MGC-02030N page 1 of 8
Installation and Operation Manual for
Generator Control System
®
MGC2000
MGC-02030N
Effective 04-03
Section 75
00-02-0505
Description
The compact and powerful MGC2000 generator control system features a
unique, simple-to-install and setup design and enhanced operation.
The control method for the MGC2000 may be specified for using either the
AS3000 Autostart automatic controller or the 518APH electrically tripped
annunciator method.
The system is available in 2 basic configurations:
1. MGC2000
features mechanical gages:
-
MGC2000-A
Automatic Control:
with AS3000 Generator Controller.
-
MGC2000-M
Manual Control:
with 518APH annunciator control.
Both configurations include standard AC voltmeter, AC ammeter, and
frequency meter. Available for single phase, standard three phase, and three
phase re-configutable generators.
2. MGC2000E
features electric gages:
-
MGC2000E-A
Automatic Control:
with AS3000 Generator Controller.
-
MGC2000E-M
Manual Control:
with 518APH annunciator control.
Both configurations include standard AC voltmeter, AC ammeter, and
frequency meter. Available for single phase, standard three phase, and three
phase re-configutable generators.
System Specifications
Pressure gage:
100°psi (680 kPa) [7 bar]
Mechanical gage pressure connection:
1/8" NPT.
Electric gage pressure connection:
2-wire.
Temperature gage:
0-250°F (121°C)
Mechanical gage temperature connection:
12ft. (3.67 m) capillary tubing
and sensing bulb.
Electric gage temperature connection:
2-wire.
Enclosure:
16 Ga CRS powder coated.
Optional NEMA 4X Type Enclosure:
Water and dust tight indoor/outdoor enclosure intended to protect
enclosed equipment against splashing, seepage, falling or hose-directed
water and severe external condensation.
AC Meters:
AC ammeter and an AC voltmeter and a frequency meter are
standard features. Ranges must be specified.
Single or Three phase:
Specify.
Control Method:
may be specified:
- AS3000 Autostart automatic controller or
- 518APH Annunciator control method.
NOTE:
Autostart method is highly recommended.
DC Voltage:
12 or 24 volt DC voltage must be specified.
Power supply:
• Continuous voltage range: 8-35 VDC
• Brown out voltage < 5 VDC for 2 secs (recovery to 8V)
• Blackout voltage: 0V for 50mS (from 10V, recovery to 5V)
• Overvoltage withstand: 50 VDC for 5 seconds (to SAEJ1810 load dump
immunity
• Reverse voltage withstand: 100 VDC continuous
Current consumption (standby):
50mA
Current consumption (max):
500mA (plus output loads)
DC Inputs:
• Pressure, coolant temperature
• Closed to negative DC (±3V) on fault auxiliary and charger faults
• Remote start positive open from positive DC to start
• Remote start negative close to negative DC (±3V) to start DC (±3V) to
activate DC input protection ±50 VDC max.
continued on next page
Please read the following information before installing
.
A visual inspection of this product for damage during shipping is
recommended before mounting. It is your responsibility to have a qualified person install this unit and make sure it conforms to
NEC and local codes.
GENERAL INFORMATION
WARNING
BEFORE BEGINNING INSTALLATION OF THIS MURPHY PRODUCT
✔
Disconnect all electrical power to the machine.
✔
Make sure the machine cannot operate during installation.
✔
Follow all safety warnings of the machine manufacturer.
✔
Read and follow all installation instructions.
WARNING: Do not bundle AC and DC wiring together. It is required
to use separate conduit runs and keep apart by at least 2 inches.