WARNING

Air Quality Hazard

• Do not use this heater for heating human living quarters.
• Use of direct-fired heaters in the construction environment can result in exposure to levels of CO, CO2, and NO2 considered

to be hazardous to health and potentially life threatening.

• Do not use in unventilated areas.
• Know the signs of CO and CO2 poisoning.

• Headaches, stinging eyes
• Dizziness, disorientation
• Difficulty breathing, feels of being suffocated

• Proper ventilation air exchange (OSHA 29 CFR 1926.57) to support combustion and maintain acceptable air quality shall be

provided in accordance with OSHA 29 CFR Part 1926.154, ANSI A10.10 Safety Requirements for Temporary and Portable
Space Heating Devices and Equipment used in the Construction Industry or the Natural Gas and Propane Installation Codes
CSA B149.1.

• Periodically monitor levels of CO, CO2 and NO2 existing at the construction site – at the minimum at the start of the

shift and after 4 hours.

• Provide ventilation air exchange, either natural or mechanical, as required to maintain acceptable indoor air quality.

USA 8-Hr Time weighted average

(OSHA 29 CFR 1926.55 App A)

Canada 8-hr time weighted average

WorkSafe BC OHS Guidelines Part 5.1

and Ontario Workplaces Reg 833

CO

50 ppm

25 ppm

CO

2

5000 ppm

5000 ppm

NO

2

3 ppm (Reg 833)

USA – Ceiling Limit

(Short Term Exposure Limit = 15 minutes)

Canada STEL (15 minutes Reg 833/1 hour 

WSBC) WorkSafe BC OHS Guidelines Part 

5.1 and Ontario Workplaces Reg 833

CO

100 ppm

CO

2

15000 ppm (WSBC)

30000 ppm (Reg 833)

NO

2

5 ppm

1.0 ppm (WorkSafeBC)

5.0 ppm (Reg 833)

• Ensure that the flow of combustion and ventilation air exchange cannot become obstructed.
• As the building ‘tightens up’ during the construction phases ventilation may need to be increased.

Installation of this appliance at altitudes above 2000 ft (610 m) shall be in accordance with local codes, or in the absence of local 
codes, the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or National Standard of Canada, Natural Gas and Propane Installation 
Code, CSA B149.1

The heater has been shipped from the factory set up for operation on propane gas.

Summary of Contents for F270500

Page 1: ...nce Extinguish any open flame Shut off gas to appliance Service must be performed by a qualified service agency This is an unvented gas fired portable heater It uses air oxygen from the area in which...

Page 2: ...witter YouTube There are now informational videos on YouTube WEBSITE Mr Heater s full line of product are now at WWW MRHEATER COM WARNING YOUR SAFETY IS IMPORTANT TO YOU AND TO OTHERS SO PLEASE READ T...

Page 3: ...te heater unless the shells are fully extended and locked into position 4 Use only propane gas 5 Use only VAPOR WITHDRAWAL propane supply If there is any question about vapor withdrawal ask your propa...

Page 4: ...d area before you return Properly trained service people must repair any leaks check for further leakages and then relight the appliance for you ODOR FADING NO ODOR DETECTED Some people cannot smell w...

Page 5: ...S AS SHOWN THE HEATER MUST NOT BE OPERATED UNLESS THE OUTER SHELL IS PROPERLY EXTENDED AND FULLY LOCKED INTO PLACE CAUTION NEVER IGNITE AND OR RUN THIS HEATER UNLESS THE SHELLS ARE FULLY EXTENDED AND...

Page 6: ...ithin the heater The flame is essentially yellow with some blue at the base of the fame adjacent to the burner There is no strong disagreeable odor eye burning or other physical discomfort There is no...

Page 7: ...lowest air temperature expected at the bottom of the chart 2 Move straight up to time of operation desired left side of chart 3 Read the cylinder size required All heaters should have full cylinders...

Page 8: ...er Electrode 1 11 28619 Igniter Electrode Bracket 1 12 28620 Pilot Burner Head 1 13 28621 Pilot Burner Orifice 1 14 28622 Pilot Gas Supply line 1 15 28623 Igniter Lead 1 16 20735 Piezo Igniter With Nu...

Page 9: ...85 Burner Cone 1 7 28584 Burner Orifice Holder 1 8 28583 Burner Orifice 1 10 28595 Burner Supply Tube 1 11 28594 Fuel Inlet Supply tube 1 12 28591 Variable Rate Valve Knob 1 13 28587 Valve Control Ass...

Page 10: ...ainer Nut 1 8 28600 Valve With Integrated Piezo Igniter 1 9 28602 Burner Orifice 1 10 28603 Orifice Holder 1 11 28599 Burner Supply Tube 1 12 28610 Inlet Nipple 1 13 N A Inlet Flare fitting 1 14 N A R...

Page 11: ...hours Provide ventilation air exchange either natural or mechanical as required to maintain acceptable indoor air quality USA 8 Hr Time weighted average OSHA 29 CFR 1926 55 App A Canada 8 hr time weig...

Page 12: ...ss for a particular purpose and there is no warranty of merchantability In no event shall the Company be liable for delay caused by imperfections for consequential damages or for any charges of the ex...

Page 13: ...ez l alimentation en gaz l appareil L entretien doit tre effectu par un fournisseur de services d entretien qualifi Cet appareil de chauffage portatif aliment au gaz n est pas ventil Il utilise l oxyg...

Page 14: ...ure pr s du plancher 2pi 2pi 2pi SP CIFICATIONS AVERTISSEMENT VOTRE S CURIT EST IMPORTANTE POUR VOUS ET POUR LES AUTRES PAR CONS QUENT VEUILLEZ LIRE CES DIRECTIVES AVANT DE FAIRE FONCTIONNER CET APPAR...

