Refrigerated Cabinet Operation
Default temperature setpoint = 36° F with a ±2° F
Differential
NORMAL OPERATION
The microprocessor control board controls the cabinet
temperature based on the input received from the
cabinet temperature thermistor. The thermistor value
is compared to the control board setpoint. When the
reach-in temperature is equal or greater than the
setpoint (plus half the differential) the compressor
relay closes provided the following conditions are
satisfied:
•
Power has been uninterrupted to the control board
for a 3 minute period.
OR
•
The 3 minute compressor time delay has expired.
The delay period starts after the compressor has
run and then cycles off.
The compressor relay opens when the reach-in
temperature is less than the setpoint (minus half the
differential).
EVAPORATOR AND CONDENSER FAN MOTOR
OPERATION
The condenser fan motor and compressor share the
same relay. The evaporator fan motor relay is
energized continuously and the evaporator fan cycles
off only during cleaning cycle.
Summary of Contents for MB-8-1
Page 22: ...22 Part Number STH034 3 12 This Page Intentionally Left Blank...
Page 24: ...24 Part Number STH034 3 12 Dimensions A 26 00 66 cm B 32 82 83 cm A B Elevation View...
Page 26: ...26 Part Number STH034 3 12 G 32 82 83 cm J 39 09 99 cm I 36 15 92 cm G I J Side View...
Page 96: ...96 Part Number STH034 3 12 This Page Intentionally Left Blank...
Page 158: ...158 Part Number STH034 3 12 This Page Intentionally Left Blank...
Page 164: ...164 Part Number STH034 3 12 This Page Intentionally Left Blank...
Page 169: ...Part Number STH034 3 12 169 VERSION 1 ICE MACHINE R404A REFRIGERANT ICE MACHINE WIRING DIAGRAM...
Page 170: ...170 Part Number STH034 3 12 VERSION 1 ICE MACHINE R404A REFRIGERANT ICE MACHINE LOGIC DIAGRAM...
Page 175: ...Part Number STH034 3 12 175 VERSION 2 ICE MACHINE R290 REFRIGERANT ICE MAKER WIRING DIAGRAM...
Page 177: ......