- 8 -
Actually temp. 37℃, display on 36.9℃, pb value
deduct 0.1
Notice:
Please do not change any parameter value to
avoid affected the machine function.
4.NIGHT TEMPERATURE CONTROL
If you want to use this function of “DAY NIGHT TEMPERATURE TIMER” at
the same time, please turn on the function of “TEMP.TIME SWITCH” first,
then turn th
e function of “DAY NIGHT TEMPERATURE TIMER” by hand
operation and set the required time, finally, to set up the temperature of the
function of “DAY NIGHT TEMPERATURE CONTROL
5. OVER HEAT CONTROL
The knob is for over heat control. Generally, it is set from 5~10
o
C. The
indicator will light when the temperature is higher than the set temperature,
will power off automatically to avoid damage to the machine. It will heat
automatically when the temperature is dropped to the original set-point.
6. OVER LOW CONTROL
R
egarding the setting of the “OVER LOW CONTROL”, it generally is set at a
temperature lower than 5~10
o
C. When the temperature is lower than the set
temperature, the indicator will light and will power off automatically the
compressor. Will start the compressor automatically when the temperature is
rose to the original set-point.
7.DAY NIGHT TEMPERATURE TIMER
It could set temperature for 24 hour (day and night). When a set time comes
to the “TEMP.CONTROL”, it will heat and cool automatically.
How to set up: to turn on the timer switch and adjust the clock to the present
time. There are three sections of the meter switch, the upper one is the
nighttime temperature, the down one is the daytime temperature and the
middle (AUTO) is the automatic timing.
If you want to use the daytime and nighttime at the same time (or for the