Page 15: ...et verrouill e en position Consultez la feuille d assemblage pour obtenir les instructions 4 Utilisez uniquement du gaz propane 5 Utilisez uniquement une alimentation au propane LIMINATION DES MANATIO...

Page 16: ...ifier si du gaz s chappe Assurez vous qu ils aient a r l immeuble avant d y retourner Le personnel d entretien exp riment doit colmater toute fuite v rifier la pr sence d autres fuites puis se charger...

Page 17: ...MOINS QUE LES COQUES EXT RIEURES SOIENT COMPL TEMENT OUVERTES ET VERROUILL ES EN POSITION TAPE 1 APPAREIL TEL QUE RE U LA SORTIE DE L EMBALLAGE AVANT DE SOULEVER LA COQUE EXT RIEURE PROT GEZ VOUS LES...

Page 18: ...uyau ait br l 3 Tourner la valve de br leur principale la position basse claire V RIFICATION Un appareil de chauffage qui a t modifi ou qui ne fonctionne pas correctement risque d tre une cause de dan...

Page 19: ...basse pr vue au bas du tableau 2 Allez ensuite directement au haut du tableau au temps d utilisation d sir c t gauche du tableau 3 Notez la dimension de la bonbonne requise Tous les appareils de tre m...

Page 20: ...pport 1 12 28620 Veilleuse Head 1 13 28621 Veilleuse Orifice 1 14 28622 Pilote de ligne d alimentation en gaz 1 15 28623 Lead allumeur 1 16 20735 Allumeur pi zo lectrique avec crou 1 18 28624 Tube Bur...

Page 21: ...fice du br leur 1 8 28583 Orifice du br leur 1 10 28595 Tube Burner Supply 1 11 28594 Le tube d admission de carburant Supply 1 12 28591 taux variable Valve Knob 1 13 28587 Assembl e Valve Control 1 1...

Page 22: ...2 Orifice du br leur 1 10 28603 Titulaire de l orifice 1 11 28599 Tube Burner Supply 1 12 28610 Inlet Nipple 1 13 N A Inlet Flare montage 1 14 N A Cap Caoutchouc 1 15 28591 taux variable Bouton 1 16 2...

Page 23: ...ur maintenir une qualit de l air int rieur acceptable Moyenne pond r e dans le temps sur 8 heures tats Unis OSHA 29 CFR 1926 55 App A Moyenne pond r e dans le temps sur 8 heures Canada Directives SST...

Page 24: ...ar des d fectuosit s ni des dommages indirects ni des d penses encourues sans son consentement crit quelle que soit leur nature Le co t de la r paration ou du remplacement sera le seul recours possibl...

Page 25: ...ue todas las llamas expuestas Corte el suministro de gas al artefacto El mantenimiento debe ser realizado por una agencia de reparaci n calificada Este calentador port til a gas no tiene una fuente pr...

Page 26: ...4 4 32 kg HR Hose Length 10 304 cm 10 304 cm 10 304 cm Figura 1 VENTILACI N Aperturas m nimas necesarias Apertura cerca del piso 2pies 2pies 2pies Apertura cerca del cielorraso 2pies 2pies 2pies ADVER...

Page 27: ...lte la hoja del conjunto adjunta para obtener las instrucciones 4 Utilice nicamente gas propano 5 Utilice nicamente suministro de propano con RECUPERACI N DE VAPOR Si tiene alguna pregunta sobre la re...

Page 28: ...que ventilen el edificio y el rea antes de su regreso Un agente de servicios calificado debe reparar cualquier fuga revisar si hay otras fugas y volver a encender el artefacto por usted DISIPACI N DE...

Page 29: ...DEBE USAR EL CALENTADOR A MENOS QUE LA CARCASA EXTERNA SE ENCUENTRE BIEN EXTENDIDA Y COMPLETAMENTE TRABADA EN SU LUGAR CUIDADO NUNCA ENCIENDA O USE ESTE CALENTADOR A MENOS QUE LAS CARCASAS EST N EXTE...

Page 30: ...aci n original haya sido modificada o si no est funcionando correctamente Cuando el calentador funciona correctamente La llama arde en el interior del calentador La llama es fundamentalmente azul y pu...

Page 31: ...m nima esperada parte inferior del gr fico 2 Ascienda en la vertical hasta encontrar el tiempo de funcionamiento deseado a la izquierda del gr fico 3 Lea el tama o de cilindro requerido Todos los cal...

Page 32: ...odo Soporte 1 12 28620 Piloto Quemador Head 1 13 28621 Piloto del orificio del quemador 1 14 28622 Piloto de l nea de suministro de gas 1 15 28623 Conductor del encendedor 1 16 20735 Piezo encendedor...

Page 33: ...orificio 1 8 28583 Orificio del quemador 1 10 28595 Tubo del quemador de alimentaci n 1 11 28594 Tubo de entrada de suministro de combustible 1 12 28591 V lvula de Tasa Variable Perilla 1 13 28587 As...

Page 34: ...ificio del quemador 1 10 28603 Titular de orificio 1 11 28599 Tubo del quemador de alimentaci n 1 12 28610 Boquilla de entrada 1 13 N A Entrada de la llamarada ajuste 1 14 N A Funda de caucho 1 15 285...

Page 35: ...table del aire interior EE UU Promedio ponderado de 8 horas OSHA 29 CFR 1926 55 App A Canad Promedio ponderado de 8 horas Recomendaciones WorkSafe BC OHS Par te 5 1 y Reglamentaciones para lugares de...

Page 36: ...la adecuaci n para un prop sito particular y no hay garant as de comerciabilidad En ning n caso la Compa a ser responsable por demoras causadas por imperfecciones por da os consecuentes ni por ning n...

Reviews: