Model S4000TH
41
Function
Bit Position
Access
Calibration Complete
7 MSB
Read
Spanning 6
Read
Zero Complete, Waiting for Gas
5
Read
Zeroing 4
Read
Calibration Mode
3
Read/Write
Calibration Check Mode
2
Read/Write
Run Mode
1
Read
Startup Mode
0 LSB
Read
8.8.3 Status/Error
(02H)
A read returns the alarm state and errors that are occurring at the present time, which are
indicated, by bit position.
Function
Bit Position
Access
Alarm 15
MSB
Read
Warn 14
Read
Fault 13
Read
Not Used
12
Read
Not Used
11
Read
Not Used
10
Read
Not Used
9
Read
Switch Error
8
Read
Setup Error
7
Read
Calibration Check Timeout
6
Read
EEPROM Error
5
Read
EPROM Error
4
Read
Sensor Error
3
Read
Fail to Calibrate
2
Read
Low Supply Voltage
1
Read
8.8.4 Not Used (03H)
8.8.5 Unit
Type
(04H)
A read returns the decimal value 4005. This identifies the S4000TH.
8.8.6 Software
Revision
(05H)
A read returns the software revision of the S4000TH in 2 ASCII characters.
8.8.7 Status Block (06H)
A read returns a 6-byte message containing the analog (2 bytes), mode (1 byte), status/error
(2 bytes), and sensor life (1 byte) in that order. For the format of each byte, refer to the
appropriate individual commands.
NOTE:
These registers can be read individually or as a group. Only when the starting address
is 06 is a block return.