6 Mounting
Maschinenfabrik Reinhausen GmbH 2020
55
4453918/14 EN
ETOS
®
TD
6.2 Cable recommendation
Please note the following Maschinenfabrik Reinhausen GmbH recommenda-
tion when wiring the device.
▪ Excessive line capacitance can prevent the relay contacts from interrupt-
ing the contact current. In control circuits operated with alternating current,
take into account the effect of the line capacitance of long control cables
on the function of the relay contacts.
▪ If you want to route Ethernet connections from a control cabinet or build-
ing, we recommend using fiber-optic cables (in accordance with the
IEC 61850-90-4 recommendation).
▪ Ensure that the copper cables used have a temperature resistance of
70°C.
Cable
Assembly
Type
Cross section
Material
Max. length
Power supply
X1
Unshielded
2.5 mm²
Copper
-
Voltage measurement
X10 (UI1/3)
Shielded
2.5 mm²
Copper
-
Current measurement
X10 (UI1/3)
Unshielded
4 mm²
Copper
-
Digital signal inputs
DIO 28-15,
DIO 42-20
Shielded
1.5 mm
2
Copper
400 m (<25 Ω/km)
Digital signal outputs*
DIO 28-15,
DIO 42-20
Shielded
1.5 mm
2
Copper
-
Analog signal inputs
X6 (AIO 2/4)
Shielded
1 mm
2
Copper
400 m (<25 Ω/km)
Analog signal outputs
X6 (AIO 2/4)
Shielded
1 mm
2
Copper
-
RS232, SUB-D
CPU I
Shielded
0.25 mm
2
-
25 m
RS485, SUB-D
CPU I
Shielded
0.25 mm
2
-
140 m
CAN bus
CPU I
Shielded
0.75 mm²
-
2000 m (entire
CAN bus)
Ethernet RJ45
CPU I
Min. CAT5,
shielded S/FTP
-
-
100 m
Ethernet FO
MC 2-2, SW 3-3
Duplex LC,
1310 nm
-
2000 m
Grounding connection
Housing
Unshielded
16 mm²
Copper
-
Table 14: Recommendation for connection cables
*) Observe line capacitance, see note above.
6.3 Information about connecting serial interfaces RS232 and
RS485
NOTICE
Damage to the device!
Using the wrong data cable may damage the device.
► Only use data cables which comply with the description below.