DCA15SPXU4F • OPERATION MANUAL — REV. #1 (02/10/17) — PAGE 33
MAINTENANCE
RADIATOR CLEANING
The radiator (Figure 41) should be sprayed (cleaned) with
a high pressure washer when excessive amounts of dirt
and debris have accumulated on the cooling fins or tube.
When using a high pressure washer, stand at least 5 feet
(1.5 meters) away from the radiator to prevent damage to
the fins and tube.
Figure 41. Radiator Cleaning
GENERATOR STORAGE
For long term storage of the generator the following is
recommended:
Drain the fuel tank completely. Treat with a fuel stabilizer
if necessary.
Completely drain the oil from the crankcase and refill if
necessary with fresh oil.
Clean the entire generator, internal and external.
Cover the generating set and store in a clean, dry place.
Disconnect the battery.
Make sure engine coolant is at proper level.
If generator is mounted on a trailer, jack trailer up and
place on blocks so tires do not touch the ground or block
and completely remove the tires.
ENGINE BLOCK HEATING ELEMENT AND
INTERNAL BATTERY CHARGER 120 VAC INPUT
RECEPTACLES (OPTIONAL)
This generator can be optionally equipped with two 120
VAC, 20 amp input receptacles located on the output
terminal panel.
The purpose of these receptacles is to provide power via
commercial power to the
engine block heating element
and
internal battery charger.
These receptacles will
ONLY
function when commercial
power has been supplied to them (Figure 42). To apply
commercial power to these receptacles, a power cord of
adequate size will be required (See Table 6).
When using the generator in
hot
climates there is no
reason to apply power to jacket water heater. However, if the
generator will be used in
cold
climates, it is always a good
idea to apply power to the jacket water heater at all times.
To apply power to the engine block heating element, simply
apply power to the heating element receptacle via
commercial power using a power cord of adequate size.
Figure 42. Battery Charger and Engine Block
Heating Element Power Connections
If the generator will be used daily, the battery should
normally not require charging. If the generator will be idle
(not used) for long periods of time, apply power to the
battery charger receptacle via commercial power using a
power cord of adequate size.
NOTICE
To ensure adequate starting capability, always have
power applied to the generator's internal battery
charger.
Summary of Contents for WHISPERWATT Series
Page 38: ...PAGE 38 DCA15SPXU4F OPERATION MANUAL REV 1 02 10 17 GENERATOR WIRING DIAGRAM ...
Page 39: ...DCA15SPXU4F OPERATION MANUAL REV 1 02 10 17 PAGE 39 ENGINE WIRING DIAGRAM ...
Page 40: ...PAGE 40 DCA15SPXU4F OPERATION MANUAL REV 1 02 10 17 BATTERY CHARGER WIRING DIAGRAM ...
Page 41: ...DCA15SPXU4F OPERATION MANUAL REV 1 02 10 17 PAGE 41 ENGINE BLOCK HEATER WIRING DIAGRAM ...