Installation manual
20
High pressure duct
SW7 Definition
SW6
ON
1 2 3
SW6
ON
1 2 3
1 means old display panel
1 means auto air blow under
auto mode
non-auto mode
reserved
SW6 Definition
0 means new display panel
0 means auto air blow under
standard
configuration
last unit of
the network
reserve d
J1, J2
Difinition
without jumper fo r
auto restart function
"J1"
with jumper for
non-auto restart function
"J1"
J1
J1
J2
0/1 Difinition
means 0
means 1
●
●
To prevent collapsing of deforming, please bend the pipe at its
biggest radius.
Use bender to get a small radius pipes.
Use the market brass pipe.
Be sure to use the same insulating materials when you buy the
brass pipe. (More than 9mm thick)
For 200 unit, a mainboard in the electric control should
set the code ENC1 to B; the other one should set the code
ENC1 to 8;
For 250 unit, a mainboard in the electric control should
set the code ENC1 to C; the other one should set the code
ENC1 to 9;
For 280 unit, a mainboard in the electric control should
set the code ENC1 to D; the other one should set the code
ENC1 to 9;
13
.
TROUBLE SHOOTING
Table.13-1
NO.
Error code
Indication
Timer LED and run LED
flash together,or show
"FE"
Communication error between
indoor and outdoor unit
DC FAN error
1
2
3
4
5
7
6
No address when first time
power on
Defrost LED flash
or show "E0"
Timer LED flash
or show "E1"
Run LED flash
or show "E2"
Run LED flash
or show "E3"
Run LED flash
or show "E4"
Timer LED flash slowly
or show "E6"
Defrost LED flash slowly
or show "E7"
Alarm LED flash slowly
or show "Ed"
Alarm LED flash
or show "EE"
Mode conflict
Temp.sensor (T1) error
Temp.sensor (T2) error
Temp.sensor (T2B) error
8
9
10
EEPROM error
Outdoor unit error
SW6
ON
1 2 3
SW7
ON
1 2
SW7
ON
1 2
ON
ON
Water level alarm
For both
When using central controller to control the indoor unit,
please pay attention to the address setting, as the 220,
250 and 280 units have two or more mainboards. We suggest
setting the neighbor address for the mainboards in the same
indoor unit. When using a central controller for controlling,
mainboards in the same unit must be opened and closed
at the same time, for avoiding the unexpected incident.
CAUTION
●
Please adjust the code ENC1 to the suitable position (both
system A and B should be adjusted for 200, 250 and 280
indoor unit).
Then expose the pipe (cover it with tapes after bending).
SW 2 Definition
00 means shutting down the unit
to “stop cold air” at 15
℃
00 means the time of stopping
TERMAL fan is 4 mintue
01 means shutting down the unit
to “stop cold air” at 20
℃
10 means shutting down the unit
to “stop cold air” at 24
℃
11 means shutting down the unit
to “stop cold air” at 26
℃
01 means the time of stopping
TERMAL fan is 8 mintue
10 means the time of stopping
TERMAL fan is 12 mintue
11 means the time of stopping
TERMAL fan is 16 mintue
SW2
ON
1234
SW2
ON
1234
SW2
ON
1234
SW2
ON
1234
SW2
ON
1234
SW2
ON
1234
SW2
ON
1234
SW2
ON
1234