ATD Actuator
®
Troubleshooting Guide
Symptom
Solutions
Door does not move
1) Check Power to Unit
x
Blown Supply Fuse supplying power to ATD
x
Power Cable plugged into selector switch inside
x
Selector switch set to correct voltage (115 or 230
VAC). If wrong voltage is selected the control or
power module will be damaged!
x
Is the supply voltage too high or too low (+/- 10%)
2) Correct Wiring
x
Correct signals to correct wiring terminals
x
External wiring error from relay, pushbutton, etc.
x
Is relay, pushbutton, etc. working correctly
x
Check to verify that no external voltage is present on
the signal wires
x
The signal wire is properly connected to the terminal
x
Verify that the wires are not damaged
x
Is the ribbon cable from the input signal board to the
ATD control module (ATD 50 and 101) plugged in
properly
x
Are the quick-connect wire terminals plugged in
properly
x
Are the quick-connect terminals plugged into the
correct location
Control Module Functioning Properly
x
Are all the cables (encoder, brake, output relay
module) all plugged into the Control Module
x
Is the Green LED Lighted (ATD 50 and 101 on Control
Module. ATD 100 on Power Module)
x
Yes – Go to #2 below
x
No – Is Red LED Illuminate
x
Yes – Emergency Stop is active or there is
a problem with the Control / Power Module.
Check the Diagnostics Screen for
information.
26