7

200 SERIES WARM CLIMATE DISASSEMBLY AND REASSEMBLY INSTRUCTIONS 

4. 

Run manual flush for 2 minutes.

 

NOTE: Plunger inside solenoid 
should be down when running and 
up when off.  

5. 

If everything checks out, reinstall 

solenoid in valve.

6. 

Avoid cross threading. Any 

resistance means solenoid is 
not going in correctly and cross 
threading may occur. Do not 
overtighten. Tighten until snug.
If everything checks out, the 
electrical system is in working order. 

Disassembly and Check 

For units manufactured from August 
2004 to present, use the following 
directions. If you have an older 
model with a different valve and  
lost the manual, please call us at  
(800) 423-1323 option #9 to get 
the manual for that model.

1.

  Remove six (6) bolts from top 

cover.

2. 

Slowly pull cover off the valve.

3. 

Remove rubber diaphragm and 

inspect for holes or worn areas.

4.

 Inspect valve screen plug to be 

certain it is not damaged and clear 
of debris.

5.

 Remove valve screen plug and 

inspect valve screen for debris. 
Clean with water if necessary.

6. 

Replace the top cover back onto 

the diaphragm - make sure to line 
up the openings In both.

7. 

Match up the top cover of the 

valve with the bottom portion. 
The arrows have to align on both 
portions.

8. 

Replace the bolts and tighten 

down.

Although the Hydro-Guard® 200 
Series Warm Climate Direct 
Discharge with Air Gap was 
delivered completely assembled, it 
may be necessary and/or desirable 
to disassemble portions of the 
Unit, or the Unit in its entirety, In 
order to allow for required service 
and maintenance. If disassembly 
is necessary, please follow the 
directions below. Always close the 
curb stop before working on the unit. 

200 Series Warm Climate Removal 
of Internal Compo nents (FOR AIR 
GAP MODEL) 
1. 

Shut off water supply and secure 

isolation valve.

2.

 Remove the housing cover by 

tilting the housing upward while 
lifting slightly on its end. Once 
the retaining pin, located in the 
opposite end of the housing, is 
clear of the cover, lift upward to 
remove the cover. 

3. 

Use the sample port connection 

to bleed residual pressure within 
the line.

 

4.

 If you have dechlorination, 

remove from piping by loosening  
the nut and disconnect, 'Skip to #5, 
if no dechlorination.

5.

 Loosen the union and remove 

piping and control valve.

Electrical System Check 
1. 

Unscrew Solenoid from control 

valve.

2.

 Make sure controller is attached 

to solenoid via connectors (remove 
adaptor if present).

3. 

Position thumb or other object in  

front of plunger, leaving a slight gap  
(

"), to prevent plunger and spring 

from ejecting away from work space.

Reassembly (FOR AIR GAP 
MODEL)
1. 

Before reinstalling the working 

components, check all union 
surfaces for wear or damage. 
Reinstall the working components 
and tighten the union.

2. 

If you have dechlorination, 

re attach to piping by tightening  
the nut.  
*Skip to 3 if no dechlorination.

3. 

Turn the water supply to the unit 

back on and check for leaks.

4. 

Run a 2-minute manual flush. 

Replace the batteries in the 
controller if needed. Now program 
the flushing schedule.

Disassembly/Reassembly of Unit 

TOOLS NEEDED: HG-A2023 Security Tool, Philips screwdriver, flat-head screwdriver

200 SERIES WARM CLIMATE HIGH-PROFILE DIRECT DISCHARGE UNIT

Summary of Contents for HYDRO-GUARD 200 Series

Page 1: ...elieved 4 Always use all necessary safety equipment and follow all recommended procedures when installing operating and maintaining the Hydro Guard Automatic Flushing Device 5 Replace worn or defective parts with OEM parts and check your battery twice a year 6 Operate the Hydro Guard Automatic Flushing Device only when fully installed and correctly assembled 7 It is recommended that a pressure red...

