Safety Automatic Transfer Switch Shutdown
Section 6: Safety Automatic Transfer Switch Shutdown
If SATS shutdown becomes necessary at any time, observe the following procedure:
1. Operate the upstream AC utility input circuit breaker servicing the enclosure to the OFF position.
2. Operate the UPS’ DC and AC breakers to the OFF position and disconnect the battery harness.
3. Operate the UPS Input circuit breaker on the SATS to the OFF position.
4. If a generator is in use, disconnect the generator from the outside cabinet generator connector.
Replacement Parts
Section 7: Replacement Parts
If parts become damaged or lost during operation, replacement parts are available from Multilink.
535-037-10:
7-position terminal block plug.
540-020-10:
2-position jumper .025sq post for JMP-P, JMP-G, and JMP-M.
870-242-20:
Power harness for EDP series UPS.
870-252-20:
Power harness for Universal/Line Interactive UPS.
Fuses:
F1: 1/2 Amp, Fast-Blow, Cartridge Style, 5mm x 20mm.
F2, F3, F4: 2 Amp, Fast-Blow, Cartridge Style, 5mm x 20mm.
F5, F6, F7: 1 Amp, Slow-Blow, Cartridge Style, 5mm x 20mm.
F8: 6 Amp, Fast-Blow Cartridge Style, 5mm x 20mm.