19
23
Bypass function:
Bypass disable
If selected and power ON button is
pressed on, inverter can work in
bypass/ECO mode only if utility is
available.
Bypass enable (default)
If selected and no matter power ON
button is pressed on or not, inverter
can work in bypass mode if utility is
available.
25
Record Fault code
Record enable
Record disable (default)
26
Bulk charging voltage
(C.V voltage)
3KW default setting: 28.2V
5KW default setting: 56.4V
If self-defined is selected in program 5, this program can be set
up. Setting range is from 24.0V to 32.0V for 3KW model and 48.0V
to 64.0V for 5KW model. Increment of each click is 0.1V.
27
Floating charging voltage
3KW default setting: 27.0V
5KW default setting: 54.0V
If self-defined is selected in program 5, this program can be set
up. Setting range is from 24.0V to 32.0V for 3KW model and 48.0V
to 64.0V for 5KW model. Increment of each click is 0.1V.
28
AC output mode
*This setting is able to set
up only when the inverter is
in standby mode, Be sure
that on/off Switch is
in ”OFF” status.
Single
When the unit is operated alone,
please select “SIG” in program 28.
Parallel
When the units are used in parallel
for single phase application, please
select “PAL” in program 28. Please
refer to 5-1 for detailed information.