
Model S4000TH
20
Figure 14: Relay Reset
The relays can be reset via the remote reset input terminals on TB2. Connect a
normally open switch between terminal TB2-7 and TB2-8. Closing the switch
momentarily will reset the relays. General Monitors’ explosion-proof switch, P/N 30051-
1 can be used for this purpose. See Section 9.5 for ordering instructions.
The relays can be reset via the Modbus Interface (Section 8.8.22).
The relays can be reset via the HART communication.
NOTE:
Red LED’s above and below the digital display indicate that the alarm and warn relays
are active. Latching relays can only be reset if the gas concentration has fallen below
the respective relay set point.
4.4 User Selectable Options
The S4000TH includes many selectable options to provide the user with the most flexible H
2
S
gas detector possible. These options include selectable sensor range, warn and alarm relay set
points and configuration, HART communications and Modbus communications settings. These
allow the unit to operate with a wide variety of PLC and DCS systems. The following sections
explain the available options and how they can be customized.
A flow diagram is included to help the user in understanding the process of reviewing and
changing the available options (Figure 15).
NOTE:
If the unit was ordered without relays, HART, or Modbus communications, changing the
relay, HART, or Modbus settings will have no effect on the operation of the unit.
Modbus
Dual
Redundant
Modbus
Single Modbus and HART
HART
HART is a Master to Slave -One to One communication channel.
RGC
The Remote Gas Calibrator (RGC) is an accessory that allows remote calibration.
With this device, the user turns on and off the calibration gas manually.