PAGE 20 — DCA15SPXU4F • OPERATION MANUAL — REV. #1 (02/10/17)
OUTPUT TERMINAL PANEL FAMILIARIZATION
Connecting Loads
Loads can be connected to the generator by various
methods, output terminal lugs, camlocks or the convenience
receptacles (Figure 9). Make sure to read the operation
manual before attempting to connect a load to the generator.
To protect the output terminals from overload, a 3-pole,
70A
main
circuit breaker is provided. Make sure to switch
ALL
circuit breakers to the
OFF
position prior to starting
the engine.
Figure 9. Connecting Loads
Over Current Relay
An
over current relay
(Figure 10) is connected to the main
circuit breaker. In the event of an overload, both the circuit
breaker and the over current relay may trip. If the circuit
breaker can not be reset, the
reset button
on the over
current relay must be pressed. The over current relay is
located in the control box.
Figure 10. Over Current Relay
NOTICE
Remember the
overcurrent relay
monitors the current
flowing from the
U, N and V Output Terminal Lugs
to
the load.
In the event of a short circuit or over current condition,
it will automatically trip the 70 amp main breaker.
To restore power to the
Output Terminal Panel
, press
the reset button on the overcurrent relay and place the
main
circuit breaker in the
closed
position (
ON
).
Summary of Contents for WHISPERWATT Series
Page 38: ...PAGE 38 DCA15SPXU4F OPERATION MANUAL REV 1 02 10 17 GENERATOR WIRING DIAGRAM ...
Page 39: ...DCA15SPXU4F OPERATION MANUAL REV 1 02 10 17 PAGE 39 ENGINE WIRING DIAGRAM ...
Page 40: ...PAGE 40 DCA15SPXU4F OPERATION MANUAL REV 1 02 10 17 BATTERY CHARGER WIRING DIAGRAM ...
Page 41: ...DCA15SPXU4F OPERATION MANUAL REV 1 02 10 17 PAGE 41 ENGINE BLOCK HEATER WIRING DIAGRAM ...