     Refers the timing off setting operation of group 1 to set

that of group 2.

  3.Cancel all timing on/off settings
     Long press “          ” for 3s to enter function interface. 
     “         ” clock icon will flicker and press “          ” to 
     choose the timing function. “          ” and “          ” flicker 
     simultaneously means choosing to cancel all timing 
     functions. 
     Press “         ” to cancel timing settings. “          ” and 
     “          ” both will be extinguished. 

III.Functions of combination key

  1.Force cooling 
  

Press “        ” and “          ” simultaneously for 3s in the 

     main interface to enter into force cooling mode. The 
     force cooling mode icon will be constantly light.
     Press “       ” button and “          ” button simultaneously 
     for 3s to quit force cooling mode. The unit will enter 
     power off mode automatically when quitting force 
     cooling mode. 

  

ś

Quit parameter query function 

If there’s no operation in 20s when enter the 

     parameter query, it will quit automatically and return 
     to the main interface. 
     Press “       ” and “       ” simultaneously to quit 
     parameter query manually.

2.Parameter 

query

 function

 

Ś

To enter parameter 

query

 function

     Press “       ” and “       ” simultaneously for 3s to enter 
     into the interface of parameter 

query

 function. At this 

     moment, first 2 digits of the nixie tube                will 
     display sequence number and the last 2 digits is 
     specific  parameters.
     Press “       ” or “       ” to query the relative parameters. 
     See 

query

 orders in Table 1-1.

Table.1-1 Query

 orders

  3.Auto-lock (unlock) function
     If don’t operate the controller in 60s, the keyboard will lock automatically. Press “           ”and “          ” simultaneously 
     for 3s to unlock.

Frequency

Mode

Display operating frequency when the unit is in cooling mode and heating mode.

0-Power off

ˈ

1-water pump

ˈ

2-cooling

ˈ

3-heating

ˈ

4-force cooling

ˈ

5-force heating

No.

1

2

3

Content

Remark

Wind speed level

0-Power off (1-7)

4

Total capacity requirements

Capacity before revised (Force cooling displays 5)

6

Temp. set

Cooling/heating temp. set

7

T3

Condenser temperature sensor

8

T4

Outdoor ambient temperature sensor

9

Tp

Comp. Discharge temperature sensor

10

Tin

Inlet water temperature sensor of plate heat exchanger

11

Tout

Outlet water temperature sensor of plate heat exchanger

12

Tb1

Plate heat exchanger anti-freezing temperature sensor 1

13

Tb2

Plate heat exchanger anti-freezing temperature sensor 2

14

T6

Radiator surface temperature(reserved)

15

Unit operation current

Unit operation current

16

Power supply voltage AD value

Power supply voltage AD value

17

Opening of EXV

Model

Version number

Step number *8

18

Err1

19

Err2

20

Err3

21

22

5

Capacity requirements after revised

Capacity after revised (Force cooling displays 5)

 

(PCB has no such function)

(PCB has no such function)

(Operation panel has no such function)

(Operation panel has no such function)

4.Factory Reset: 

In main interface, long press “ENTER” for 3s, the unit will close and recovers to factory default mode.
Display panel will display“OFF”

Summary of Contents for MUENR-10-H6

Page 1: ...MINI CHILLER INVERTER H6 English CL25622 to CL25628 MUENR H6 MUENR H6T 10 12 14 16 kW www mundoclima com Installation Owner s manual and information requirements...

Page 2: ...15 17 Checking and starting up the unit 18 Activating and deactivating the unit 18 Shutting down for long periods 23 Routine maintenance 23 Extraordinary maintenance 23 U I A U I A I A I I I A I A I A...

Page 3: ...ed on the respective units All units must be earthed in conformity with legislation in force in the country concerned Hydraulic connections should be carried out as indicated in the instructions to gu...

Page 4: ...stainless steel plate type evaporator complete withelectric heater and water flow switch Casing lined with anti condensate closed cell neoprene cladding PUMPS The units feature a pump with the moving...

Page 5: ...of the unit To lift the unit insert tubes long enough to allow positioning of the lifting slings and safety pins in the feet on the unit To avoid the slings damaging the unit place protection between...

Page 6: ...nits z Fasten the feet of this unit with bolts firmly to prevent it from collapsing in case of earthquake or strong wind 6 0 c m Fix with bolt Single unit installation 300 600 300 2000 Wall or obstacl...

Page 7: ...and calibrating in outlet 4 A flow switch inlet or a differential pressure switch inlet outlet 5 Two thermometers inlet and outlet 6 An inlet filter as close as possible to the evaporator and 7 An en...

Page 8: ...ing the pump connection pipe see page 3 Connect to terminal PL PN on the electrical panel SIZE AND POSITION OF CONNECTIONS The installation must be filled to a pressure of between 1 and 2 bars It is r...

