Section 80
00-02-0829
2018-02-26
-
26 -
4.3.1.6 POR Command
The POR Command sets the percentage PWM level for each output at module power on/reset. This establishes
the output PWM level an individual output will be commanded to at start up. This can be useful in many
applications, but because the PDM is no longer under supervisory control, appropriate testing should be
conducted to ensure safe operation.
Data Length:
5 bits, signed
Resolution:
6.25 % / lsb
-100 % offset
Data Range:
-100 % to 100 %
Operational Range: same as data range
Type:
Status (command)
PGN:
POR Command Value
Commanded PWM %
Actual PWM %
01111
93.75
100
01110
87.5
87.5
01101
81.25
81.25
01100
75
75
01011
68.75
68.75
01010
62.5
62.5
01001
56.25
56.25
01000
50
50
00111
43.75
43.75
00110
37.5
37.5
00101
31.25
31.25
00100
25
25
00011
18.75
18.75
00010
12.5
12.5
00001
6.25
6.25
00000
0
0
11111
-6.25
-6.25
11110
-12.5
-12.5
11101
-18.75
-18.75
11100
-25
-25
11011
-31.25
-31.25