The Pump Monitor Relay  provides Motor Over Temperature and 
Seal Leakage alarms for Submersible Pumps.

 

 

Motor  Over  Temperature  Alarm

  

 

-

 The unit applies a low voltage 

DC signal to the Motor Thermal Sensor to check its status.  If the 
unit  detects  that  the  Motor  Thermal  Sensor  contacts  are  closed 
(normal  condition),  the  Overtemp  indication  remains  off,  and  the 
Overtemp  Relay  is  energized  closing  the  contacts  between 
terminals 2 and 11.  

 

 

If  the  Motor  Thermal  Sensor  contacts  open  (Over  Temperature 
condition),  the  Overtemp  Indication  is  turned  on  and  the 
Overtemp  Alarm  Relay  is  de

-

energized  opening  the  contacts 

between  terminals  2  and  11  and  closing  the  contacts  between 
terminals 2 and 1. 

 

 

When the High Motor Temperature condition has cleared, the unit 
will  reset  based  on  the  position  of  Alarm  Reset  Mode  Select 
Switch  (Auto  or  Manual).    When  in  the  Auto  position,  the 
Overtemp  Alarm  resets  automatically.    If  the  switch  is  in  the 
Manual  position,  the  Overtemp  Reset  Push

-

button  must  be 

pushed for approximately 1.5 seconds to clear the alarm. 

 

 

Seal  Leakage  Alarm

  

 

-

  The  unit  detects  moisture  inside  a  pump 

motor by using a low voltage AC signal to measure the resistance 
between  a  single  (or  dual)  Leakage  Probe(s)  and  the  grounded 
motor housing, or across two Leakage Probes.  A Seal Leakage 
condition  is  considered  present  when  the  amount  of  moisture  in 
the motor causes the resistance between terminal 6 and 5 to drop 
below the setting on the potentiometer.  When this occurs the unit 
turns  on  the  Leakage  Indication  and  energizes  the  Leakage 
Alarm Relay closing the contacts between terminals 9 and 10. 

 

  

 

The  alarm  trip  point  may  be  set  by  the  following  procedure:  
Isolate the Leakage Probe(s) from terminals 5 and 6.  Connect a 
resistor,  with  the  desired  trip  value,  across  terminals  5  and  6.  
Slowly adjust the potentiometer to the point where the alarm turns 
on.  Remove the resistor and reconnect to the Leakage Probe(s).

 

OPERATION

 

P

ump 

M

onitor 

R

elay PMR1

 

Input Power: 

 

Output Rating:

 

Operating Temp:

 

Storage Temp:

 

Temp Sensor Voltage:

 

Leak Sensor Voltage: 

 

Enclosure:

 

Base:

 

120 VAC ±10%,  7.0 VA max

 

8A Resistive @ 120VAC

 

-

20°C to +65 °C

 

-

45°C to +85 °C

 

6.6 VDC ±10%

 

4.7 VAC ±10%

 

White Lexan

 

Phenolic

 

ORDERING INFORMATION

 

 

                

Part Number:

   

PMR1

 

 

SPECIFICATIONS

 

UL FILE #E101681

 

2464 Vulcan Road, Apopka, Florida 32703  

 

  

(

407) 299

-

3825  

  

www.mpelectronics.com

 

MADE IN

 

THE U.S.A.

 