Page 9: ...water equipment before flowing into chilled water system If sand and clay settle in the evaporator circulation of chilled water may be blocked and thus leading to freezing accidents dness of chilled w...

Page 10: ...t short circuits and leakage to earth isolating the installation from other equipment Voltage must be within a tolerance of 10 of the rated power supply voltage for the unit for three phase units the...

Page 11: ...dual Current Circuit breaker GND Residual Current Circuit breaker GND 1 1 A B C N NOTE The outdoor units must be installed with an Residual Current Circuit breaker near the power supply and must be ef...

Page 12: ...o cooling mode forcibly c Remotecooling heating SWITCH 2 7 8 e Wire controller optional CL92340 9 10 11 P P Q E The wired controller KJR 120F1 BMK E is optional Please use 3 core shielded wire to conn...

Page 13: ...BLACK RED BLUE XT1 POWER SUPPLY Y G RED BLACK Wire controller Y G 1 2 3 4 3 1 2 6 4 5 9 7 8 GREEN GREEN BROWN BROWN To XT1 WHITE GREEN GREEN BROWN BROWN 3 4 5 6 V U W 1 2 3 4 5 6 7 8 9 10 11 12V ON OF...

Page 14: ...r supply voltage AD value EXV opening Error 1 Meanings dF Defrosting d8 Remote control Frequency Error 2 Error 3 Temp Sensor code Tin Tout Tb1 T3 T4 B 4100K R 10k 25 5 0 25 Tp B 3950K R 5k 25 5 0 90 P...

Page 15: ...door temperature 15 Heating operation If air conditioner is used beyond the above conditions safely protection features may come into operation Note When the outdoor temperature is too low the unit in...

Page 16: ...er tank L Minimum water volume L Actual water volume L HYDRAULIC DATA I A USEFUL PUMP HEAD CURVES 10 to 16 kW To obtain the useful head of the installation subtract the pressure drop of the plate heat...

Page 17: ...0 60 0 70 0 80 0 External Sta c Pressure KPa Flow m3 h PUMP LED DIAGNOSIS AND SOLUTIONS The pump has an LED operating status display This makes it easy for the technician to search for the cause of a...

Page 18: ...the required minimum is displayed on the user interface check the wiring between the user interface and unit A I FAILURE DIAGNOSIS AT THE MOMENT OF FIRST INSTALLATION 1 Connect the water supply to the...

Page 19: ...cuit valves are open Electrical connections have been carried out correctly Voltage is within a tolerance of 10 of the rated voltage for the unit The unit is correctly earthed All electrical and hydra...

Page 20: ...will be constantly light when customers choose heating mode Water pump mode icon This icon will be constantly light when customers choose water pump mode Force cooling icon This icon will be constantl...

Page 21: ...er during setting clock timing icon will flicker at the moment Press to confirm the power on mode The unit will run as the chosen mode when the mode icon will be constantly light NO Icon Description U...

Page 22: ...1 Query orders 3 Auto lock unlock function If don t operate the controller in 60s the keyboard will lock automatically Press and simultaneously for 3s to unlock Frequency Mode Display operating freque...

Page 23: ...rotection Evaporator high temperature protection in heating mode Wired controller error code list KJR 120F1 BMK E CL92340 E 3 EEPROM error code Wire controller Two times of E6 protection in 10 minutes...

Page 24: ...nd subcooling Efficiency of compressor heater Cleaning of finned coil Cleaning of fan grills Cleaning of condensate drain pan if installed for Heat pump appliances the checks are to be performed quart...

Page 25: ...essure switch or flow switch is opened the unit will For correct operation of the unit with different ambient temperatures the microprocessor controls the fan speed based on the ambient temperature an...

Page 26: ...tage Check safety systems upstream tof he appliance Check power line Switch ON Contactor coil faulty Electronic board faulty Start up capacitor faulty if present Compressor faulty Replace the componen...

Page 27: ...ent gas content Check Moisture in the refrigerant circuit liquid indicator moisture yellow Faulty fan control Faulty fan control Check High suction pressure greater than 10 bars High outside air tempe...

Page 28: ...0 3140 3 50 25 0 R410A 7 2250 9 9 3 11 2500 11 0 3 20 3000 15 6 R410A 2500 5 1550 3 23 6 2 2 1 7 0 1900 3 26 14 6 R410A 2500 V Ph Hz kW W A W W kW W A W W W A g mm mm kg C C Capacity rated Input rate...

Page 29: ...tection system is installed at least every 24 months 2 For equipment that contains fluorinated greenhouse gases in quantities of 50 tonnes of CO2 equivalent or more but of less than 500 tonnes of CO2...

