5.4 Horn / Local Buzzer
The operation of the horn relay has been covered to a large extent in the Alarm, Warning and
Trouble sections of this manual. Table 5.2 is a summary of horn relay/local buzzer function. The
horn relay is always configured to be non-fail safe (normally de-energized) and may not be changed.
The local audible buzzer mounted on the front of the unit duplicates the function of the horn relay.
Table 5.4: Horn Relay / Local Audible Buzzer Functions
Condition
Horn Relay Function
Buzzer Function
Alarm
Energize horn relay
Continuous tone
Warning
Pulsing, Energize horn relay, 2 sec.
De-energize horn relay, 2 sec.
Pulsing tone, 2 sec. ON,
2 sec. OFF (50% Duty)
Trouble
Pulsing, Energize horn relay, 1 sec.
De-energize horn relay, 4 sec.
Pulsing tone, 1 sec. ON,
4 sec. OFF (20% Duty)
Summary of Contents for MultiGard 5000
Page 7: ......
Page 8: ......
Page 99: ...91 Section 4 SENSOR ANALYZER MANUALS Supplied on SD Card...
Page 100: ...92 Section 5 MULTIGARD 5000 SYSTEM SUPPORT DOCUMENTS...
Page 101: ...93...
Page 102: ...94...
Page 103: ...95...
Page 104: ...96...
Page 105: ...97...
Page 106: ...98...
Page 107: ...99...
Page 108: ...100...
Page 109: ...101...
Page 110: ...102...
Page 111: ...103...
Page 112: ...104...
Page 113: ...105...
Page 114: ...106...
Page 115: ...107...
Page 116: ...108...
Page 117: ...109...
Page 118: ...110...
Page 119: ...111...
Page 120: ...112...
Page 121: ...113...
Page 122: ...114...
Page 123: ...115...
Page 124: ...116...
Page 125: ...117...
Page 126: ...118...
Page 127: ...119...
Page 128: ...120...
Page 129: ...121...
Page 130: ...122...
Page 131: ...123...