Gutter sections
Available lengths: 0.6 m – 1.2 m – 1.8 m – 2.4 m – 3.0 m
It is recommended to use as many as possible 3.0 m sections, than complete the required length with a shorter
cut on size section.
Please note that total length must be a multiple of 0.6 m.
Examples:
1.
total length 12 m:
use q.ty 4 sections with 3.0 m length;
2.
total length 16.8 m: use q.ty 5 sections with 3.0 m length and q.ty 1 section with 1.8 m length.
Water supply and drain
Using 0.75 hp pump on 100 mm thick evaporative pad it is suggested to place a water supply every 24 m and
a water drain every 12 m.
Using 0.75 hp pump on 150 mm thick evaporative pad it is suggested to place a water supply every 16 m and
a water drain every 12 m.
If several water connections are required, divide distance between them uniformly.
q.ty 2 water connections
L/4 L/2 L/4
q.ty 3 water connections
L/6 L/3 L/3 L/6
q.ty 4 water connections
L/8 L/4 L/4 L/4 L/8
Diagram 1