Page 30: ...t chillers 0 1 3 4 567 8 9 9 8 4 8 4 3 9 8 3 3 4 4 A B 0 D 5 7 E9 D 5667 4 F8 F 4 89 G 5 7 8 567 8 4 4 4 4 5667 0 1 1 D 4 4 J K 9 4 3 3 4 4 D 4 4 L 5 7 L E 3 3M0 9 4 D 4 B 4 D 4 INFORMATION REQUIREMEN...

Page 31: ...0 1 3 4 567 8 9 9 8 4 8 4 3 9 8 3 3 4 4 A B 0 D 5 7 E9 D 5667 4 F8 F 4 89 G 5 7 8 567 8 4 4 4 4 5667 0 1 1 D 4 4 J K 9 4 3 3 4 4 D 4 4 L 5 7 L E 3 3M0 9 4 D 4 B 4 D 4 BA B19 891B B 0 EB 9A B 8 A9EB 5...

Page 32: ...0 1 3 4 567 8 9 9 8 4 8 4 3 9 8 3 3 4 4 A B 0 D 5 7 E9 D 5667 4 F8 F 4 89 G 5 7 8 567 8 4 4 4 4 5667 0 1 1 D 4 4 J K 9 4 3 3 4 4 D 4 4 L 5 7 L E 3 3M0 9 4 D 4 B 4 D 4 BA B19 891B B 0 EB 9A B 8 A9EB 5...

Page 33: ...0 0 1 3 4 567 8 9 9 8 4 8 4 3 9 8 3 3 4 4 A B D 5 7 E9 D 5667 4 F8 F 4 89 G 5 7 8 567 8 4 4 4 4 5667 0 1 1 D 4 4 J K 9 4 3 3 4 4 D 4 4 L 5 7 L E 3 3M0 9 4 D 4 B 4 D 4 BA B19 891B B 0 EB 9A B 8 A9EB 5...

Page 34: ...0 1 3 4 567 8 9 9 8 4 8 4 3 9 8 3 3 4 0 4 A B D 5 7 E9 D 5667 4 F8 F 4 89 G 5 7 8 567 8 4 4 4 4 5667 0 1 1 D 4 4 J K 9 4 3 3 4 4 D 4 4 L 5 7 L E 3 03M0 9 4 D 4 B 4 D 4 BA B19 891B B 0 EB 9A B 8 A9EB...

Page 35: ...9 5 D 3 O87 3 P8 8 4 4 D DD 8 89 D DD N 1 5667 8 4 N M 9A D DD P8 9 9 4 5667 D DD 4 3 9 8 4 8 0 8 D A B D 5B7 3 3 M Q 4 A B 0 5B7 3 3 M Q D 4 B QM 0 4 3 3 M Q D 4 1 4 4 D 1 Q D 4 1 Q D 4 B B 8 D 4 B...

Page 36: ...7 8 4 N M 9A D DD P8 9 9 4 5667 D DD 4 3 9 8 4 8 0 8 D A B D 5B7 3 3 M Q 4 A B 0 5B7 3 3 M Q D 4 B QM 4 3 3 M Q D 4 1 4 4 D 1 Q D 4 1 Q D 4 B B 8 D 4 B B 8 D FR 8 N 567 4 4 4 4 4 4 G 4 4 4 4 4 4 G 4 4...

Page 37: ...8 4 N M 9A D DD P8 9 9 4 5667 D DD 4 3 9 8 4 8 0 8 D A B D 5B7 3 3 M Q 4 A B 0 5B7 3 3 M Q D 4 B QM 4 3 3 M Q D 4 1 4 4 D 1 Q D 4 1 Q D 4 B B 8 D 4 B B 8 D FR 8 N 567 4 4 4 4 4 4 G 4 4 4 4 4 4 G 4 4...

Page 38: ...8 4 N M 9A D DD P8 9 9 4 5667 D DD 4 3 9 8 4 8 0 8 D A B D 5B7 3 3 M Q 4 A B 5B7 3 3 M Q D 4 B QM 0 4 3 3 M Q D 4 1 4 4 D 1 Q D 4 1 Q D 4 B B 8 D 4 B B 8 D FR 8 N 567 4 4 4 4 4 4 G 4 4 4 4 4 4 G 4 4...

Page 39: ...8 4 N M 9A D DD P8 9 9 4 5667 D DD 4 3 9 8 4 8 0 8 D A B D 5B7 3 3 M Q 0 4 A B 5B7 3 3 M Q D 4 B QM 4 3 3 M Q D 4 1 4 4 D 1 Q D 4 1 Q D 4 B B 8 D 4 B B 8 D FR 8 N BA B19 891B B 0 567 4 4 4 4 4 4 G 4...

Page 40: ...www mundoclima com C N POLES 249 P1 08013 BARCELONA SPAIN 34 93 446 27 80 SAT 34 93 652 53 57...

Reviews: