5. Wiring Connection
The cable size of each inverter is shown as below:
Recommended battery cable and terminal size for each inverter:
Model
Wire Size
Ring Terminal
Torque
value
Cable
mm
2
Dimensions
D (mm)
L (mm)
3KW
1*1/0AWG
60
6.4
49.7
2~ 3 Nm
2*4AWG
44
6.4
49.7
5KW
1*1/0AWG
60
6.4
49.7
2~ 3 Nm
2 * 4AWG
44
6.4
49.7
WARNING:
Be sure the length of all battery cables is the same. Otherwise, there will be voltage difference
between inverter and battery to cause parallel inverters not working.
Recommended AC input and output cable size for each inverter:
Model
AWG no.
Torque
3KW
10 AWG
1.2~1.6Nm
5KW
8 AWG
1.4~1.6Nm
You need to connect the cables of each inverter together. Take the battery cables for example: You need to use
a connector or bus-bar as a joint to connect the battery cables together, and then connect to the battery
terminal. The cable size used from joint to battery should be X times cable size in the tables above. “X” indicates
the number of inverters connected in parallel.
Regarding AC input and output, please also follow the same principle.
CAUTION!!
Please install the breaker at the battery and AC input side. This will ensure the inverter can be
securely disconnected during maintenance and fully protected from over current of battery or AC input. The
recommended mounted location of the breakers is shown in the figures in 5-1 and 5-2.
Recommended breaker specification of battery for each inverter:
Model
1 unit*
3KW
150A/60VDC
5KW
125A/80VDC
*If you want to use only one breaker at the battery side for the whole system, the rating of the breaker should
be X times current of 1 unit. “X” indicates the number of inverters connected in parallel.
Recommended breaker specification of AC input:
Model
2 units
3 units
4 units
5 units
6 units
7 units
8 units
9 units
3KW
80A
120A
160A
200A
240A
280A
320A
360A
5KW
100A
150A
200A
250A
300A
350A
400A
450A
Note1:
Also, you can use 40A breaker for 3KW and 50A for 5KW for only 1 unit and install one breaker at its AC
input in each inverter.
Note2:
Regarding three-phase system, you can use 4-pole breaker directly and the rating of the breaker
should be compatible with the phase current limitation from the phase with maximum units
Ring terminal: