background image

2. Compressor Does Not Run

      a. Check the electrical receptacle for power and correct voltage. The incoming voltage
     must be within 10% of the rated voltage on the serial nameplate.
b. The cold thermostat is accessible by removing the bottom access cover. If the cold
     thermostat capillary bulb loses its charge or becomes kinked it will fail in the open position
     causing a disruption of power to the compressor. Unplug the water cooler and using and
     ohm meter check for continuity across the two electrical terminals on the thermostat. Install
     a new thermostat if there is no continuity.
c. Check for loose wires within the compressor box. The incoming power leads must be
     connected to the overload and relay.
d. If all components check positive for continuity then test the wiring harness plug for
     continuity to see if there is a broken wire within the wiring harness insulation.

3. Compressor Runs – Water Is Warm

a. The most common cause for a water cooler to run without producing cold water is a loss
   of refrigerant. The water cooler must be taken to a certified refrigerant technician for repairs. 
b. Make sure the condenser fan motor is operative. The fan blade must turn freely to help
   remove the heat of compression. 
c. An incorrect refrigerant charge, restriction or defective compressor (not pumping) will also
   cause the compressor to run without producing cold water. All these signs indicate a
   problem within the refrigeration system and the water cooler must be checked by an
   authorized service company.

4. Compressor Cycling On Overload Protector 

a. A dirty condenser or a blocked fan will cause a high head pressure and frequent cycling of
   the overload protector. 
b. Check the incoming voltage to make sure it is within 10% of the serial nameplate rating. 
c. A restriction or moisture in the system will also cause intermittent cycling. A certified
   refrigeration mechanic should be contacted in this situation.
d. Change the overload or relay if defective.

5. Noisy Operation 

a. Check to make sure the fan blade is rotating freely. 
b. Make sure the water cooler is correctly mounted to the wall. Absence of the two lower
   mounting bolts may cause excess noise and vibration. 
c. Check the compressor mounting to make sure the pins and clips are not rattling. If the
   compressor appears to be noisy internally, it must be replaced. 

6. Restricted Or No Water Flow 

a. Ensure water supply service stop valve is fully open. 
b. Verify minimum 20 psig supply line flow pressure. 
c. Check for twists or kinks in bubbler tubing. 
d. Check the water inlet strainer. Sediment from the main supply can get trapped in the
   screen along with installation materials such as pipe dope and flux. The screen should
   be cleaned and checked on a regular basis and replace if needed.
e. The cartridge valve located in the water control assembly or bubbler can also become
   clogged with foreign material. The cartridge valve can only be replaced and not repaired.
f.  The water cooler may also develop a freezing condition in which the water will become
   frozen inside the evaporator coil. This indicates a refrigeration problem or thermostat
   failure in which case the water cooler needs to be checked by a

 qualified technician. 

 

A511.5

Page 5 of 9

RVA 

05/28/21

7020-921-001

MURDOCK  MFG.  • 

15125  Proctor  Avenue  •  City  of  Industry,  CA  91746  USA 

Phone  800-453-7465  or  626-333-2543  •  Fax  626-855-4860  •  www.murdockmfg.com

Member of

CONTEMPORARY WATER COOLERS

 

I N S TA L L AT I O N / M A I N T E N A N C E  I N S T R U C T I O N S

 WATER COOLERS

 

Summary of Contents for A511.5 Series

Page 1: ... into the water cooler or drinking fountain or Murdock s limited warranty is void LIMITED WARRANTY UNITED STATES CANADA LIMITED EXPORT WARRANTY One year on parts only Murdock warrants that every cooler bottle filling station packaged water chiller fountain and accessory to be free from defects in material and workmanship under normal use for one 1 year from date of install or eighteen 18 months af...

Page 2: ...rnished with this water cooler to meet this requirement ROUGHING IN AND DIMENSIONAL DRAWING Prior to roughing consult with local state and federal codes for proper mounting height A511 5 Page 2 of 9 RVA 05 28 21 7020 921 001 MURDOCK MFG 15125 Proctor Avenue City of Industry CA 91746 USA Phone 800 453 7465 or 626 333 2543 Fax 626 855 4860 www murdockmfg com Member of GENERAL NOTES 1 ALL DIMENSIONS ...

Page 3: ...ns with water flowing through system 5 With power still NOT connected carefully manually rotate cooling fan to insure proper clearance and free fan action 3 If water flow requires adjustment insert a slotted narrow blade screwdriver through the hole centered on the pushbutton to the flow regulator Turning clockwise will increase flow and turning counterclockwise will decrease flow 4 After thorough...

Page 4: ...hould any of these problems arise from the water supply 5 Do NOT solder copper tube when inserted into the coupler as damage to the o ring will result IMPORTANT 8 This unit must be grounded per the requirements of applicable electrical codes 9 Warranty is voided if installation is not made following current Acorn Engineering installation instructions and if components are assembled to the fixture ...

Page 5: ...f the overload protector b Check the incoming voltage to make sure it is within 10 of the serial nameplate rating c A restriction or moisture in the system will also cause intermittent cycling A certified refrigeration mechanic should be contacted in this situation d Change the overload or relay if defective 5 Noisy Operation a Check to make sure the fan blade is rotating freely b Make sure the wa...

Page 6: ...nless steel They can scratch easily and should only be cleaned using a clean soft cloth and mild soap with water or a mild glass cleaner CARTRIDGE VALVE PARTS BREAKDOWN STANDARD CARTRIDGE VALVE PARTS BREAKDOWN ITEM PART NUMBER DESCRIPTION 1 7000 050 001 Valve Cartridge Assembly 2 7000 060 000 Valve Cartridge 3 7000 053 199 Jam Nut ITEM PART NUMBER DESCRIPTION 1 2 3 7000 000 001 7000 060 001 0401 0...

Page 7: ...the PE tubing to remove from the push in fitting TO CUT TUBE Cut to fit length of 1 4 PE tubing and remove any burrs or sharp edges Ensure that the outside diameter is free from score marks Tube ends should be square 1 Firmly and fully insert the tubing end into the push in fitting up to the tube stop located approximately deep INSERTING THE TUBE COLLET COLLET O RING O RING TUBE STOP COLLET COLLET...

Page 8: ...octor Avenue City of Industry CA 91746 USA Phone 800 453 7465 or 626 333 2543 Fax 626 855 4860 www murdockmfg com Member of 4 5 6 12 13 14 17 18 19 9 20 22 9 15 7 2 11 10 16 8 3 21 23 1 24 25 15 26 24 25 18 NOTE Flow Restrictor Only Available With Low Flow Bubbler CONTEMPORARY WATER COOLERS I N S TA L L AT I O N M A I N T E N A N C E I N S T R U C T I O N S WATER COOLERS ...

Page 9: ... 000 START CAPACITOR 220V 7012 014 001 COMPRESSOR 7012 030 001 COMPRESSOR 220V 6 7003 350 000 FAN BLADE 7003 302 000 FAN MOTOR 7012 062 001 FAN MOTOR 220V 8 7000 021 001 Y STRAINER 7004 009 020 SIDE PANEL GRAY 7004 081 199 SIDE PANEL STAINLESS STEEL 10 7004 024 199 BACK PLATE 11 0124 056 000 8 x 3 8 LONG PHILLIP PH SHEET METAL SCREW 12 7000 039 001 DRAIN TUBE ASSEMBLY 13 7000 005 199 DRAIN ADAPTER...

Reviews: