685 – AL Lube Oil Min
Red alarm.
Associated parameter 1.1480.307
Cause
Corrective action
Minimum engine oil filling level
detected.
1. Check engine oil level (→ Page 153).
2. Check replenishment system.
3. Fill oil.
686 – AL Lube Oil Max
Red alarm.
Associated parameter 1.1480.309
Cause
Corrective action
Maximum engine oil filling level
detected.
1. Check engine oil level (→ Page 153).
2. Check replenishment system.
3. Drain oil.
688 – LO Oil Refill
Yellow alarm.
Associated parameter 1.1480.301
Cause
Corrective action
No oil replenishment within a
programmable time.
u
Check oil replenishment system.
689 – HI Oil Refill
Yellow alarm.
Associated parameter 1.1480.303
Cause
Corrective action
Engine oil was refilled too often
within a certain time interval.
u
Check engine oil level (→ Page 153). Check oil supply.
691 – HI Lube Oil Level Refill.
Yellow alarm.
Associated parameter 1.1480.311
Cause
Corrective action
Engine oil was refilled too often
within a certain time interval.
u
Check engine oil level. Check oil supply.