HYDROCAL 1005 Manual for Installation and Operation
Page 69/111
Modbus-
Function
Code
Modbus-
Address
Dec. / Hex
Register
Address 1)
(5 Digit Dec.)
HydroCal
0x04
Read
Input
Registers
3000
..
3015
33001
..
33016
Alert status
Alert #1
..
Alert #16
The full alert status information is returned.
0
no alert
1
level 1 alert (not active)
2
level 2 alert (not active)
3
active level 1 alert
4
active level 2 alert
0x04
Read
Input
Registers
4000-
4001
..
4002-
4003
34001 -
34002
..
34003 -
34004
Query ageing rate
Loss-of-Life
in seconds
Time-into-Service
in seconds
A value is returned within 2 MODBUS register as
a 32-bit unsigned integer in big endian format.
0x06
Write
Single
Register
0
..
1
40001
..
40002
Holding Register
Test register #1, #2
To test the write functionality there are 2 registers
that may be modified freely. (The reset initializa-
tion values of the registers are 0xA5A5 and
0x5A5A.)
0x06
Write
Single
Register
1000
41001
Confirmation / Reset of alerts
Alert status #16 .. #1
The alerts are coded as a bit field and are pre-
sented as a single MODBUS register (alert #16 ->
0x8000, alert #1 -> 0x0001).
By writing a '0'-Bit at the corresponding position a
probably active alert can be reset. Writing '0000'
resets all alerts.
0x06
Write
Single
Register
2000
42001
Switch MODBUS protocol off
MODBUS off
It is now possible to switch the MODBUS protocol
off via MODBUS. This is done by writing 0x00FF
(like OFF).
0x03
Read
Holding
Registers
0
..
1
1000
2000
40001
..
40002
41001
42001
Holding Registers
16-Bit test register #1, #2
Alert status bit pattern #16 .. #1
MODBUS protocol status
Remark: The reading is always 0x0000. If the
MODBUS status is OFF it is not possible to read
this status via MODBUS.
1)
Modicon® PLC addressing scheme