4.3.1 Configure Output Function
The Configure Output Function message sets the mode, power-on characteristics and general
behavior for each output. The message must be sent at least one time for LSC and as often
as required if the output configuration needs to change. A handshake message is returned by
the PDM to confirm the setup.
CAN message sent to the PDM to set up the configuration or command the outputs.
Transmission Repetition
On change of state
Data Length
8 bytes
Data Page
0
PDU Format (PF)
239
Proprietary A, PDU1 format
PDU Specific (PS)
30 (1Eh) or as set
DA (Source Address of the PDM)
Priority
5
Parameter Group Number
61184 (EF00h)
Start Position Length
Parameter Name
Reference
1
1 byte
Configuration or Command Identifier
2
1 byte
Output Channel Number
3
1 byte
Soft-Start Step Size
4
1 byte
Motor/Lamp Mode
5.3
6 bits
Reserved (Always high, binary 111111)
5.1
2 bits
Loss of Communication
6
1 byte
Reserved (always FFh)
7.4
5 bits
POR Command
7.3
1 bit
POR Enable
7.2
1 bit
Command Type
7.1
1 bit
Motor Braking
8.5
4 bits
LSC Digital Input
8.3
2 bits
Calibration Time
8.1
2 bits
Response