26
2. Add 20-30g of diagnostic oil (PAG46yf) to the compressor.
3. Fix the compressor on the test bench as shown in Item 2.3 of the Manual.
4. Select and press «Automatic test».
5. Read Item 2.4 to learn how to perform the procedure in automatic mode
6. Take note of the pressure values in HP and LP lines of the compressor.
7. Upon completion, pump the refrigerant out and dismount the compressor from the bench.
8. Drain the diagnostic oil.
9. Fill the compressor with the factory oil.
5. TEST BENCH MAINTENANCE
To ensure a longtime unfailing performance of a compressor and its objective health assessment,
the Test Bench runs self-diagnostic checks and evaluates the condition of its main components
on a regular basis. During its operation the following messages can be displayed:
• «HP pressure is too low!» (Fig.30). This message appears when the bench operates in autotest
mode and the operator didn’t turn the valve off prior to launching “Productivity Test” or “Noise
Test”.
Figure 30 – Message «PH pressure is too low!»
Operation manual - test bench MS111
English