Page 2: ...Hydro Guard Unit into place pressing it firmly into the noncompacted bedding material until it is fully seated 4 Connect the utility s water system to the Hydro Guard Unit by means of the 2 threaded connection Ensure that Unit is level before beginning the backfilling operation to the installation of the device the drainage patterns for the intended installation location should be reviewed The dra...

Page 3: ...nch the application on your Smartphone or Tablet 4 Associate the controller with your phone by tapping the Add a Controller button 5 The app will now ask what type of Bluetooth device you would like to add 200 SERIES WARM CLIMATE HIGH PROFILE DIRECT DISCHARGE UNIT Programming Unit PROGRAMMING HYDRO GUARD UNIT FOR OPERATION Discharged water flushed from the Hydro Guard Unit must be routed away from...

Page 4: ...ray and connect the battery connector to controller 3 Make sure no water is inside battery compartment 4 Screw the NODE rear body back onto front half NOTE Make sure that seal marker on rear half of the NODE lines up with front half ensuring a proper seal is created Also The NODE has non volatile memory which allows battery replacement without losing program information Idle Mode Waking Up Normall...

Page 5: ...lush for a different program if desired 5 Press RETURN ENTER key to proceed to next programming function or allow controller to return to Idle mode Manual Flushing Manual flushing allows user to test the Hydro Guard unit or a program for a specified run time Make sure controller is in Idle Mode 1 Press and hold RIGHT ARROW until HAND icon is displayed The station number always 1 will be displayed ...

Page 6: ... Warm Climate Direct Discharge Unit The following is a brief overview and introduction to Hydro Guard Options Sample Station Included A standard feature on the 200 Series Warm Climate High Profile Direct Discharge Unit is the sample port which allows Hydro Guard s Portable Sample Valve Part HG S 1167 to attach to the sample port to obtain a sample Slip off the sanitary blue cap attach the quick co...

Page 7: ...allow for required service and maintenance If disassembly is necessary please follow the directions below Always close the curb stop before working on the unit 200 Series Warm Climate Removal of Internal Compo nents FOR AIR GAP MODEL 1 Shut off water supply and secure isolation valve 2 Remove the housing cover by tilting the housing upward while lifting slightly on its end Once the retaining pin l...

Page 8: ...enoid will not close Try this Correction Run a manual flush for 1 minute Change batteries Check connections for corrosion breaks or lack of connection Check the adapters and solenoid for debris Run the electrical systems check Refer to valve troubleshooting for possible corrective measures Check the water pressure at the unit The pressure must be in the operating range of the solenoid and programm...

Page 9: ...Gap 6 Receiver Pipe By Others Dechlorination System BlueTooth or NODE Controller Integrated Program Mueller Curb Box Optional Mueller 2 Curb Stop Optional Quick Disconnect Supply Line By Others Quick Connect HG S116B Portable Sample Valve Optional SCH 80 PVC Internal Piping Brass Optional 200 SERIES WARM CLIMATE HIGH PROFILE DIRECT DISCHARGE UNIT ...

Page 10: ...ipe Release Light Green Enclosure ID PART NUMBER DESCRIPTION 1 HG 15100 LG Enclosure 2 HG DECHLORHG2 HP Dechlorination Chamber 3 HG 123100 2 Composite Control Valve 4 546589 NODE Controller Assembly Programming Option 5 HG S302 BlueTooth Controller Programming Option 6 546767 200 Series Warm High Profile Replacement Piping Assembly 7 HG 15113 P Key Enclosure Security 8 HG S294 HG2 TCV Assembly 1 2...

Page 11: ...11 Notes 200 SERIES WARM CLIMATE HIGH PROFILE DIRECT DISCHARGE UNIT ...

Page 12: ...ter Products Inc All Rights Reserved The trademarks logos and service marks displayed in this document are the property of Mueller Water Products Inc its affiliates or other third parties Products marked with a section symbol are subject to patents or patent applications For details visit www mwppat com These products are intended for use in potable water applications Please contact your Mueller S...

Reviews: