWG
2~ 3 Nm
22
6.4
33.2
14
6.4
29.2
Please follow below steps to implement battery connection:
1. Assemble battery ring terminal based on recommended battery cable and terminal size.
2. Connect all battery packs as units requires. It's suggested to connect at least 200Ah capacity battery for 3KW~
5KW model.
Install the unit by screwing three screws
Battery Connection
CAUTION:
For safety operation and regulation compliance, it's requested to install a separate DC over-current
protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in
some applications, however, it's still requested to have over-current protection installed. Please refer to typical
amperage in below table as required fuse or breaker size.
WARNING!
All wiring must be performed by a qualified personnel.
WARNING!
It's very important for system safety and efficient operation to use
appropriate cable for battery connection. To reduce risk of injury, please use the
proper recommended cable and terminal size as below.
Recommended battery cable and terminal size:
24
Display Setting
The LCD display information will be switched in turns by pressing "UP" or "DOWN" key. The selectable information is
switched as below order: battery voltage, battery current, inverter voltage, inverter current, grid voltage, grid
current, load in Watt, load in VA, grid frequency, inverter frequency, PV voltage, PV charging power, PV charging
output voltage, PV charging current.
Battery voltage/DC discharging current
Inverter output voltage/Inverter output current
Grid voltage/Grid current
Load in Watt
Grid frequency/Inverter frequency
PV voltage and power
PV charger output voltage and PV charging current
Selectable information
LCD display
Low Loss Return Frequency
Low Loss Frequency
Nominal Input Frequency
Max AC Input Voltage
High Loss Return Voltage
High Loss Voltage
42HZ±1HZ(UPS,APL,GEN);
47.5HZ±0.05HZ(VDE)
40HZ±1HZ(UPS,APL,GEN);
47.5HZ±0.05HZ(VDE)
50HZ/60HZ(Auto detection)
300Vac
270Vac±7V(UPS,APL,GEN);
250Vac±7V(VDE)
280Vac±7V(UPS,APL,GEN);
253Vac±7V(VDE)
100Vac±7V(APL,GEN);180Vac±7V(UPS);
196Vac±7V(VDE)
Low Loss Return Voltage
90Vac±7V(APL,GEN);170Vac±7V(UPS);
186Vac±7V(VDE)
Low Loss Voltage
Nominal Input Voltage
230Vac
Sinusoidal (utility or generator)
Input Voltage Waveform
INVERTER MODEL
3KW~5KW
High Loss Return Frequency
High Loss Frequency
63HZ±1HZ(APL,GEN,UPS);
50.05HZ±0.05HZ(VDE)
65HZ±1HZ(UPS,APL,GEN);
51.5HZ±0.05HZ(VDE)
SPECIFICATIONS
Table 1 Line Mode Specifications