START-UP
EN - English
Page 8
PRESSURIZING
1.
Put the bypass system in 'bypass' position.
2.
Make sure the electronic controller of the multi-purpose
water filter is in service mode.
3.
Open the mains water supply.
4.
Open a cold treated water faucet nearby the multi-
purpose water filter and let the water run for a few
minutes until all air is purged and all foreign material that
may have resulted from the installation is washed out;
close the tap.
5.
Gently pressurize the multi-purpose water filter, by
putting it into service:
factory bypass:
1.
open the 'outlet' valve;
2.
slowly open the 'inlet' valve.
3-valve bypass:
1.
close the 'bypass' valve;
2.
open the 'outlet' valve;
3.
slowly open the 'inlet' valve.
6.
After 2-3 minutes, open a cold treated water faucet
nearby the multi-purpose water filter and let the water
run for a few minutes until all air is purged from the
installation and the filter media is rinsed (it is normal for
the rinse water to show some discoloration!); close the
tap.
7.
Check the multi-purpose water filter and all hydraulic
connections for leaks.
After the first regenerations of the multi-purpose water
filter, some slight discoloration of the treated water might
occur. This is totally harmless and will disappear rapidly!
ELECTRONIC CONTROL PANEL
8.
Program the electronic controller.
PERFORM REGENERATION
9.
Manually initiate a regeneration, by pressing the scroll
button; the display will show:
10.
Leave the appliance in this position; the count-down
timer will count down to 0 sec and start a regeneration.
Regen in 10 sec