Fig. 30: Determine start and end position
2. Set start position (0 % output) (Fig. 30):
• Set the position magnet to start position
• Press and release the “0 %” button
3. Set end position (100 % output) (Fig. 30):
• Set the position magnet to end position
• Press and release the “100 %” button
4. Back to normal function (operation mode):
• Press and release the “Start” button
• LED “Programming mode” stops flashing
• Slide switch to “Run”
• Green LED “24 VDC” shows normal function
Output 1
Output 2
Output from
order code
Start posi-
tion (0 %
output)
End positi-
on (100 %
output)
Start posi-
tion (0 %
output)
End positi-
on (100 %
output)
V01
0 VDC
10 VDC
—
—
V11
10 VDC
0 VDC
—
—
V03
0 VDC
10 VDC
10 VDC
0 VDC
V02
0 VDC
10 VDC
0 VDC *
10 VDC *
V12
10 VDC
0 VDC
10 VDC *
0 VDC *
A01
4 mA
20 mA
—
—
A11
20 mA
4 mA
—
—
A03
4 mA
20 mA
20 mA
4 mA
A02
4 mA
20 mA
4 mA *
20 mA *
A12
20 mA
4 mA
20 mA *
4 mA *
* When using the analog hand programmer only the start and end
positions of magnet 1 (output 1) are adjusted. The settings of
magnet 2 (output 2) are not affected.